4101:1-4-01 Special detailed requirements based on use and occupancy.  

  • Text Box: ACTION: Final Text Box: DATE: 02/02/2007 1:03 PM

     

     

     

     

     

     

    4101:1-4-01   Special detailed requirements based on use and occupancy.

     

    [Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:1-35-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.4 of rule 4101:1-1-01 of the Administrative Code.]

     

    SECTION 401 SCOPE

    401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code, the provisions of this chapter apply to the special uses and occupancies described herein.

     

     

    SECTION 402 COVERED MALL BUILDINGS

    402.1Scope. The provisions of this section shall apply to buildings or structures defined herein as covered mall buildings not exceeding three floor levels at any point nor more than three stories above grade plane. Except as specifically required by this section, covered mall buildings shall meet applicable provisions of this code.

    Exceptions:

    1. Foyers and lobbies of Groups B, R-1 and R-2 are not required to comply with this section.

    2. Buildings need not comply with the provisions of this section when they totally comply with other applicable provisions of this code.

    402.2Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.

    ANCHOR BUILDING. An exterior perimeter building of a group other than H having direct access to a covered mall building but having required means of egress independent of the mall.

    COVERED MALL BUILDING. A single building enclosing a number of tenants and occupants such as retail stores, drinking and dining establishments, entertainment and amusement facilities, passenger transportation terminals, offices, and other similar uses wherein two or more tenants have a main entrance into one or more malls. For the purpose of this chapter, anchor buildings shall not be considered as a part of the covered mall building.

    FOOD COURT. A public seating area located in the mall that serves adjacent food preparation tenant spaces.

    GROSS LEASABLE AREA. The total floor area designed for tenant occupancy and exclusive use. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. All tenant areas, including areas used for storage, shall be included in calculating gross leasable area.

    MALL. A roofed or covered common pedestrian area within a covered mall

     

     

     

     

     

     

     

     

    building that serves as access for two or more tenants and not to exceed three levels that are open to each other.

    402.3Lease plan. Each covered mall building owner shall provide both the building and fire departments with a lease plan, to the extent known, showing the location of each occupancy and its exits before the certificate of occupancy is  issued. As a condition of the certificate of occupancy, such plans shall be kept current by the owner. No modifications or changes in occupancy or use shall be made from that shown on the lease plan without prior approval of the building official.

    402.4Means of egress. Each tenant space and the covered mall building shall be provided with means of egress as required by this section and this code. Where there is a conflict between the requirements of this code and the requirements of this section, the requirements of this section shall apply.

    402.4.1Determination of occupant load. The occupant load permitted in any individual tenant space in a covered mall building shall be determined as required by this code. Means of egress requirements for individual tenant spaces shall be based on the occupant load thus determined.

    402.4.1.1Occupant formula. In determining required means of egress of the mall, the number of occupants for whom means of egress are to be provided shall be based on gross leasable area of the covered mall building (excluding anchor buildings) and the occupant load factor as determined by the following equation.

    OLF = (0.00007) (GLA) + 25       (Equation 4-1)

    where:

    OLF= The occupant load factor (square feet per per-son).  GLA= The gross leasable area (square feet).

    402.4.1.2OLF range. The occupant load factor (OLF) is not required to be less than 30 and shall not exceed 50.

    402.4.1.3Anchor buildings. The occupant load of anchor buildings opening into the mall shall not be included in computing the total number of occupants for the mall.

    402.4.1.4Food courts. The occupant load of a food court shall be determined in accordance with Section 1004. For the purposes of determining the means of egress requirements for the mall, the food court occupant load shall be added to the occupant load of the covered mall building as calculated above.

    402.4.2Number of means of egress. Wherever the distance of travel to the mall from any location within a tenant space used by persons other than employees exceeds 75 feet (22 860 mm) or the tenant space has an occupant load of 50 or more, not less than two means of egress shall be provided.

    402.4.3Arrangements of means of egress. Assembly occupancies with an occupant load of 500 or more shall be so located in the covered mall building that their entrance will be immediately adjacent to a principal entrance to the mall and shall have not less than one-half of their required means of egress opening directly to the exterior of the covered mall building.

    402.4.3.1Anchor building means of egress. Required means of egress for

    anchor buildings shall be provided independently from the mall means of egress system. The occupant load of anchor buildings opening into the mall shall not be included in determining means of egress requirements for the mall. The path of egress travel of malls shall not exit through anchor buildings. Malls terminating at an anchor building where no other means of egress has been provided shall be considered as a dead-end mall.

    402.4.4Distance to exits. Within each individual tenant space in a covered mall building, the maximum distance of travel from any point to an exit or entrance to the mall shall not exceed 200 feet (60 960 mm).

    The maximum distance of travel from any point within a mall to an exit shall not exceed 200 feet (60 960 mm).

    402.4.5Access to exits. Where more than one exit is required, they shall be so arranged that it is possible to travel in either direction from any point in a mall to separate exits. The minimum width of an exit passageway or corridor from a mall shall be 66 inches (1676 mm).

    Exception: Dead ends not exceeding a length equal to twice the width of the mall measured at the narrowest location within the dead-end portion of the mall.

    402.4.5.1Exit passageways. Where exit passageways provide a secondary means of egress from a tenant space, doorways to the exit passageway shall be protected by 1-hour fire door assemblies that are self- or  automatic closing by smoke detection in accordance with Section 715.4.7.3.

    402.4.6Service areas fronting on exit passageways. Mechanical rooms, electrical rooms, building service areas and service elevators are permitted to open directly into exit passageways, provided the exit passageway is separated from such rooms with not less than 1-hour fire-resistance-rated fire barriers and 1-hour opening protectives.

    402.5Mall width. For the purpose of providing required egress, malls are permitted to be considered as corridors but need not comply with the requirements of Section 1005.1 of this code where the width of the mall is as specified in this section.

    402.5.1Minimum width. The minimum width of the mall shall be 20 feet (6096 mm). The mall width shall be sufficient to accommodate the occupant load served. There shall be a minimum of 10 feet (3048 mm) clear exit width to a height of 8 feet (2438 mm) between any projection of a tenant space bordering the mall and the nearest kiosk, vending machine, bench, display opening, food court or other obstruction to means of egress travel.

    402.6Types of construction. The area of any covered mall building, including anchor buildings, of Type I, II, III and IV construction, shall not be limited provided the covered mall building and attached anchor buildings and parking garages are surrounded on all sides by a permanent open space of not less than 60 feet (18 288 mm) and the anchor buildings do not exceed three stories in height. The allowable height and area of anchor buildings greater than three stores in height shall comply with Section 503, as modified by Sections 504 and 506. The construction type of open parking garages and enclosed parking garages shall comply with Sections 406.3 and 406.4, respectively.

    402.7Fire-resistance-rated separation. Fire-resistance-rated separation is not required between tenant spaces and the mall. Fire-resistance-rated separation is

    not required between a food court and adjacent tenant spaces or the mall.

    402.7.1Attached garage. An attached garage for the storage of passenger vehicles having a capacity of not more than nine persons and open parking garages shall be considered as a separate building where it is separated from the covered mall building by a fire barrier having a fire-resistance rating of at least 2 hours.

    Exception: Where an open parking garage or enclosed parking garage is separated from the covered mall building or anchor building a distance greater than 10 feet (3048 mm), the provisions of Table 602 shall apply. Pedestrian walkways and tunnels which attach the open parking garage or enclosed parking garage to the covered mall building or anchor building shall be constructed in accordance with Section 3104.

    402.7.2Tenant separations. Each tenant space shall be separated from other tenant spaces by a fire partition complying with Section 708. A tenant separation wall is not required between any tenant space and the mall.

    402.7.3Anchor building separation. An anchor building shall be separated from the covered mall building by fire walls complying with Section 705.

    Exception: Anchor buildings of not more than three stories above grade plane that have an occupancy classification the same as that permitted for tenants of the covered mall building shall be separated by 2-hour fire- resistive fire barriers complying with Section 706.

    402.7.3.1 Openings between anchor building and mall. Except for the separation between Group R-1 sleeping units and the mall, openings between anchor buildings of Type IA, IB, IIA and IIB construction and the mall need not be protected.

    402.8Automatic sprinkler system. The covered mall building and buildings connected shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, which shall comply with the following:

    1.    The automatic sprinkler system shall be complete and operative throughout occupied space in the covered mall building prior to occupancy of any of the tenant spaces. Unoccupied tenant spaces shall be similarly protected unless provided with approved alternate protection.

    2.    Sprinkler protection for the mall shall be independent from that provided for tenant spaces or anchors. Where tenant spaces are supplied by the same system, they shall be independently controlled.

    Exception: An automatic sprinkler system shall not be required in spaces or areas of open parking garages constructed in accordance with Section 406.2 and 406.3.

    402.8.1 Standpipe system. The covered mall building shall be equipped throughout with a standpipe system as required by Section 905.3.3.

    402.9Smoke control. A smoke control system shall be provided where required for atriums in Section 404.

    402.10Kiosks. Kiosks and similar structures (temporary or permanent) shall meet the following requirements:

    1.    Combustible kiosks or other structures shall not be located within the mall unless constructed of any of the following materials:

    1.1.Fire-retardant-treated wood complying with Section 2303.2.

    1.2.Foam plastics having a maximum heat release rate not greater than 100kW (105 Btu/h) when tested in accordance with the exhibit booth protocol in UL 1975.

    1.3.Aluminum composite material (ACM) having a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84.

    2.    Kiosks or similar structures located within the mall shall be provided with approved fire suppression and detection devices.

    3.    The minimum horizontal separation between kiosks or groupings thereof and other structures within the mall shall be 20 feet (6096 mm).

    4.    Each kiosk or similar structure or groupings thereof shall have a maximum area of 300 square feet (28 m2).

    402.11Children's playground structures. Structures intended as children's playgrounds that exceed 10 feet (3048 mm) in height and 150 square feet (14 m2) in area shall comply with the following.

    402.11.1Materials. Children's playground structures shall be constructed of noncombustible materials or of combustible materials that comply with the following:

    1. Fire-retardant-treated wood.

    2. Light-transmitting plastics complying with Section 2606.

    3. Foam plastics (including the pipe foam used in soft-contained play equipment structures) having a maximum heat-release rate not greater than 100 kW when tested in accordance with UL 1975.

    4. Aluminum composite material (ACM) meeting the requirements of Class A interior finish in accordance with Chapter 8 when tested as an assembly in the maximum thickness intended for use.

    5. Textiles and films complying with the flame propagation performance criteria contained in NFPA 701.

    6. Plastic materials used to construct rigid components of soft-contained play equipment structures (such as tubes, windows, panels, junction boxes, pipes, slides and decks) meeting the UL 94 V-2 classification when tested in accordance with UL 94.

    7. Ball pool balls, used in soft-contained play equipment structures, having a maximum heat release rate not greater than 100 kW when tested in accordance with UL 1975. The minimum specimen test size shall be 36 inches by 36 inches (914 mm by 914 mm) by an average of 21 inches (533 mm) deep, and the balls shall be held in a box constructed of galvanized steel poultry netting wire mesh.

    8. Foam plastics shall be covered by a fabric, coating or film meeting the flame propagation performance criteria of NFPA 701.

    9. The floor covering placed under the children's play-ground structure shall exhibit a Class I interior floor finish classification, as described in Section 804, when tested in accordance with NFPA 253.

    402.11.2Fire protection. Children's playground structures located within the mall shall be provided with the same level of approved fire suppression and detection devices required for kiosks and similar structures.

    402.11.3Separation. Children's playground structures shall have a minimum horizontal separation from other structures within the mall of 20 feet (6090 mm).

    402.11.4Area limits. Children's playground structures shall not exceed 300 square feet (28 m2) in area, unless a special investigation has demonstrated adequate fire safety.

    402.12Security grilles and doors. Horizontal sliding or vertical security grilles or doors that are a part of a required means of egress shall conform to the following:

    1.    They shall remain in the full open position during the period of occupancy by the general public.

    2.    Doors or grilles shall not be brought to the closed position when there are 10 or more persons occupying spaces served by a single exit or 50 or more persons occupying spaces served by more than one exit.

    3.    The doors or grilles shall be openable from within with-out the use of any special knowledge or effort where the space is occupied.

    4.    Where two or more exits are required, not more than one-half of the exits shall be permitted to include either a horizontal sliding or vertical rolling grille or door.

    402.13Standby power. Covered mall buildings exceeding 50,000 square feet (4645 m2) shall be provided with standby power systems that are capable of operating the emergency voice/alarm communication system.

    402.14Emergency voice/alarm communication system. Covered mall buildings exceeding 50,000 square feet (4645 m2) in total floor area shall be provided with an emergency voice/alarm communication system. Emergency voice/alarm communication systems serving a mall, required or otherwise, shall be accessible

    to the fire department. The system shall be provided in accordance with Section 907.2.12.2.

    402.15Plastic signs. Plastic signs affixed to the storefront of any tenant space facing the mall shall be limited as specified in Sections 402.15.1 through 402.15.5.2.

    402.15.1Area. Plastic signs shall not exceed 20 percent of the wall area facing the mall.

    402.15.2Height and width. Plastic signs shall not exceed a height of 36 inches (914 mm), except if the sign is vertical, the height shall not exceed 96 inches (2438 mm) and the width shall not exceed 36 inches (914 mm).

    402.15.3Location. Plastic signs shall be located a minimum distance of 18 inches (457 mm) from adjacent tenants.

    402.15.4Plastics other than foam plastics. Plastics other than foam plastics used in signs shall be light-transmitting plastics complying with Section 2606.4 or shall have a self-ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D 1929, and a flame spread index not greater than 75 and smoke-developed index not greater than 450 when tested in the manner intended for use in accordance with ASTM E 84 or meet the acceptance criteria of Section 803.2.1 when tested in accordance with NFPA 286.

    402.15.4.1 Encasement. Edges and backs of plastic signs in the mall shall be fully encased in metal.

    402.15.5Foam plastics. Foam plastics used in signs shall have flame-retardant characteristics such that the sign has a maximum heat-release rate of 150 kilowatts when tested in accordance with UL 1975 and the foam plastics shall have the physical characteristics specified in this section. Foam plastics used in signs installed in accordance with Section 402.14 shall not be required to comply with the flame spread and smoke-developed indexes specified in Section 2603.3.

    402.15.5.1Density. The minimum density of foam plastics used in signs shall not be less than 20 pounds per cubic foot (pcf) (320 kg/m3).

    402.15.5.2Thickness.  The  thickness  of  foam  plastic  signs  shall  not  be greater than 1/2 inch (12.7 mm).

    402.16 Fire department access to equipment. Rooms or areas containing controls for air-conditioning systems, automatic fire-extinguishing systems or other detection, suppression or control elements shall be identified for use by the fire department.

    SECTION 403 HIGH-RISE BUILDINGS

    403.1Applicability. The provisions of this section shall apply to buildings with an occupied floor located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access.

    Exception: The provisions of this section shall not apply to the following buildings and structures:

    1. Airport traffic control towers in accordance with Section 412.

    2. Open parking garages in accordance with Section 406.3.

    3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1.

    4. Low-hazard special industrial occupancies in accordance with Section 503.1.1.

    5. Buildings with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 415.

    403.2Automatic sprinkler system. Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and a secondary water supply where required by Section 903.3.5.2.

    Exception: An automatic sprinkler system shall not be required in spaces or areas of:

    1. Open parking garages in accordance with Section 406.3.

    2. Telecommunications equipment buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic fire detection system in accordance with Section 907.2 and are separated from the remainder of the building by fire barriers consisting of not less than 1-hour fire-resistance- rated walls and 2-hour fire-resistance-rated floor/ceiling assemblies.

    403.3Reduction in fire-resistance rating. The fire-resistance-rating reductions

    listed in Sections 403.3.1 and 403.3.2 shall be allowed in buildings that have sprinkler control valves equipped with supervisory initiating devices and water- flow initiating devices for each floor.

    403.3.1Type of construction. The following reductions in the minimum construction type allowed in Table 601 shall be allowed as provided in Section 403.3:

    1. For  buildings  not  greater  than  420  feet  (128  m)  in  height,  Type  IA construction shall be allowed to be reduced to Type IB.

    Exception: The required fire-resistance rating of columns supporting floors shall not be allowed to be reduced.

    2. In other than Groups F-1, M and S-1, Type IB construction shall be allowed to be reduced to Type IIA.

    3. The height and area limitations of the reduced construction type shall be allowed to be the same as for the original construction type.

    403.3.2Shaft enclosures. For buildings not greater than 420 feet (128 m) in height, the required fire-resistance rating of the fire barriers enclosing vertical shafts, other than exit enclosures and elevator hoistway enclosures, shall be reduced to 1 hour where automatic sprinklers are installed within the shafts at the top and at alternate floor levels.

    403.4Emergency escape and rescue. Emergency escape and rescue openings required by Section 1026 are not required.

    403.5Automatic fire detection. Smoke detection shall be provided in accordance with Section 907.2.12.1.

    403.6Emergency voice/alarm communication systems. An emergency voice/alarm communication system shall be provided in accordance with Section 907.2.12.2.

    403.7Fire department communications system. A two-way fire department communications system shall be provided for fire department use in accordance with Section 907.2.12.3.

    403.8Fire command. A fire command center complying with Section 911 shall be provided in a location approved by the fire department.

    403.9Elevators. Elevator operation and installation shall be in accordance with Chapter 30.

    403.10Standby power. A standby power system complying with Section 2702 shall be provided for standby power loads specified in Section 403.10.2.

    403.10.1Special requirements for standby power systems. If the standby system is a generator set inside a building, the system shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 706 or horizontal assemblies constructed in accordance with Section 711, or both. System supervision with manual start and transfer features shall be provided at the fire command center.

    403.10.2Standby power loads. The following are classified as standby power loads:

    1. Power and lighting for the fire command center required by Section 403.8;

    2. Electrically powered fire pumps; and

    3. Ventilation and automatic fire detection equipment for smokeproof enclosures.

    Standby power shall be provided for elevators in accordance with Sections 1007.4 and 3003.

    403.11Emergency power systems. An emergency power system complying with Section 2702 shall be provided for emergency power loads specified in Section 403.11.1.

    403.11.1Emergency power loads. The following are classified as emergency power loads:

    1. Exit signs and means of egress illumination required by Chapter 10;

    2. Elevator car lighting;

    3. Emergency voice/alarm communications systems;

    4. Automatic fire detection systems; and

    5. Fire alarm systems.

    403.12Stairway door operation. Stairway doors other than the exit discharge doors shall be permitted to be locked from stairway side. Stairway doors that are locked from the stairway side shall be capable of being unlocked simultaneously without unlatching upon a signal from the fire command center.

    403.12.1Stairway communications system. A telephone or other two-way communications system connected to an approved constantly attended station shall be provided at not less than every fifth floor in each required stairway where the doors to the stairway are locked.

    403.13Smokeproof exit enclosures. Every required stairway serving floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall comply with Sections 909.20 and 1020.1.7.

    403.14Seismic considerations. For seismic considerations, see Chapter 16.

    SECTION 404 ATRIUMS

    404.1General. In other than Group H occupancies, and where permitted by Exception 5 in Section 707.2, the provisions of this section shall apply to buildings or structures containing vertical openings defined herein as "Atriums."

    404.1.1 Definition. The following word and term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning shown herein.

    ATRIUM. An opening connecting two or more stories other than enclosed stairways, elevators, hoistways, escalators, plumbing, electrical, air- conditioning or other equipment, which is closed at the top and not defined as a mall. Stories, as used in this definition, do not include balconies within assembly groups or mezzanines that comply with Section 505.

    404.2Use. The floor of the atrium shall not be used for other than low fire hazard uses and only approved materials and decorations in accordance with the fire code  shall be used in the atrium space.

    Exception: The atrium floor area is permitted to be used for any approved use

    where the individual space is provided with an automatic sprinkler system in accordance with Section 903.3.1.1.

    404.3Automatic sprinkler protection. An approved automatic sprinkler system shall be installed throughout the entire building.

    Exceptions:

    1.That area of a building adjacent to or above the atrium need not be sprinklered, provided that portion of the building is separated from the atrium portion by not less than a 2-hour fire-resistance-rated fire barrier or horizontal assembly, or both.

    2.Where the ceiling of the atrium is more than 55 feet (16 764 mm) above the floor, sprinkler protection at the ceiling of the atrium is not required.

    404.4Smoke control. A smoke control system shall be installed in accordance with Section 909.

    Exception: Smoke control is not required for atriums that connect only two stories.

    404.5               Enclosure of atriums. Atrium spaces shall be separated from adjacent spaces by a 1-hour fire barrier constructed in accordance with Section 706 or a horizontal assembly constructed in accordance with Section 711, or both.

    Exceptions:

    1.    A glass wall forming a smoke partition where automatic sprinklers are spaced 6 feet (1829 mm) or less along both sides of the separation wall, or on the room side only if there is not a walkway on the atrium side, and between 4 inches and 12 inches (102 mm and 305 mm) away from the glass and designed so that the entire surface of the glass is wet upon activation of the sprinkler system without obstruction. The glass shall be installed in a gasketed frame so that the framing system deflects without breaking (loading) the glass before the sprinkler system operates.

    2.    A glass-block wall assembly in accordance with Section 2110 and having a 3/4-hour fire protection rating.

    3.    The adjacent spaces of any three floors of the atrium shall not be required to be separated from the atrium where such spaces are included in the design of the smoke control system.

    404.6Standby power. Equipment required to provide smoke control shall be connected to a standby power system in accordance with Section 909.11.

    404.7Interior finish. The interior finish of walls and ceilings of the atrium shall not be less than Class B with no reduction in class for sprinkler protection.

    404.8Travel distance. In other than the lowest level of the atrium, where the required means of egress is through the atrium space, the portion of exit access travel distance within the atrium space shall not exceed 200 feet (60 960 mm).

    404.9 Fire alarm system. When the atrium connects more than two stories, a fire alarm system shall be installed in accordance with Section 907.2.13.

    SECTION 405 UNDERGROUND BUILDINGS

    405.1 General. The provisions of this section apply to building spaces having a

    floor level used for human occupancy more than 30 feet (9144 mm) below the lowest level of exit discharge.

    Exceptions:

    1.    One-, two-, and three-family dwellings, sprinklered in accordance with Section 903.3.1.3.

    2.    Parking garages with automatic sprinkler systems in compliance with Section 405.3.

    3.    Fixed guideway transit systems.

    4.    Grandstands, bleachers, stadiums, arenas and similar facilities.

    5.   Where the lowest story is the only story that would qualify the building as an underground building and has an area not exceeding 1,500 square feet (139 m2) and has an occupant load less than 10.

    405.2Construction requirements. The underground portion of the building shall be of Type I construction.

    405.3Automatic sprinkler system. The highest level of exit discharge serving the underground portions of the building and all levels below shall be equipped with an automatic sprinkler system installed in accordance with Section 903.3.1.1. Water-flow switches and control valves shall be supervised in accordance with Section 903.4.

    405.4Compartmentation. Compartmentation shall be in accordance with Sections 405.4.1 through 405.4.3.

    405.4.1Number of compartments. A building having a floor level more than 60 feet (18 288 mm) below the lowest level of exit discharge shall be divided into a minimum of two compartments of approximately equal size. Such compartmentation shall extend through the highest level of exit discharge serving the underground portions of the building and all levels below.

    Exception: The lowest story need not be compartmented where the area does not exceed 1,500 square feet (139 m2) and has an occupant load of less than 10.

    405.4.2Smoke barrier penetration. The compartments shall  be  separated from each other by a smoke barrier in accordance with Section 709. Penetrations between the two compartments shall be limited to plumbing and electrical piping and conduit that are firestopped in accordance with Section 712. Doorways shall be protected by fire door assemblies that are automatic closing by smoke detection in accordance with Section 715.4.7.3 and are installed in accordance with NFPA 105 and Section 715.4.3. Where provided, each compartment shall have an air supply and an exhaust system independent of the other compartments.

    405.4.3Elevators. Where elevators are provided, each compartment shall have direct access to an elevator. Where an elevator serves more than one compartment, an elevator lobby shall be provided and shall be separated from each compartment by a smoke barrier in accordance with Section 709. Doors shall be gasketed, have a drop sill and be automatic closing by smoke detection in accordance with Section 715.4.7.3.

    405.5Smoke control system. A smoke control system shall be provided in accordance with Sections 405.5.1 and 405.5.2.

    405.5.1Control system. A smoke control system is required to control the migration of products of combustion in accordance with Section 909 and the provisions of this section. Smoke control shall restrict movement of smoke to the general area of fire origin and maintain means of egress in a usable condition.

    405.5.2Compartment smoke control system. Where compartmentation is required, each compartment shall have an independent smoke control system. The system shall be automatically activated and capable of manual operation in accordance with Section 907.2.18.

    405.6Fire alarm systems. A fire alarm system shall be provided where required by Section 907.2.19.

    405.7Public address. A public address system shall be provided where required by Section 907.2.19.1.

    405.8Means of egress. Means of egress shall be in accordance with Sections 405.8.1 and 405.8.2.

    405.8.1Number of exits. Each floor level shall be provided with a minimum of two exits. Where compartmentation is required by Section 405.4, each compartment shall have a minimum of one exit and shall also have an exit access door-way into the adjoining compartment.

    405.8.2Smokeproof enclosure. Every required stairway serving floor levels more than 30 feet (9144 mm) below its level of exit discharge shall comply with the requirements for a smokeproof enclosure as provided in Section 1020.1.7.

    405.9Standby power. A standby power system complying with Section 2702 shall be provided standby power loads specified in Section 405.9.1.

    405.9.1Standby power loads. The following loads are classified as standby power loads.

    1. Smoke control system.

    2. Ventilation and automatic fire detection equipment for smokeproof enclosures.

    3.    Fire pumps.

    Standby power shall be provided for elevators in accordance with Section 3003.

    405.9.2Pick-up time. The standby power system shall pick up its connected loads within 60 seconds of failure of the normal power supply.

    405.10Emergency power. An emergency power system complying with Section 2702 shall be provided for emergency power loads specified in Section 405.10.1.

    405.10.1Emergency power loads. The following loads are classified as emergency power loads:

    1. Emergency voice/alarm communications systems.

    2. Fire alarm systems.

    3. Automatic fire detection systems.

    4. Elevator car lighting.

    5. Means of egress and exit sign illumination as required by Chapter 10.

    405.11Standpipe   system.   The   underground   building   shall   be   equipped throughout with a standpipe system in accordance with Section 905.

    SECTION 406

    MOTOR-VEHICLE-RELATED OCCUPANCIES

    406.1Private garages and carports.

    406.1.1Classification. Buildings or parts of buildings classified as Group U occupancies because of the use or character of the occupancy shall not exceed 1,000 square feet (93 m2) in area or one story in height except as provided in Section 406.1.2. Any building or portion thereof that exceeds the limitations specified in this section shall be classified in the occupancy group other than Group U that it most nearly resembles.

    406.1.2Area increase. Group U occupancies used for the storage of private or pleasure-type motor vehicles where no repair work is completed or fuel is dispensed are permitted to be 3,000 square feet (279 m2) when the following provisions are met:

    1.    For a mixed occupancy building, the exterior wall and opening protection for the Group U portion of the building shall be as required for the major occupancy of the building. For such a mixed occupancy building, the allowable floor area of the building shall be as permitted for the major occupancy contained therein.

    2.    For a building containing only a Group U occupancy, the exterior wall shall not be required to have a fire-resistance rating and the area of openings shall not be limited when the fire separation distance is 5 feet (1524 mm) or more.

    More than one 3,000-square-foot (279 m2) Group U occupancy shall be permitted to be in the same building, provided each 3,000-square-foot (279 m2) area is separated by fire walls complying with Section 705.

    406.1.3Garages and carports. Carports shall be open on at least two sides. Carport floor surfaces shall be of approved noncombustible material. Carports not open on at least two sides shall be considered a garage and shall comply with the provisions of this section for garages.

    Exception:  Asphalt  surfaces  shall  be  permitted  at  ground  level  in carports.

    The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.

    406.1.4Separation. Separations shall comply with the following:

    1.    The private garage shall be separated from the dwelling unit and its attic area by means of a minimum 1/2-inch (12.7 mm) gypsum board applied to the garage side. Garages beneath habitable rooms shall be separated from all habitable rooms above by not less than a 5/8-inch Type X gypsum board or equivalent. Door openings between a private garage and the dwelling unit shall be equipped with either solid wood doors or solid or honeycomb core steel doors not less than  13/8  inches  (34.9  mm)  thick,  or  doors  in  compliance  with

    Section 715.4.3. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Doors shall be self- closing and self-latching.

    2.    Ducts in a private garage and ducts penetrating the walls or ceilings separating the dwelling unit from the garage shall be constructed of a minimum 0.019-inch (0.48 mm) sheet steel and shall have no openings into the garage.

    3. A separation is not required between a Group R-3 and U carport, provided the carport is entirely open on two or more sides and there are not enclosed areas above.

    406.2Parking garages.

    406.2.1Classification. Parking garages shall be classified as either open, as defined in Section 406.3, or enclosed and shall meet the appropriate criteria in Section 406.4. Also see Section 509 for special provisions for parking garages.

    406.2.2Clear height. The clear height of each floor level in vehicle and pedestrian traffic areas shall not be less than 7 feet (2134 mm). Vehicle and pedestrian areas accommodating van-accessible parking required by Section 1106.5 shall conform to "ADAAG".

    406.2.3Guards. Guards shall be provided in accordance with Section 1012 at exterior and interior vertical openings on floor and roof areas where vehicles are parked or moved and where the vertical distance to the ground or surface directly below exceeds 30 inches (762 mm).

    406.2.4Vehicle barriers. Parking areas shall be provided with exterior or interior walls or vehicle barriers, except at pedestrian or vehicular accesses, designed in accordance with Section 1607.7. Vehicle barriers not less than 2 feet (607 mm) high shall be placed at the end of drive lanes, and at the end of parking spaces where the difference in adjacent floor elevation is greater than 1 foot (305 mm).

    Exception: Vehicle storage compartments in a mechanical access parking garage.

    406.2.5Ramps. Vehicle ramps shall not be considered as required exits unless pedestrian facilities are provided. Vehicle ramps that are utilized for vertical circulation as well as for parking shall not exceed a slope of 1:15 (6.67 percent).

    406.2.6Floor surface. Parking surfaces shall be of concrete or similar noncombustible and nonabsorbent materials.

    Exception: Asphalt parking surfaces are permitted at ground level.

    The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway.

    406.2.7Mixed separation. Parking garages shall be separated from other occupancies in accordance with Section 508.3.

    406.2.8Special hazards. Connection of a parking garage with any room in

    which there is a fuel-fired appliance shall be by means of a vestibule providing a two-doorway separation.

    Exception: A single door shall be allowed provided the sources of ignition in the appliance are at least 18 inches (457 mm) above the floor.

    406.2.9Attached to rooms. Openings from a parking garage directly into a room used for sleeping purposes shall not be permitted.

    406.3Open parking garages.

    406.3.1Scope. Except where specific provisions are made in the following subsections, other requirements of this code shall apply.

    406.3.2Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.

    MECHANICAL-ACCESS  OPEN  PARKING  GARAGES.  Open  parking

    garages employing parking machines, lifts, elevators or other mechanical devices for vehicles moving from and to street level and in which public occupancy is prohibited above the street level.

    OPEN PARKING GARAGE. A structure or portion of a structure with the openings as described in Section 406.3.3.1 on two or more sides that is used for the parking or storage of private motor vehicles as described in Section 406.3.4.

    RAMP-ACCESS OPEN PARKING GARAGES. Open parking garages employing a series of continuously rising floors or a series of interconnecting ramps between floors permitting the movement of vehicles under their own power from and to the street level.

    406.3.3Construction. Open parking garages shall be of Type I, II or IV construction. Open parking garages shall meet the design requirements of Chapter 16. For vehicle barriers, see Section 406.2.4.

    406.3.3.1 Openings. For natural ventilation purposes, the exterior side of the structure shall have uniformly distributed openings on two or more sides. The area of such openings in exterior walls on a tier must be at least 20 percent of the total perimeter wall area of each tier. The aggregate length of the openings considered to be providing natural ventilation shall constitute a minimum of 40 percent of the perimeter of the tier. Interior walls shall be at least 20 percent open with uniformly distributed openings.

    Exception: Openings are not required to be distributed over 40 percent of the building perimeter where the required openings are uniformly distributed over two opposing sides of the building.

    406.3.4Uses. Mixed uses shall be allowed in the same building as an open parking garage subject to the provisions of Sections 508.3, 402.7.1, 406.3.13, 509.3, 509.4 and 509.7.

    406.3.5Area and height. Area and height of open parking garages shall be limited as set forth in Chapter 5 for Group S-2 occupancies and as further provided for in Section 508.3.

    406.3.5.1 Single use. When the open parking garage is used exclusively for the parking or storage of private motor vehicles, with no other uses in the building, the area and height shall be permitted to comply with Table 406.3.5, along with increases allowed by Section 406.3.6.

    Exception: The grade-level tier is permitted to contain an office, waiting and toilet rooms having a total combined area of not more than 1,000 square feet (93 m2). Such area need not be separated from the open parking garage.

    In open parking garages having a spiral or sloping floor, the horizontal projection of the structure at any cross section shall not exceed the allowable area per parking tier. In the case of an open parking garage having a continuous spiral floor, each 9 feet 6 inches (2896 mm) of height, or portion thereof, shall be considered a tier.

    The clear height of a parking tier shall not be less than 7 feet (2134 mm), except that a lower clear height is permitted in mechanical-access open parking garages where approved by the building official.

    TABLE 406.3.5

     

     

    TYPE OF CONSTRUCTION

     

    AREA PER TIER

    (square feet)

    HEIGHT (in tiers)

     

    Ramp access

    Mechanical access

    Automatic sprinkler system

    No

    Yes

    IA

    Unlimited

    Unlimited

    Unlimited

    Unlimited

    IB

    Unlimited

    12 tiers

    12 tiers

    18 tiers

    IIA

    50,000

    10 tiers

    10 tiers

    15 tiers

    IIB

    50,000

    8 tiers

    8 tiers

    12 tiers

    IV

    50,000

    4 tiers

    4 tiers

    4 tiers

     

     
    OPEN PARKING GARAGES AREA AND HEIGHT

                                                                     

    For SI:  1 square foot = 0.0929 m2.

    406.3.6Area and height increases. The allowable area and height of  open parking garages shall be increased in accordance with the provisions of this section. Garages with sides open on three-fourths of the building's perimeter are permitted to be increased by 25 percent in area and one tier in height. Garages with sides open around the entire building's perimeter are permitted to be increased by 50 percent in area and one tier in height. For a side to be considered open under the above provisions, the total area of openings along the side shall not be less than 50 percent of the interior area of the side at each tier and such openings shall be equally distributed along the length of the tier.

    Allowable tier areas in Table 406.3.5 shall be increased for open parking garages constructed to heights less than the table maximum. The gross tier area of the garage shall not exceed that permitted for the higher structure. At least three sides of each such larger tier shall have continuous horizontal openings not less than 30 inches (762 mm) in clear height extending for at least 80 percent of the length of the sides and no part of such larger tier shall be more than 200 feet (60 960 mm) horizontally from such an opening. In addition, each such opening shall face a street or yard accessible to a street with a width of at least 30 feet (9144 mm) for the full length of the opening, and standpipes shall be provided in each such tier.

    Open parking garages of Type II construction, with all sides open, shall be unlimited in allowable area where the height does not exceed 75 feet (22 860 mm). For a side to be considered open, the total area of openings along the side shall not be less than 50 percent of the interior area of the side at each tier and such openings shall be equally distributed along the length of the tier. All portions of tiers shall be within 200 feet (60 960 mm) horizontally from such openings or other natural ventilation openings as defined in Section 406.3.3.1. These openings shall be permitted to be provided in courts with a minimum width of 30 feet (9144 mm) for the full width of the openings.

    406.3.7Fire separation distance. Exterior walls and openings in exterior walls shall comply with Tables 601 and 602. The distance to an adjacent lot line shall be determined in accordance with Table 602 and Section 704.

    406.3.8Means of egress. Where persons other than parking attendants are permitted, open parking garages shall meet the means of egress requirements of Chapter 10. Where no persons other than parking attendants are permitted, there shall not be less than two 36-inch-wide (914 mm) exit stair-ways. Lifts shall be permitted to be installed for use of employees only, provided they are completely enclosed by noncombustible materials.

    406.3.9Standpipes. Standpipes shall be installed where required by the provisions of Chapter 9.

    406.3.10Sprinkler systems. Where required by other provisions of this code, automatic sprinkler systems and standpipes shall be installed in accordance with the provisions of Chapter 9.

    406.3.11Enclosure of vertical openings. Enclosure shall not be required for vertical openings except as specified in Section 406.3.8.

    406.3.12Ventilation. Ventilation, other than the percentage of openings specified in Section 406.3.3.1, shall not be required.

    406.3.13Prohibitions. The following uses and alterations are not permitted:

    1.    Vehicle repair work.

    2.   Parking of buses, trucks and similar vehicles.

    3.   Partial or complete closing of required openings in exterior walls by tarpaulins or any other means.

    4.   Dispensing of fuel.

    406.4Enclosed parking garages.

    406.4.1Heights and areas. Enclosed vehicle parking garages and portions thereof that do not meet the definition of open parking garages shall be limited to the allowable heights and areas specified in Table 503 as modified by Sections 504, 506 and 507. Roof parking is permitted.

    406.4.2Ventilation.  A mechanical  ventilation  system  shall  be  provided  in accordance with the mechanical code.

    406.5Motor fuel-dispensing facilities.

    406.5.1Construction. Motor fuel-dispensing facilities shall be constructed in accordance with the "International Fire Code" and this section.

    406.5.2Canopies. Canopies under which fuels are dispensed shall have a clear,

    unobstructed height of not less than 13 feet 6 inches (4115 mm) to the lowest projecting element in the vehicle drive-through area. Canopies and their supports over pumps shall be of noncombustible materials, fire-retardant- treated wood complying with Chapter 23, wood of Type IV sizes or of construction providing 1-hour fire resistance. Combustible materials used in or on a canopy shall comply with one of the following:

    1.    Shielded from the pumps by a noncombustible element of the canopy, or wood of Type IV sizes;

    2. Plastics covered by aluminum facing having a minimum thickness  of 0.010 inch (0.30 mm) or corrosion-resistant steel having a minimum base metal thickness of 0.016 inch (0.41 mm). The plastic shall have a flame spread index of 25 or less and a smoke-developed index of 450 or less when tested in the form intended for use in accordance with ASTM E 84 and a self-ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D 1929; or

    3. Panels constructed of light-transmitting plastic materials shall be permitted to be installed in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided the panels are located at least 10 feet (3048 mm) from any building on the same lot and face yards or streets not

    less than 40 feet (12 192 mm) in width on the other sides. The aggregate areas of plastics shall not exceed 1,000 square feet (93 m2). The maximum area of any individual panel shall not exceed 100 square feet (9.3 m2).

    406.5.2.1Canopies used to support gaseous hydrogen systems. Canopies that are used to shelter dispensing operations where flammable compressed gases are located on the roof of the canopy shall be in accordance with the following:

    1. The canopy shall meet or exceed Type I construction requirements.

    2. Operations located under canopies shall be limited to refueling only.

    3. The canopy shall be constructed in a manner that prevents the accumulation of hydrogen gas.

    406.6Repair garages.

    406.6.1General. Repair garages shall be constructed in accordance with the  fire code and this section. This occupancy shall not include motor fuel- dispensing facilities, as regulated in Section 406.5.

    406.6.2Mixed uses. Mixed uses shall be allowed in the same building as a repair garage subject to the provisions of Section 508.3.

    406.6.3Ventilation. Repair garages shall be mechanically ventilated in accordance with the mechanical code. The ventilation system shall be controlled at the entrance to the garage.

    406.6.4Floor surface. Repair garage floors shall be of concrete or similar noncombustible and nonabsorbent materials.

    Exception: Slip-resistant, nonabsorbent, interior floor finishes having a critical radiant flux not more than 0.45 W/cm2, as determined by NFPA 253, shall be permitted.

    406.6.5Heating equipment. Heating equipment shall be installed in accordance with the mechanical code.

    406.6.6Gas detection system. Repair garages used for repair  of  vehicles fueled by nonodorized gases, such as hydrogen and nonodorized LNG, shall be provided with an approved flammable gas-detection system.

    406.6.6.1System design. The flammable gas-detection system shall be calibrated to the types of fuels or gases used by vehicles to be repaired. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower explosive limit. Gas detection shall also be provided in lubrication or chassis repair pits of garages used for repairing nonodorized LNG-fueled vehicles.

    406.6.6.2Operation. Activation of the gas detection system shall result in all of the following:

    1. Initiation of distinct audible and visual alarm signals in the repair garage.

    2. Deactivation of all heating systems located in the repair garage.

    3. Activation of the mechanical ventilation system, where the system is interlocked with gas detection.

    406.6.6.3Failure of the gas detection system. Failure of the gas detection system shall result in the deactivation of the heating system, activation of the mechanical ventilation system when the system is inter-locked with the gas detection system and cause a trouble signal to sound in an approved location.

    SECTION 407 GROUP I-2

    407.1General. Occupancies in Group I-2 shall comply with the provisions of this section and other applicable provisions of this code.

    407.2Corridors. Corridors in occupancies in Group I-2 shall be continuous to the exits and separated from other areas in accordance with Section 407.3 except spaces conforming to Sections 407.2.1 through 407.2.4.

    407.2.1Spaces of unlimited area. Waiting areas and  similar  spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following criteria are met:

    1. The spaces are not occupied for patient sleeping units, treatment rooms, hazardous or incidental use areas as defined in Section 508.2.

    2. The open space is protected by an automatic fire detection system installed in accordance with Section 907.

    3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic fire detection system installed in accordance with Section 907, or the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.

    4. The space is arranged so as not to obstruct access to the required exits.

    407.2.2Nurses' stations. Spaces for doctors' and nurses' charting, communications and related clerical areas shall be permitted to be open to the corridor, when such spaces are constructed as required for corridors.

    407.2.3Mental health treatment areas. Areas wherein mental health patients who are not capable of self-preservation are housed, or group meeting or multipurpose therapeutic spaces other than incidental use areas as defined in Section 508.2, under continuous supervision by facility staff, shall be permitted to be open to the corridor, where the following criteria are met:

    1. Each area does not exceed 1,500 square feet (140 m2).

    2. The area is located to permit supervision by the facility staff.

    3. The area is arranged so as not to obstruct any access to the required exits.

    4. The area is equipped with an automatic fire detection system installed in accordance with Section 907.2.

    5. Not more than one such space is permitted in any one smoke compartment.

    6. The walls and ceilings of the space are constructed as required for corridors.

    407.2.4  Gift shops. Gift shops less than 500 square feet (46.5 m2) in area shall be permitted to be open to the corridor provided the gift shop and storage areas are fully sprinklered and storage areas are protected in accordance with Section 508.2.

    407.3Corridor walls. Corridor walls shall be constructed as smoke partitions in accordance with Section 710.

    407.3.1Corridor doors. Corridor doors, other than those in a wall required to be rated by Section 508.2 or for the enclosure of a vertical opening or an exit, shall not have a required fire protection rating and shall not be required to be equipped with self-closing or automatic-closing devices, but shall provide an effective barrier to limit the transfer of smoke and shall be equipped with positive latching. Roller latches are not permitted. Other doors shall conform to Section 715.4.

    407.3.2Locking devices. Locking devices that restrict access to the patient room from the corridor, and that are operable only by staff from the corridor side, shall not restrict the means of egress from the patient room.

    Exception: Locking systems installed in accordance with section 1008.1.8.6.2 shall be permitted in areas where patients must be restricted for their own safety.

    407.4Smoke barriers. Smoke barriers shall be provided to subdivide every story used by inpatients for sleeping or treatment, regardless of occupant load, into at least two smoke compartments and to divide other stories containing a health care occupancy with an occupant load of 50 or more persons, regardless of use, into at

    least two smoke compartments. Such stories shall be divided into smoke compartments with an area of not more than 22,500 square feet (2092 m2) and the travel distance from any point in a smoke compartment to a smoke barrier door shall not exceed 200 feet (60 960 mm). The smoke barrier shall be in accordance

    with Section 709.

    407.4.1   Refuge area. At least 30 net square feet (2.8 m2) per patient shall be provided within the aggregate area of corridors, patient rooms, treatment rooms, lounge or dining areas and other low-hazard areas on each side of each smoke barrier. On floors not housing patients confined to a bed or litter, at least 6 net

    square feet (0.56 m2) per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments.

    407.4.2Independent egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originated.

    407.5Automatic sprinkler system. Smoke compartments containing patient sleeping units shall be equipped throughout with an automatic fire sprinkler system in accordance with Section 903.3.1.1. The smoke compartments shall be equipped with approved quick-response or residential sprinklers in accordance with Section 903.3.2.

    407.6Automatic fire detection. Corridors in nursing homes (both intermediate care and skilled nursing facilities), detoxification facilities and spaces permitted to be open to the corridors by Section 407.2 shall be equipped with an automatic fire detection system. Hospitals shall be equipped with smoke detection as required in Section 407.2.

    Exceptions:

    1.Corridor smoke detection is not required where patient sleeping units are provided with smoke detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each patient sleeping unit and an audible and visual alarm at the nursing station attending each unit.

    2.Corridor smoke detection is not required where patient sleeping unit doors are equipped with automatic door-closing devices with integral smoke detectors on the unit sides installed in accordance with their listing, provided that the integral detectors perform the required alerting function.

    407.7Secured yards. Grounds are permitted to be fenced and gates therein are permitted to be equipped with locks, provided that safe dispersal areas having 30 net square feet (2.8 m2) for bed and litter patients and 6 net square feet (0.56 m2)

    for ambulatory patients and other occupants are located between the building and the fence. Such provided safe dispersal areas shall not be located less than 50 feet (15 240 mm) from the building they serve.

    SECTION 408 GROUP I-3

    408.1General. Occupancies in Group I-3 shall comply with the provisions of this section and other applicable provisions of this code (see Section 308.4).

        408.1.1 Definition. The following word shall, for the purposes of this section and as used elsewhere in this code, have the meaning as follows:

              Sallyport. A security vestibule with two or more doors where the intended purpose is to prevent continuous and unobstructed passage by allowing the release of only one door at a time.

    408.2Mixed occupancies. Portions of buildings with an occupancy in Group I-3 that are classified as a different occupancy shall meet the applicable requirements of this code for such occupancies. Where security operations necessitate the locking of required means of egress, provisions shall be made for the release of occupants at all times.

    Means of egress from detention and correctional occupancies that traverse other

    use areas shall, as a minimum, conform to requirements for detention and correctional occupancies.

    Exception: It is permissible to exit through a horizontal exit into other contiguous occupancies that do not conform to detention and correctional occupancy egress provisions but that do comply with requirements set forth in the appropriate occupancy, as long as the occupancy is not a high-hazard use.

    408.3Means of egress. Except as modified or as provided for in this section, the provisions of Chapter 10 shall apply.

    408.3.1Door width. Doors to resident sleeping units shall have a clear width of not less than 28 inches (711 mm).

    408.3.2Sliding doors. Where doors in a means of egress are of the horizontal- sliding type, the force to slide the door to its fully open position shall not exceed 50 pounds (220 N) with a perpendicular force against the door of 50 pounds (220 N).

    408.3.3Spiral stairs. Spiral stairs that conform to the requirements of Section 1009.8 are permitted for access to and between staff locations.

    408.3.4Exit discharge. Exits are permitted to discharge into a fenced or walled courtyard. Enclosed yards or courts shall be of a size to accommodate all occupants, a minimum of 50 feet (15 240 mm) from the building with a net area of 15 square feet (1.4 m2) per person.

    408.3.5Sallyports. A sallyport shall be permitted in a means of egress where there are provisions for continuous and unobstructed passage through the sallyport during an emergency egress condition.

    408.3.6Exit enclosures. One of the required exit enclosures in each building shall be permitted to have glazing installed in doors and interior walls at each landing level providing access to the enclosure, provided that the following conditions are met:

    1. The exit enclosure shall not serve more than four floor levels.

    2. Exit doors shall not be less than 3/4-hour fire door assemblies complying with Section 715.4

    3. The total area of glazing at each floor level shall not exceed 5,000 square inches (3 m2) and individual panels of glazing shall not exceed 1,296 square inches (0.84 m2).

    4. The glazing shall be protected on both sides by an

    automatic fire sprinkler system. The sprinkler system shall be designed to wet completely the entire surface of any glazing affected by fire when actuated.

    5. The glazing shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler system operates.

    6. Obstructions, such as curtain rods, drapery traverse rods, curtains, drapes or similar materials shall not be installed between the automatic sprinklers and the glazing.

    408.4Locks. Egress doors are permitted to be locked in accordance with the applicable use condition. Doors from an area of refuge to the exterior are permitted to be locked with a key in lieu of locking methods described in Section

    408.4.1. The keys to unlock the exterior doors shall be available at all times and the locks shall be operable from both sides of the door.

    408.4.1Remote release. Remote release of locks on doors in a means of egress shall be provided with reliable means of operation, remote from the resident living areas, to release locks on all required doors. In Occupancy Conditions 3 or 4, the arrangement, accessibility and security of the release mechanism(s) required for egress shall be such that with the minimum available staff at any time, the lock mechanisms are capable of being released within 2 minutes.

    Exception: Provisions for remote locking and unlocking of occupied rooms in Occupancy Condition 4 are not required provided that not more than 10 locks are necessary to be unlocked in order to move occupants from one smoke  compartment  to a  refuge  area within 3 minutes. The opening of necessary locks shall be accomplished with not more than two separate keys.

    408.4.2Power-operated doors and locks. Power-operated sliding doors or power-operated locks for swinging doors shall be operable by a manual release mechanism at the door, and either emergency power or a remote mechanical operating release shall be provided.

    Exception: Emergency power is not required in facilities with 10 locks or less complying with the exception to Section 408.4.1.

    408.4.3Redundant operation. Remote release, mechanically operated sliding doors or remote release, mechanically operated locks shall be provided with a mechanically operated release mechanism at each door, or shall be provided with a redundant remote release control.

    408.4.4Relock capability. Doors remotely unlocked under emergency conditions shall not automatically relock when closed unless specific action is taken at the remote location to enable doors to relock.

    408.5Vertical openings. Vertical openings shall be enclosed in accordance with Section 707.

    Exception: A floor opening between floor levels of residential housing areas is permitted without enclosure protection between the levels, provided that both of the following conditions are met:

    1. The entire normally occupied areas so interconnected are open and unobstructed so as to enable observation of the areas by supervisory personnel.

    2. Means of egress capacity is sufficient to provide simultaneous egress for all occupants from all inter-connected levels and areas.

    The height difference between the highest and lowest finished floor levels shall not exceed 23 feet (7010 mm). Each story, considered separately, has at least one- half of its individual required means of egress capacity provided by exits leading directly out of that story without traversing another story within the interconnected area.

    408.6Smoke barrier. Occupancies in Group I-3 shall have smoke barriers complying with Section 709 to divide every story occupied by residents for sleeping, or any other story having an occupant load of 50 or more persons, into at least two smoke compartments.

    Exception: Spaces having a direct exit to one of the following, provided that the locking arrangement of the doors involved complies with the requirements for doors at the smoke barrier for the use condition involved:

    1. A public way.

    2. A building separated from the resident housing area by a 2-hour fire- resistance-rated assembly or 50 feet (15 240 mm) of open space.

    3. A secured yard or court having a holding space 50 feet (15 240 mm) from the housing area that provides 6 square feet (0.56 m2) or more of refuge area per occupant, including residents, staff and visitors.

    408.6.1Smoke compartments. The maximum number of residents in any smoke compartment shall be 200. The travel distance to a door in a smoke barrier from any room door required as exit access shall not exceed 150 feet (45 720 mm). The travel distance to a door in a smoke barrier from any point in a room shall not exceed 200 feet (60 960 mm).

    408.6.2  Refuge area. At least 6 net square feet (0.56 m2) per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments. This space shall be readily available wherever the occupants are moved across the smoke barrier in a fire emergency.

    408.6.3Independent egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originates.

    408.7Subdivision of resident housing areas. Sleeping areas and any contiguous day room, group activity space or other common spaces where residents are housed shall be separated from other spaces in accordance with Sections 408.7.1 through 408.7.4.

    408.7.1Occupancy Conditions 3 and 4. Each sleeping area in Occupancy Conditions 3 and 4 shall be separated from the adjacent common spaces by a smoke-tight partition where the travel distance from the sleeping area through the common space to the corridor exceeds 50 feet (15 240 mm).

    408.7.2Occupancy Condition 5. Each sleeping area in Occupancy Condition 5 shall be separated from adjacent sleeping areas, corridors and common spaces by a smoke-tight partition. Additionally, common spaces shall be separated from the corridor by a smoke-tight partition.

    408.7.3Openings in room face. The aggregate area of openings in a solid sleeping room face in Occupancy Conditions 2, 3, 4 and 5 shall not exceed 120 square inches (77 419 mm2). The aggregate area shall include all openings

    including door undercuts, food passes and grilles. Openings shall be not more than 36 inches (914 mm) above the floor. In Occupancy Condition 5, the openings shall be closeable from the room side.

    408.7.4Smoke-tight doors. Doors in openings in partitions required to be smoke tight by Section 408.7 shall be substantial doors, of construction that will resist the passage of smoke. Latches and door closures are not required on cell doors.

    408.8Windowless buildings. For the purposes of this section, a windowless building or portion of a building is one with nonopenable windows, windows not readily breakable or without windows. Windowless buildings shall be provided with an engineered smoke control system to provide ventilation (mechanical or natural) in accordance with Section 909 for each windowless smoke compartment.

    SECTION 409

    MOTION PICTURE PROJECTION ROOMS

    409.1General. The provisions of this section shall apply to rooms in which ribbon-type cellulose acetate or other safety film is utilized in conjunction with electric arc, xenon or other light-source projection equipment that develops hazardous gases, dust or radiation. Where cellulose nitrate film is utilized or stored, such rooms shall comply with NFPA 40.

    409.1.1Projection room required. Every motion picture machine projecting film as mentioned within the scope of this section shall be enclosed in a projection room. Appurtenant electrical equipment, such as rheostats, transformers and generators, shall be within the projection room or in an adjacent room of equivalent construction.

    409.2Construction of projection rooms. Every projection room shall be of permanent construction consistent with the construction requirements for the type of building in which the projection room is located. Openings are not required to be protected.

    The room shall have a floor area of not less than 80 square feet (7.44 m2) for a single machine and at least 40 square feet (3.7 m2) for each additional machine. Each motion picture projector, floodlight, spotlight or similar piece of equipment shall have a clear working space of not less than 30 inches by 30 inches (762 mm by 762 mm) on each side and at the rear thereof, but only one such space shall be required between two adjacent projectors. The projection room and the rooms appurtenant thereto shall have a ceiling height of not less than 7 feet 6 inches (2286 mm). The aggregate of openings for projection equipment shall not exceed 25 percent of the area of the wall between the projection room and the auditorium. Openings shall be provided with glass or other approved material, so as to close completely the opening.

    409.3Projection room and equipment ventilation. Ventilation shall be provided in accordance with the mechanical code.

    409.3.1Supply air. Each projection room shall be provided with adequate air supply inlets so arranged as to provide well-distributed air throughout the room. Air inlet ducts shall provide an amount of air equivalent to the amount of air being exhausted by projection equipment. Air is permitted to be taken from the outside; from adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system, provided it is so arranged as to provide sufficient air when other systems are not in operation.

    409.3.2Exhaust air. Projection rooms are permitted to be exhausted through the lamp exhaust system. The lamp exhaust system shall be positively interconnected with the lamp so that the lamp will not operate unless there is the required airflow. Exhaust air ducts shall terminate at the exterior of the building in such a location that the exhaust air cannot be readily recirculated into any air supply system. The projection room ventilation system is permitted to also serve appurtenant rooms, such as the generator and rewind rooms.

    409.3.3Projection machines. Each projection machine shall be provided with an exhaust duct that will draw air from each lamp and exhaust it directly to the outside of the building. The lamp exhaust is permitted to serve to exhaust air from the projection room to provide room air circulation. Such ducts shall be of rigid materials, except for a flexible connector approved for the purpose. The projection lamp or projection room exhaust system, or both, is permitted to be

    combined but shall not be interconnected with any other exhaust or return system, or both, within the building.

    409.4Lighting control. Provisions shall be made for control of the auditorium lighting and the means of egress lighting systems of theaters from inside the projection room and from at least one other convenient point in the building.

    409.5Miscellaneous equipment. Each projection room shall be provided with rewind and film storage facilities.

    SECTION 410 STAGES AND PLATFORMS

    410.1Applicability. The provisions of this section shall apply to all parts of buildings and structures that contain stages or platforms and similar appurtenances as herein defined.

    410.2Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

    FLY GALLERY. A raised floor area above a stage from which the movement of scenery and operation of other stage effects are controlled.

    GRIDIRON. The structural framing over a stage supporting equipment for hanging or flying scenery and other stage effects.

    PINRAIL. A rail on or above a stage through which belaying pins are inserted and to which lines are fastened.

    PLATFORM. A raised area within a building used for worship, the presentation of music, plays or other entertainment; the head table for special guests; the raised area for lecturers and speakers; boxing and wrestling rings; theater-in-the-round stages; and similar purposes wherein there are no overhead hanging curtains, drops, scenery or stage effects other than lighting and sound. A temporary platform is one installed for not more than 30 days.

    PROSCENIUM WALL. The wall that separates the stage from the auditorium or assembly seating area.

    STAGE. A space within a building utilized for entertainment or presentations, which includes overhead hanging curtains, drops, scenery or stage effects other than lighting and sound.

    410.3Stages. Stage construction shall comply with Sections 410.3.1 through 410.3.7.

    410.3.1Stage construction. Stages shall be constructed of materials as required for floors for the type of construction of the building in which such stages are located.

    Exceptions:

    1. Stages of Type IIB or IV construction with a nominal 2-inch (51 mm) wood deck, provided that the stage is separated from other areas in accordance with Section 410.3.4.

    2. In buildings of Type IIA, IIIA and VA construction, a fire-resistance- rated  floor  is  not  required,  provided  the  space  below  the  stage  is

    equipped  with  an  automatic  fire-extinguishing  system  in  accordance with Section 903 or 904.

    3. In all types of construction, the finished floor shall be constructed of wood or approved noncombustible materials. Openings through stage floors shall be equipped with tight-fitting, solid wood trap doors with approved safety locks.

    410.3.1.1 Stage height and area. Stage areas shall be measured to include the entire performance area and adjacent backstage and support areas not separated from the performance area by fire-resistance-rated construction. Stage height shall be measured from the lowest point on the stage floor to the highest point of the roof or floor deck above the stage.

    410.3.2Galleries, gridirons, catwalks and pinrails. Beams designed only for the attachment of portable or fixed theater equipment, gridirons, galleries and catwalks shall be constructed of approved materials consistent with the requirements for the type of construction of the building; and a fire-resistance rating shall not be required. These areas shall not be considered to be floors, stories, mezzanines or levels in applying this code.

    Exception: Floors of fly galleries and catwalks shall be constructed of any approved material.

    410.3.3Exterior stage doors. Where protection of openings is required, exterior exit doors shall be protected with fire door assemblies that comply with Section 715. Exterior openings that are located on the stage for means of egress or loading and unloading purposes, and that are likely to be open during occupancy of the theater, shall be constructed with vestibules to prevent air drafts into the auditorium.

    410.3.4Proscenium wall. Where the stage height is greater than 50 feet (15 240 mm), all portions of the stage shall be completely separated from the seating area by a proscenium wall with not less than a 2-hour fire-resistance rating extending continuously from the foundation to the roof.

    410.3.5Proscenium curtain. Where a proscenium wall is required to have a fire-resistance rating, the stage opening shall be provided with a fire curtain of approved material or an approved water curtain complying with Section 903.3.1.1. The fire curtain shall be designed and installed to intercept hot gases, flames and smoke and to prevent a glow from a severe fire on the stage from showing on the auditorium side for a period of 20 minutes. The closing of the fire curtain from the full open position shall be accomplished in less than 30 seconds, with the last 8 feet (2438 mm) of travel requiring 5 or more seconds for full closure.

    410.3.5.1Activation. The curtain shall be activated by rate-of-rise heat detection installed in accordance with Section 907.10 operating at a rate of temperature rise of 15 to 20°F per minute (8 to 11°C per minute), and by an auxiliary manual control.

    410.3.5.2Fire test. A sample curtain with a minimum of two vertical seams shall be subjected to the standard fire test specified in ASTM E 119 for a period of 30 minutes. The curtain shall overlap the furnace edges by an amount that is appropriate to seal the top and sides. The curtain shall have a bottom pocket containing a minimum of 4 pounds per linear foot (5.9 kg/m) of batten. The exposed surface of the curtain shall not glow, and flame or

    smoke shall not penetrate the curtain during the test period. Unexposed surface temperature and hose stream test requirements are not applicable to the proscenium fire safety curtain test.

    410.3.5.3Smoke test. Curtain fabrics shall have a smoke-developed rating of 25 or less when tested in accordance with ASTM E 84.

    410.3.5.4Tests. The completed proscenium curtain shall be subjected to operating tests prior to the issuance of a certificate of occupancy.

    410.3.6Scenery. Combustible materials used in sets and scenery shall meet the fire propagation performance criteria of NFPA 701, in accordance with Section 805 and the "International Fire Code". Foam plastics and materials containing foam plastics shall comply with Section 2603 and the "International Fire Code".

    410.3.7Stage ventilation. Emergency ventilation shall be provided for stages larger than 1,000 square feet (93 m2) in floor area, or with a stage height greater than 50 feet (15 240 mm). Such ventilation shall comply with Section 410.3.7.1 or 410.3.7.2.

    410.3.7.1Roof vents. Two or more vents constructed to open automatically by approved heat-activated devices and with an aggregate clear opening area of not less than 5 percent of the area of the stage shall be located near the center and above the highest part of the stage area. Supplemental means shall be provided for manual operation of the ventilator. Curbs shall be provided as required for skylights in Section 2610.2. Vents shall be labeled.

    410.3.7.2Smoke control. Smoke control in accordance with Section 909 shall be provided to maintain the smoke layer interface not less than 6 feet (1829 mm) above the highest level of the assembly seating or above the top of the proscenium opening where a proscenium wall is provided in compliance with Section 410.3.4.

    410.4Platform construction. Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed of fire-retardant-treated wood for Type I, II, and IV construction where the platforms are not more than 30 inches (762 mm) above the main floor,

    and not more than one-third of the room floor area and not more than 3,000 square feet (279 m2) in area. Where the space beneath the permanent platform is used for storage or any other purpose other than equipment, wiring or plumbing, the   floor   construction   shall   not   be   less   than   1-hour   fire-resistance-rated

    construction. Where the space beneath the permanent platform is used only for equipment, wiring or plumbing, the underside of the permanent platform need not be protected.

    410.4.1Temporary platforms. Platforms installed for a period of not more than 30 days are permitted to be constructed of any materials permitted by the code. The space between the floor and the platform above shall only be used for plumbing and electrical wiring to platform equipment.

    410.5Dressing and appurtenant rooms. Dressing and appurtenant rooms shall comply with Sections 410.5.1 through 410.5.3.

    410.5.1Separation from stage. Where the stage height is greater than 50 feet (15 240 mm), the stage shall be separated from dressing rooms, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage and other parts of the building by a fire barrier with not less than a 2-hour

    fire-resistance rating with approved opening protectives. For stage heights of 50 feet (15 240 mm) or less, the required stage separation shall be a fire barrier with not less than a 1-hour fire-resistance rating with approved opening protectives.

    410.5.2Separation from each other. Dressing rooms, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage shall be separated from each other by fire barriers with not less than a 1-hour fire- resistance rating with approved opening protectives.

    410.5.3Stage exits. At least one approved means of egress shall be provided from each side of the stage and from each side of the space under the stage. At least one means of escape shall be provided from each fly gallery and from the gridiron. A steel ladder, alternating tread stairway or spiral stairway is permitted to be provided from the gridiron to a scuttle in the stage roof.

    410.6Automatic sprinkler system. Stages shall be equipped with an automatic fire-extinguishing system in accordance with Chapter 9. Sprinklers shall be installed under the roof and gridiron and under all catwalks and galleries over the stage. Sprinklers shall be installed in dressing rooms, per-former lounges, shops and storerooms accessory to such stages.

    Exceptions:

    1. Sprinklers are not required under stage areas less than 4 feet (1219 mm) in clear height that are utilized exclusively for storage of tables and chairs, provided the concealed space is separated from the adjacent spaces by not less than 5/8-inch (15.9 mm) Type X gypsum board.

    2. Sprinklers are not required for stages 1,000 square feet (93 m2) or less in area and 50 feet (15 240 mm) or less in height where curtains, scenery or other combustible hangings are not retractable vertically. Combustible hangings shall be limited to a single main curtain, borders, legs and a single backdrop.

    3. Sprinklers are not required within portable orchestra enclosures on stages.

    410.7Standpipes. Standpipe systems shall be provided in accordance with Section 905.

    SECTION 411

    SPECIAL AMUSEMENT BUILDINGS

    411.1General. Special amusement buildings having an occupant load of 50 or more shall comply with the requirements for the appropriate Group A occupancy and this section. Amusement buildings having an occupant load of less than 50 shall comply with the requirements for a Group B occupancy and this section.

    Exception: Amusement buildings or portions thereof that are without walls or a roof and constructed to prevent the accumulation of smoke.

    For flammable decorative materials, see the "International Fire Code".

    411.2Special amusement building. A special amusement building is any temporary or permanent building or portion thereof that is occupied for amusement, entertainment or educational purposes and that contains a device or system that conveys passengers or provides a walkway along, around or over a course in any direction so arranged that the means of egress path is not readily

    apparent due to visual or audio distractions or is intentionally confounded or is not readily available because of the nature of the attraction or mode of conveyance through the building or structure.

    411.3Automatic fire detection. Special amusement buildings shall be equipped with an automatic fire detection system in accordance with Section 907.

    411.4Automatic sprinkler system. Special amusement buildings shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where the special amusement building is temporary, movable, or portable, the sprinkler water supply shall be of an approved temporary means.

    Exceptions:

    1.Automatic sprinklers are not required where the total floor area of a temporary special amusement occupancy is less than 1,000 square feet (93 m2) and the travel distance from any point to an exit is less than 50 feet (15 240 mm).

    2.Automatic fire sprinklers are not required where the total floor area of a temporary special amusement occupancy in an existing building is less than 5000 square feet (93 m2), the travel distance from any point to an exit is less

    than 50 feet (15 240 mm), and where, in the opinion of the building official, additional means have been provided to ensure an equivalent level of safety for all occupants during the hours that the special amusement building is operated and occupied. Such additional means may include, but not be limited to: fire watches; reduced occupant loads; additional means of egress; additional detection; and portable fire extinguishers.

    411.5Alarm. Actuation of a single smoke detector, the automatic  sprinkler system or other automatic fire detection device shall immediately sound an alarm at the building at a constantly attended location from which emergency action can be initiated including the capability of manual initiation of requirements in Section 907.2.11.2.

    411.6Emergency voice/alarm communications system. An emergency voice/alarm communications system shall be provided in accordance with Sections 907.2.11 and 907.2.12.2, which is also permitted to serve as a public address system and shall be audible throughout the entire special amusement building.

    411.7Exit marking. Exit signs shall be installed at the required exit or exit access doorways of amusement buildings. Approved directional exit markings shall also be provided. Where mirrors, mazes or other designs are utilized that disguise the path of egress travel such that they are not apparent, approved low- level exit signs and directional path markings shall be provided and located not more than 8 inches (203 mm) above the walking surface and on or near the path of egress travel. Such markings shall become visible in an emergency. The directional exit marking shall be activated by the automatic fire detection system and the automatic sprinkler system in accordance with Section 907.2.11.2.

    411.8Interior finish. The interior finish shall be Class A in accordance with Section 803.1.

    SECTION 412

    AIRCRAFT-RELATED OCCUPANCIES

    412.1Airport traffic control towers.

    412.1.1General. The provisions of this section shall apply to airport traffic control towers not exceeding 1,500 square feet (140 m2) per floor occupied only for the following uses:

    1.    Airport traffic control cab.

    2.    Electrical and mechanical equipment rooms.

    3.    Airport terminal radar and electronics rooms.

    4.    Office spaces incidental to the tower operation.

    5.    Lounges for employees, including sanitary facilities.

    412.1.2Type of construction. Airport traffic control towers shall  be constructed to comply with the height and area limitations of Table 412.1.2.

    TABLE 412.1.2

    TYPE OF CONSTRUCTION

    HEIGHTa

    (feet)

    MAXIMUM AREA

    (square feet)

    IA

    Unlimited

    1,500

    IB

    240

    1,500

    IIA

    100

    1,500

    IIB

    85

    1,500

    IIIA

    65

    1,500

     

     
    HEIGHT AND AREA LIMITATIONS FOR AIRPORT TRAFFIC CONTROL TOWERS

    For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2. a. Height to be measured from grade plane to cab floor.

    412.1.3Egress. A minimum of one exit stairway shall be permitted for airport traffic control towers of any height provided that the occupant load per floor does not exceed 15. The stairway shall conform to the requirements of Section 1009. The stairway shall be separated from elevators by a minimum distance of one-half of the diagonal of the area served measured in a straight line. The exit stairway and elevator hoistway are permitted to be located in the same shaft enclosure, provided they are separated from each other by a 4-hour fire barrier having no openings. Such stairway shall be pressurized to a minimum of 0.15 inch of water column (43 Pa) and a maximum of 0.35 inch of water column (101 Pa) in the shaft relative to the building with stairway doors closed. Stairways need not extend to the roof as specified in Section 1009.11. The provisions of Section 403 do not apply.

    Exception: Smokeproof enclosures as set forth in Section 1020.1.7 are not required where required stairways are pressurized.

    412.1.4Automatic fire detection systems. Airport traffic control towers shall be provided with an automatic fire detection system installed in accordance with Section 907.2.

    412.1.5Standby power. A standby power system that conforms to Section 2702 shall be provided in airport traffic control towers more than 65 feet (19 812 mm) in height. Power shall be provided to the following equipment:

    1. Pressurization equipment, mechanical equipment and lighting.

    2. Elevator operating equipment.

    3. Fire alarm and smoke detection systems.

    412.1.6Accessibility. Airport traffic control towers shall be accessible in accordance with the requirements of "ADAAG".

    412.2Aircraft hangars. Aircraft hangars shall be in accordance with Sections 412.2.1 through 412.2.6.

    412.2.1Exterior walls. Exterior walls located less than 30 feet (9 144 mm) from property lines, lot lines or a public way shall have a fire-resistance rating not less than 2 hours.

    412.2.2Basements. Where hangars have basements, the floor over the basement shall be of Type IA construction and shall be made tight against seepage of water, oil or vapors. There shall be no opening or communication between the basement and the hangar. Access to the basement shall be from outside only.

    412.2.3Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump.

    Exception: Aircraft hangars with individual lease spaces not exceeding 2,000 square feet (186 m2) each in which servicing, repairing or washing is not conducted and fuel is not dispensed shall have floors that are graded toward the door, but shall not require a separator.

    412.2.4Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire-resistance-rated construction. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separa- tion.

    Exceptions:

    1. Unit heaters and vented infrared radiant heating equipment suspended at least 10 feet (3048 mm) above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar and at least 8 feet (2438 mm) above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.

    2. A single interior door shall be allowed, provided the sources of ignition in the appliances are at least 18 inches (457 mm) above the floor.

    412.2.5Finishing. The process of "doping," involving use of a volatile flammable solvent, or of painting, shall be carried on in a separate detached building equipped with automatic fire-extinguishing equipment in accordance with Section 903.

    412.2.6Fire suppression. Aircraft hangars shall be provided with fire suppression as required by NFPA 409.

    Exception: Group II hangars as defined in NFPA 409 storing private aircraft without major maintenance or overhaul are exempt from foam suppression requirements.

    412.3Residential aircraft hangars. Residential aircraft hangars as defined in Section 412.3.1 shall comply with Sections 412.3.2 through 412.3.6.

    412.3.1Definition. The following word and term shall, for the purposes of this chapter and as used elsewhere in this code, have the meaning shown herein.

    RESIDENTIAL AIRCRAFT HANGAR. An accessory building less than 2,000 square feet (186 m2) and 20 feet (6096 mm) in height, constructed on a one-, two-, or three-family residential property where aircraft are stored. Such use will be considered as a residential accessory use incidental to the dwelling.

    412.3.2Fire separation. A hangar shall not be attached to a dwelling unless separated by a fire barrier having a fire-resistance rating of not less than 1 hour. Such separation shall be continuous from the foundation to the underside of the roof and unpierced except for doors leading to the dwelling unit. Doors into the dwelling unit must be equipped with self-closing devices and conform to the requirements of Section 715 with at least a 4-inch (102 mm) noncombustible raised sill. Openings from a hanger directly into a room used for sleeping purposes shall not be permitted.

    412.3.3Egress. A hangar shall provide two means of egress. One of the doors into the dwelling shall be considered as meeting only one of the two means of egress.

    412.3.4Smoke alarms. Smoke alarms shall be provided within the hangar in accordance with Section 907.2.21.

    412.3.5Independent systems. Electrical, mechanical and plumbing drain, waste and vent (DWV) systems installed within the hangar shall be independent of the systems installed within the dwelling. Building sewer lines shall be permitted to be connect outside the structures.

    Exception: Smoke detector wiring and feed for electrical subpanels in the hangar.

    412.3.6Height and area limits. Residential aircraft hangars shall not exceed 2,000 square feet (186 m2) in area and 20 feet (6096 mm) in height.

    412.4Aircraft paint hangars. Aircraft painting operations where flammable liquids are used in excess of the maximum allowable quantities per control area listed in Table 307.7(1) shall be conducted in an aircraft paint hangar that complies with the provisions of Section 412.4.

    412.4.1Occupancy group. Aircraft paint hangars shall be classified as Group H-2. Aircraft paint hangars shall comply with the applicable requirements of this code and the fire code for such occupancy.

    412.4.2Construction. The aircraft paint hangar shall be of Type I or II construction.

    412.4.3Operations. Only those flammable liquids necessary for painting operations shall be permitted in quantities less than the maximum allowable quantities per control area in Table 307.1(1). Spray equipment cleaning operations shall be conducted in a liquid use, dispensing and mixing room.

    412.4.4Storage. Storage of flammable liquids shall be in a liquid storage room.

    412.4.5Fire suppression. Aircraft paint hangars shall be provided with fire suppression as required by NFPA 409.

    412.4.6Ventilation. Aircraft paint hangars shall be provided with ventilation as

    required in the mechanical code.

    412.5Heliports and helistops. Heliports and helistops shall be permitted to be erected on buildings or other locations where they are constructed in accordance with this section.

    412.5.1Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.

    HELIPORT. An area of land or water or a structural surface that is used, or intended for use, for the landing and taking off of helicopters, and any appurtenant areas that are used, or intended for use, for heliport buildings and other heliport facilities.

    412.5.2Size. The landing area for helicopters less than 3,500 pounds (1588 kg) shall be a minimum of 20 feet (6096 mm) in length and width. The landing area shall be surrounded on all sides by a clear area having a minimum aver-age width at roof level of 15 feet (4572 mm) but with no width less than 5 feet (1524 mm).

    412.5.3Design. Helicopter landing areas and the supports thereof on the roof of a building shall be noncombustible construction. Landing areas shall be designed to confine any flammable liquid spillage to the landing area itself and provisions shall be made to drain such spillage away from any exit or stairway serving the helicopter landing area or from a structure housing such exit or stairway. For structural design requirements, see Section 1605.5.

    412.5.4Means of egress. The means of egress from heliports and helistops shall comply with the provisions of Chapter 10. Landing areas located on buildings or structures shall have two or more means of egress. For landing areas less than 60 feet (18 288 mm) in length, or less than 2,000 square feet (186 m2) in area, the second means of egress may be a fire escape or ladder

    leading to the floor below.

    412.5.5Rooftop heliports and helistops. Rooftop heliports and helistops shall comply with NFPA 418.

    SECTION 413 COMBUSTIBLE STORAGE

    413.1General. High-piled stock or rack storage in any occupancy group shall comply with NFPA 230, NFPA 13, and Chapter 23 of the fire code.

    413.2Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 13/4 inch (45 mm) in thickness.

    Exceptions:

    1. Areas protected by approved automatic sprinkler systems.

    2. Group R-3 and U occupancies.

    SECTION 414 HAZARDOUS MATERIALS

    414.1General. The provisions of this section shall apply to buildings and structures occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials.

    414.1.1Other provisions. Buildings and structures with an occupancy  in Group H shall also comply with the applicable provisions of Section 415 and the fire code.

    414.1.2Materials. The safe design of hazardous material occupancies is material dependent. Individual material requirements are also found in Sections 307 and 415, and in the mechanical code and the fire code.

    414.1.2.1 Aerosols. Level 2 and 3 aerosol products shall be stored and displayed in accordance with the "International Fire Code". See Section 311.2 and the "International Fire Code" for occupancy group requirements.

    414.1.3Information required. Separate floor plans shall be submitted for buildings and structures with an occupancy in Group H, identifying the locations of anticipated contents and processes so as to reflect the nature of each occupied portion of every building and structure. A report identifying hazardous materials including, but not limited to, materials representing hazards that are classified in Group H to be stored or used, shall be submitted and the methods of protection from such hazards shall be indicated on the construction documents. The opinion and report shall be prepared by a qualified person, firm or corporation approved by the building official and shall be provided without charge to the enforcing agency.

    414.2Control areas. Control areas shall comply with Sections 414.2.1 through 414.2.5 and the fire code.

    414.2.1Construction requirements. Control areas shall be separated from each other by fire barriers constructed in accordance with Section 706 or horizontal assemblies constructed in accordance with Section 711, or both.

    414.2.2Percentage of maximum allowable quantities. The percentage of maximum allowable quantities of hazardous materials per control area permitted at each floor level within a building shall be in accordance with Table 414.2.2.

      TABLE 414.2.2

    DESIGN AND NUMBER OF CONTROL AREAS

     

    FLOOR LEVEL

    PERCENTAGE OF THE MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREAa

    NUMBER OF CONTROL AREAS PER FLOOR

    FIRE-RESISTANCE RATING FOR FIRE BARRIERS IN HOURSb

     

     

     

    Above grade

    Higher than 9

    5

    1

    2

    7- 9

    5

    2

    2

    6

    12.5

    2

    2

    5

    12.5

    2

    2

    plane

    4

    12.5

    2

    2

    3

    50

    2

    1

    2

    75

    3

    1

    1

    100

    4

    1

     

    Below grade plane

    1

    2

    Lower than 2

    75

    50

    Not Allowed

    3

    2

    Not Allowed

    1

    1

    Not Allowed

    a. Percentages shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2), with all increases allowed in the notes to those tables.

    b. Fire barriers shall include walls and f l o o r s as necessary to provide separation from other portions of the building.

    414.2.3Number. The maximum number of control areas within a building shall be in accordance with Table 414.2.3.

    414.2.4Fire-resistance-rating requirements. The required fire-resistance rating for fire barriers shall be in accordance with Table 414.2.2. The floor construction of the control area and the construction supporting the floor of the control area shall have a minimum 2-hour fire-resistance rating.

    Exception: The floor construction of the control area and the construction supporting the floor of the control area is allowed to be 1-hour fire-resistance rated in buildings of Type IIA, IIIA and VA construction, provided that both of the following conditions exist:

    The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and the building is three stories or less in height.

    414.2.5Hazardous material in Group M display and storage areas and in Group S storage areas. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials permitted within a single control area of a Group M display and storage area, a Group S storage area or an outdoor control area is permitted to exceed the maximum allowable quantities per control area specified in Tables 307.1(1) and 307.1(2) without classifying the building or use as a Group H occupancy, provided that the materials are displayed and stored in accordance with the fire code and quantities do not exceed the maximum allowable specified in Table 414.2.5(1).

    In  Group  M  occupancy  wholesale  and  retail  sales  uses,  indoor  storage  of

    flammable and combustible liquids shall not exceed the maximum allowable quantities per control area as indicated in Table 414.2.5(2), provided that the materials are displayed and stored in accordance with the fire code.

    The maximum quantity of aerosol products in Group M occupancy retail display areas, storage areas adjacent to retail display areas and retail storage areas shall be in accordance with the "International Fire Code".

    414.3Ventilation. Rooms, areas or spaces of Group H in which explosive, corrosive, combustible, flammable or highly toxic dusts, mists, fumes, vapors or gases are or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated as required by the fire code and the  mechanical code.

    Ducts conveying explosives or flammable vapors, fumes or dusts shall extend directly to the exterior of the building without entering other spaces. Exhaust ducts shall not extend into or through ducts and plenums.

    Exception: Ducts conveying vapor or fumes having flammable constituents less than 25 percent of their lower flammable limit (LFL) are permitted to pass through other spaces.

    Emissions generated at workstations shall be confined to the area in which they are generated as specified in the fire code and the mechanical code.

    The location of supply and exhaust openings shall be in accordance with the  mechanical code. Exhaust air contaminated by highly toxic material shall be treated in accordance with the fire code.

    A manual shutoff control for ventilation equipment required by this section shall be provided outside the room adjacent to the principal access door to the room. The switch shall be of the break-glass type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.

     414.4 Hazardous material systems. Systems involving hazardous  materials shall be suitable for the intended application. Controls shall be designed to prevent materials from entering or leaving process or reaction systems at other than the intended time, rate or path. Automatic controls, where provided, shall be designed to be fail safe.

     414.5 Inside storage, dispensing and use. The inside storage, dispensing and use of hazardous materials in excess of the maximum allowable quantities per control area of Tables 307.1(1) and 307.1(2) shall be in accordance with Sections 414.5.1 through 414.5.5 of this code and the "International Fire Code".

     414.5.1 Explosion control. Explosion control shall be provided in accordance with Section 911 of the fire code as required by Table 414.5.1 where quantities of hazardous materials specified in that table exceed the maximum allowable quantities in Table 307.1(1) or where a structure, room or space is occupied for purposes involving explosion hazards as required by Section 415 or the fire code.

     414.5.2 Monitor control equipment. Monitor control equipment shall be provided where required by the fire code.

     414.5.3 Automatic fire detection systems. Group H occupancies shall be provided with an automatic fire detection system in accordance with Section 907.2.

     414.5.4 Standby or emergency power. Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency or standby power system in accordance with Chapter 27.

    Exceptions:

    1.    Storage areas for Class I and II oxidizers.

    2.    Storage areas for Class III, IV and V organic per-oxides.

    3. Storage, use and handling areas for highly toxic or toxic materials as provided for in the fire code.

    4. Standby power for mechanical ventilation, treatment systems and temperature control systems shall not be required where an approved fail-safe engineered system is installed.

    414.5.5 Spill control, drainage and containment. Rooms, buildings or areas occupied  for  the  storage  of  solid  and  liquid  hazardous  materials  shall  be provided with a means to control spillage and to contain or drain off spillage and fire protection water discharged in the storage area where required in the fire code. The methods of spill control shall be in accordance with the fire code.

    414.6Outdoor storage, dispensing and use. The outdoor storage, dispensing and use of hazardous materials shall be in accordance with the "International Fire Code".

     414.6.1 Weather protection. Where weather protection is provided for sheltering outdoor hazardous material storage or use areas, such areas shall be considered outdoor storage or use when the weather protection structure complies with Sections 414.6.1.1 through 414.6.1.3.

     414.6.1.1  Walls.  Walls  shall  not  obstruct  more  than  one  side  of  the structure.

    Exception: Walls shall be permitted to obstruct portions of multiple sides of the structure, provided that the obstructed area does not exceed 25

    percent of the structure's perimeter.

     414.6.1.2 Separation distance. The distance from the structure to buildings, lot lines, public ways or means

     TABLE 414.2.5(1)

    MAXIMUM ALLOWABLE QUANTITY PER INDOOR AND OUTDOOR CONTROL AREA IN GROUP M AND S OCCUPANCIES NONFLAMMABLE SOLIDS AND NONFLAMMABLE AND NONCOMBUSTIBLE LIQUIDS d, e,f 

    CONDITION                                                                                           MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA

    Materiala                                           Class

    Solids pounds

    Liquids gallons

    A.  Health-hazard materials-nonflammable and noncombustible solids and liquids

    1.  Corrosivesb, c                                                                        Not Applicable                                        9,750                                                  975

    2.  Highly toxics                                                Not Applicable                                        20b, c                                                                             2b, c

    3.  Toxicsb, c                                                                                  Not Applicable                                        1,000                                                  100

    B. Physical-hazard materials-nonflammable and noncombustible solids and liquids

    1.  Oxidizersb, c

    4                                                Not Allowed                                    Not Allowed 3                            1,150g                      115

    2                                                      2,250h                                               225

    1                                                   18,000i, j                                                                   1,800i, j

    4                                               Not Allowed                                    Not Allowed

    2.  Unstable (reactives)b, c

    3.  Water (reactives)

    3                                                     550                                                     55

    2                                                     1,150                                                 115

    1                                                 Not Limited                                     Not Limited

    3b, c                                                                           550                                                      55

    2b,c                                                                              1,150                                                 115

    1                                                 Not Limited                                     Not Limited

    For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L.

    a.  Hazard categories are as specified in the fire code .

    b.   Maximum allowable quantities shall be increased 100 percent in buildings that are sprinklered in accordance with Section 903.3.1.1.When Note c also applies, the increase for both notes shall be applied accumulatively.

    c.    Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, in accordance with the "Inte rnational Fi re Code". When Note b also applies, the increase for both notes shall be applied accumulatively.

    d.   See Table 414.2.2 for design and number of control areas.

    e.    Allowable quantities for other hazardous material categories shall be in accordance with Section 307.

    f.    Maximum quantities shall be increased 100 percent in outdoor control areas.

    g.    Maximum amounts are permitted to be increased to 2,250 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.

    h.   Maximum amounts are permitted to be increased to 4,500 pounds when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 10 pounds each.

    i.    The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in

    accordance with Section 903.3.1.1.

    j.    Quantities are unlimited in an outdoor control area.

    TABLE 4 1 4 . 2 . 5 ( 2 )

     

     

     

    TYPE OF LIQUID

    MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA (gallons)

     

    Sprinklered in accordance with Note b densities and arrangements

    Sprinklered in accordance with Tables 3404.3.6.3(4) through 3404.3.6.3(8) and Table 3404.3.7.5.1 of the f i re  code

     

     

    Nonsprinklered

    Class IA

    60

    60

    30

    Class IB, IC, II and IIIA

    7,500c

    15,000c

    1,600

    Class IIIB

    Unlimited

    Unlimited

    13,200

     

     
    MAXI MUM A LLOWABLE QUANTITY OF FLAMMABLE AND C O MBUSTIBLE LIQUID S IN WHOLESALE AND RETAIL SALES OCCUPANCIES PER CONTROL A R E A a

    For SI: 1 foot= 304.8 mm, 1 square foot = 0.0929 m2,1 gallon = 3.785 L, 1 gallon per minute per square foot = 40.75 L/min/m2. a. Control areas shall be separated from each other by not less than a 1-hour f i r e barrier wall.

    b. To be considered as sprinklered, a building shall be equipped throughout with an approved automatic sprinkler system with a design providing minimum densities as follows:

    1.   For uncartoned commodities on shelves 6 feet or less in height where the ceiling height does not exceed 18 feet, quantities are those permitted with a minimum sprinkler design density of Ordinary Hazard Group 2.

    2.  For cartoned, palletized or racked commodities where storage is 4 feet 6 inches or less in height and where the ceiling height does not exceed 18 feet, quantities are those permitted with a minimum sprinkler design density of 0.21 gallon per minute per square foot over the most remote 1,500-square-foot area.

    c. Where wholesale and retail sales or storage areas exceed 50,000 square feet in area, the maximum allowable quantities are allowed to be increased by 2 percent for each 1,000 square feet of area in excess of 50,000 square feet, up to a maximum of 100 percent of the table amounts. A control area separation is not required. The cumulative amounts, including amounts attained by having an additional control area, shall not exceed 30,000 gallons.

    of egress to a public way shall not be less than the distance required for an outside hazardous material storage or use area without weather protection.

    414.6.1.3 Noncombustible construction. The over-head structure shall be of approved noncombustible construction with a maximum area of 1,500 square feet (140

    m2).

    Exception: The increases permitted by Section 506 apply.

    414.7Emergency alarms. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein.

    414.7.1Storage. An approved manual emergency alarm system shall be provided in buildings, rooms or areas used for storage of hazardous materials. Emergency alarm-initiating devices shall be installed outside of each interior exit or exit access door of storage buildings, rooms or areas. Activation of an

    emergency alarm-initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials.

    414.7.2Dispensing, use and handling. Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 150-foot (45 720 mm) intervals and at each exit and exit access doorway through-out the transport route. The signal shall be relayed to an approved central, proprietary or remote station service or constantly attended on-site location and shall also initiate a local audible alarm.

    414.7.3Supervision. Emergency alarm systems shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location.

    SECTION 415

    GROUPS H-1, H-2, H-3, H-4 AND H-5

    415.1Scope. The provisions of this section shall apply to the storage and use of hazardous materials in excess of the maximum allowable quantities per control area listed in Section 307.1. Buildings and structures with an occupancy in Group H shall also comply with the applicable provisions of Section 414 and the "International Fire Code".

    415.2Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in the code, have the meanings shown herein.

    CONTINUOUS GAS-DETECTION SYSTEM. A gas detection system where the analytical instrument is maintained in continuous operation and sampling is performed without interruption. Analysis is allowed to be performed on a cyclical basis at intervals not to exceed 30 minutes.

    EMERGENCY CONTROL STATION. An approved location on the premises where signals from emergency equipment are received and which is staffed by trained personnel.

    EXHAUSTED ENCLOSURE. An appliance or piece of equipment that consists of a top, a back and two sides providing a means of local exhaust for capturing gases, fumes, vapors and mists. Such enclosures include laboratory hoods, exhaust fume hoods and similar appliances and equipment used to locally retain and exhaust the gases, fumes, vapors and mists that could be released. Rooms or areas provided with general ventilation, in themselves, are not exhausted enclosures.

    FABRICATION AREA. An area within a semiconductor fabrication facility and related research and development areas in which there are processes using hazardous production materials. Such areas are allowed to include ancillary rooms or areas such as dressing rooms and offices that are directly related to the fabrication area processes.

    FLAMMABLE VAPORS OR FUMES. Mixtures of gases in air at concentrations equal to or greater than the lower flammability limit (LFL) and less than or equal to the upper flammability limit (UFL).

    GAS CABINET. A fully enclosed, noncombustible enclosure used to provide an isolated environment for compressed gas cylinders in storage or use. Doors and access ports for exchanging cylinders and accessing pressure-regulating controls are allowed to be included.

    GAS ROOM. A separately ventilated, fully enclosed room in which only compressed gases and associated equipment and supplies are stored or used.

    HAZARDOUS PRODUCTION MATERIAL (HPM). A solid, liquid or gas associated with semiconductor manufacturing that has a degree-of-hazard rating in health, flammability or reactivity of Class 3 or 4 as ranked by NFPA 704 and which is used directly in research, laboratory or production processes that have as their end product materials that are not hazardous.

    HPM FLAMMABLE LIQUID. An HPM liquid that is defined as either a Class I flammable liquid or a Class II or Class IIIA combustible liquid.

    HPM ROOM. A room used in conjunction with or serving a Group H-5 occupancy, where HPM is stored or used and which is classified as a Group H-2, H-3 or H-4 occupancy.

    IMMEDIATELY  DANGEROUS  TO  LIFE  AND  HEALTH  (IDLH).  The

    concentration of air-borne contaminants which poses a threat of death, immediate or delayed permanent adverse health effects, or effects that could prevent

    TABLE 4 14.5.1

    EXPLOSION CONTROL R E Q U I R E M E N T S a

     

     

    MATERIAL

     

     

    CLASS

    EXPLOSION CONTROL METHODS

     

     

    Barricade construction

    Explosion (deflagration) venting or explosion (deflagration) prevention systemsb

    HAZARD CATEGORY

     

     

    Combustible dustsc

    -

    Not Required

    Required

    Cryogenic flammables

    -

    Not Required

    Required

    a.   See Section 414.1.3.

    b. See the fire code.

    c.   As generated during manufacturing or processing. See definition of "Combustible dust" in Chapter 3.

    d.   Storage or use.

    e.   In open use or dispensing.

    f.    Rooms containing dispensing and use of hazardous materials when an explosive environment can occur because of the characteristics or nature of the hazardous materials or as a result of the dispensing or use process.

    g.   A method of explosion control shall be provided when Class 2 water-reactive materials can form potentially explosive mixtures.

    escape from such an environment. This contaminant concentration level is established by the National Institute of Occupational Safety and Health (NIOSH) based on both toxicity and flammability. It generally is expressed in parts per million by volume (ppm v/v) or milligrams per cubic meter (mg/m3). If adequate

    data do not exist for precise establishment of IDLH concentrations, an independent certified industrial hygienist, industrial toxicologist, appropriate regulatory agency or other source approved by the code official shall make such determination.

    LIQUID. A material that has a melting point that is equal to or less than 68°F (20°C) and a boiling point that is greater than 68°F (20°C) at 14.7 pounds per square inch absolute (psia) (101 kPa). When not otherwise identified, the term "liquid" includes both flammable and combustible liquids.

    LIQUID STORAGE ROOM. A room classified as a Group H-3 occupancy used

    for the storage of flammable or combustible liquids in a closed condition.

    LIQUID USE, DISPENSING AND MIXING ROOMS. Rooms in which Class I, II and IIIA flammable or combustible liquids are used, dispensed or mixed in open containers.

    LOWER FLAMMABLE LIMIT (LFL). The minimum concentration of vapor in air at which propagation of flame will occur in the presence of an ignition source. The LFL is some-times referred to as "LEL" or "lower explosive limit."

    NORMAL TEMPERATURE AND PRESSURE (NTP). A temperature of 70°F (21°C) and a pressure of 1 atmosphere [14.7 psia (101 kPa)].

    PHYSIOLOGICAL WARNING THRESHOLD LEVEL. A concentration of air-borne contaminants, normally expressed in parts per million (ppm) or milligrams per cubic meter, that represents the concentration at which persons can sense the presence of the contaminant due to odor, irritation or other quick-acting physiological response. When used in conjunction with the permissible exposure limit (PEL) the physiological warning threshold levels are those consistentwith the classification system used to establish the PEL. See the definition of "Permissible exposure limit (PEL)"in the fire code.

    SERVICE CORRIDOR. A fully enclosed passage used for transporting HPM and purposes other than required means of egress.

    SOLID. A material that has a melting point, decomposes or sublimes at a temperature greater than 68°F (20°C).

    STORAGE, HAZARDOUS MATERIALS.

    1.    The keeping, retention or leaving of hazardous materials in closed containers, tanks, cylinders or similar vessels, or

    2.    Vessels supplying operations through closed connections to the vessel.

    USE (MATERIAL). Placing a material into action, including solids, liquids and gases.

    WORKSTATION. A defined space or an independent principal piece of equipment using HPM within a fabrication area where a specific function, laboratory procedure or research activity occurs. Approved or listed hazardous materials storage cabinets, flammable liquid storage cabinets or gas cabinets serving a workstation are included as part of the workstation. A workstation is allowed to contain ventilation equipment, fire protection devices, detection devices, electrical devices and other processing and scientific equipment.

    415.3Fire separation distance. Group H occupancies shall be located on property in accordance with the other provisions of this chapter. In Groups H-2 and H-3, not less than 25 percent of the perimeter wall of the occupancy shall be an exterior wall.

    Exceptions:

    1. Liquid use, dispensing and mixing rooms having a floor area of not more than 500 square feet (46.5 m2) need not be located on the outer perimeter of the building where they are in accordance with the fire code and NFPA 30.

    2. Liquid storage rooms having a floor area of not more than 1,000 square feet (93 m2) need not be located on the outer perimeter where they are in accordance with the fire code and NFPA 30.

    3. Spray paint booths that comply with the fire code need not be located on the outer perimeter.

    415.3.1Group H occupancy minimum fire separation distance. Regardless of any other provisions, buildings containing Group H occupancies shall be set back to the minimum fire separation distance as set forth in Items 1 through 4 below. Distances shall be measured from the walls enclosing the occupancy to lot lines, including those on a public way. Distances to assumed lot lines established for the purpose of determining exterior wall and opening protection are not to be used to establish the minimum fire separation distance for buildings on sites where explosives are manufactured or used when separation is provided in accordance with the quantity distance tables specified for explosive materials in the "International Fire Code".

    Exception: All buildings used in the manufacturing, storage, or sale of fireworks shall be located in accordance with the fire code.

    1.Group H-1. Not less than 75 feet (22 860 mm) and not less than required by the "International Fire Code".

    Exceptions:

    1. Deleted.

    2. Buildings containing the following materials when separated in accordance with Table 415.3.1:

    2.1.Organic peroxides, unclassified detonable. 2.2. Unstable reactive materials, Class 4.

    2.3. Unstable reactive materials, Class 3 detonable. 2.4. Detonable pyrophoric materials.

    2.Group H-2. Not less than 30 feet (9144 mm) where the area of the occupancy exceeds 1,000 square feet (93 m2) and it is not required to be located in a detached building.

    Table 415.3.1

    MINIMUM SEPARATION DISTANCES FOR BUILDINGS CONTAINING E X PLOSIVE MATERIALS

     

    QUANTITY OF EXPLOSIVE MATERIALa

    MINIMUM DISTANCE (feet)

    Lot linesb and inhabited buildingsc

    Separation of magazinesd, e, f

    Pounds over

    Pounds not over

    Barricadedd

    Unbarricaded

    2

    5

    70

    140

    12

    5

    10

    90

    180

    16

    10

    20

    110

    220

    20

    20

    30

    125

    250

    22

    30

    40

    140

    280

    24

    40

    50

    150

    300

    28

    50

    75

    170

    340

    30

    75

    100

    190

    380

    32

    100

    125

    200

    400

    36

    125

    150

    215

    430

    38

    150

    200

    235

    470

    42

    200

    250

    255

    510

    46

    250

    300

    270

    540

    48

    300

    400

    295

    590

    54

    400

    500

    320

    640

    58

    500

    600

    340

    680

    62

    600

    700

    355

    710

    64

    700

    800

    375

    750

    66

    800

    900

    390

    780

    70

    900

    1,000

    400

    800

    72

    1,000

    1,200

    425

    850

    78

    1,200

    1,400

    450

    900

    82

    1,400

    1,600

    470

    940

    86

    1,600

    1,800

    490

    980

    88

    1,800

    2,000

    505

    1,010

    90

    2,000

    2,500

    545

    1,090

    98

    2,500

    3,000

    580

    1,160

    104

    3,000

    4,000

    635

    1,270

    116

    4,000

    5,000

    685

    1,370

    122

    5,000

    6,000

    730

    1,460

    130

    6,000

    7,000

    770

    1,540

    136

    7,000

    8,000

    800

    1,600

    144

    8,000

    9,000

    835

    1,670

    150

    9,000

    10,000

    865

    1,730

    156

    10,000

    12,000

    875

    1,750

    164

    12,000

    14,000

    885

    1,770

    174

    14,000

    16,000

    900

    1,800

    180

    16,000

    18,000

    940

    1,880

    188

    18,000

    20,000

    975

    1,950

    196

    20,000

    25,000

    1,055

    2,000

    210

    25,000

    30,000

    1,130

    2,000

    224

    30,000

    35,000

    1,205

    2,000

    238

    35,000

    40,000

    1,340

    2,000

    248

    40,000

    45,000

    1,340

    2,000

    258

    45,000

    50,000

    1,400

    2,000

    270

    50,000

    55,000

    1,460

    2,000

    280

    55,000

    60,000

    1,515

    2,000

    290

    60,000

    65,000

    1,565

    2,000

    300

    65,000

    70,000

    1,610

    2,000

    310

    70,000

    75,000

    1,655

    2,000

    320

    75,000

    80,000

    1,695

    2,000

    330

    80,000

    85,000

    1,730

    2,000

    340

    85,000

    90,000

    1,760

    2,000

    350

    90,000

    95,000

    1,790

    2,000

    360

    95,000

    100,000

    1,815

    2,000

    370

    100,000

    110,000

    1,835

    2,000

    390

    110,000

    120,000

    1,855

    2,000

    410

    120,000

    130,000

    1,875

    2,000

    430

    130,000

    140,000

    1,890

    2,000

    450

    140,000

    150,000

    1,900

    2,000

    470

    150,000

    160,000

    1,935

    2,000

    490

    160,000

    170,000

    1,965

    2,000

    510

    170,000

    180,000

    1,990

    2,000

    530

    180,000

    190,000

    2,010

    2,010

    550

    190,000

    200,000

    2,030

    2,030

    570

    200,000

    210,000

    2,055

    2,055

    590

    210,000

    230,000

    2,100

    2,100

    630

    230,000

    250,000

    2,155

    2,155

    670

    250,000

    275,000

    2,215

    2,215

    720

    275,000

    300,000

    2,275

    2,275

    770

    For SI: 1 pound = 0.454 kg, 1 foot = 304.8 mm, 1 square foot = 0.0929m2.

    a.    The number of pounds of explosives listed is the number of pounds of trinitrotoluene (TNT) or the equivalent pounds of other explosive.

    b.   The distance listed is the distance to lot line, including lot lines at public ways.

    c.  For the purpose of this table, an inhabited building is any building on the same lot that is regularly occupied by people. Where two or more buildings containing explosives or magazines are located on the same lot, each building or magazine shall comply with the minimum distances specified from inhabited buildings and, in addition, they shall be separated from each other by not less than the distance shown for "Separation of magazines," except that the quantity of explosive materials contained in detonator buildings or magazines shall govern in regard to the spacing of said detonator buildings or magazines from buildings or magazines containing other explosive materials. If any two or more buildings or magazines are separated from each other by less than the specified "Separation of Magazines" distances, then such two or more buildings or magazines, as a group, shall be considered as one building or magazine, and the total quantity of explosive materials stored in such group shall be treated as if the explosive were in a single building or magazine located on the site of any building or magazine of the group, and shall comply with the minimum distance specified from other magazines or inhabited buildings.

    d.   Barricades shall effectively screen the building containing explosives from other buildings, public ways or magazines. Where mounds or revetted walls of earth are used for barricades, they shall not be less than 3 feet in thickness. A straight line from the top of any side wall of the building containing explosive materials to the eave line of any other building, magazine or a point 12 feet above the centerline of a public way shall pass through the barricades.

    e. Magazine is a building or structure, other than an operating building, approved for storage of explosive materials. Portable or mobile magazines not exceeding 120 square feet in area need not comply with the requirements of this code, however, all magazines shall comply with the "International Fire Code".

    f. The distance listed is permitted to be reduced by 50 percent where approved natural or artificial barriers are provided in accordance with the requirements in Note d.

    3.    Groups H-2 and H-3. Not less than 50 feet (15 240 mm) where a detached building is required (see Table 415.3.2).

    4.    Groups H-2 and H-3. Occupancies containing materials with explosive

    characteristics shall be separated as required by the "International Fire Code". Where separations are not specified, the distances required shall not be less than the distances required by Table 415.3.1.

    415.3.2Group H-1 and H-2 or H-3 detached buildings. Where a detached building is required by Table 415.3.2, there are no requirements for wall and opening protection based on fire separation distance.

    415.4Special provisions for Group H-1 occupancies. Group H-1 occupancies shall be in buildings used for no other purpose, shall not exceed one story in height and be without a basement, crawl spaces or other under-floor spaces. Roofs shall be of lightweight construction with suitable thermal insulation to prevent sensitive material from reaching its decomposition temperature.

    Group H-1 occupancies containing materials which are in themselves both physical and health hazards in quantities exceeding the maximum allowable quantities per control area in Table 307.1.(2) shall comply with requirements for both Group H-1 and H-4 occupancies.

    415.4.1Floors in storage rooms. Floors in storage areas for organic peroxides, pyrophoric materials and unstable (reactive) materials shall be of liquid-tight, noncombustible construction.

    415.5Special provisions for Group H-2 and H-3 occupancies. Group H-2 and H-3 occupancies containing quantities of hazardous materials in excess of those set forth in Table 415.3.2 shall be in buildings used for no other purpose, shall not exceed one story in height and shall be without basements, crawl spaces or other under-floor spaces.

    Group H-2 and H-3 occupancies containing water-reactive materials shall be resistant to water penetration. Piping for conveying liquids shall not be over or through areas containing water reactives, unless isolated by approved liquid-tight construction.

    Exception: Fire protection piping.

    415.5.1Floors in storage rooms. Floors in storage areas for organic peroxides, oxidizers, pyrophoric materials, unstable (reactive) materials and water-reactive solids and liquids shall be of liquid-tight, noncombustible construction.

    TABLE 4 1 5 . 3 . 2

    REQUIRED DETACHED STORAGE

    DETACHED STORAGE IS REQUIRED WHEN THE QUANTITY OF MATERIAL EXCEEDS THAT LISTED HEREIN

    Material

    Class

    Solids and Liquids ( tons) a,b

    Gases (cubic feet) a,b

    For SI: 1 ton = 906 kg, 1 cubic foot = 0.02832 m3, 1 pound = 0.454 kg.

    a.    For materials that are detonable, the distance to other buildings or lot lines shall be as specified in Table 415.3.1 based on trinitrotoluene (TNT) equivalence of the material. For materials classified as explosives, see Chapter 33 the "International Fire Code". For all other materials, the distance shall be as indicated in Section 415.3.1.

    b.   "Maximum Allowable Quantity" means the maximum allowable quantity per control area set forth in Table 307.7(1).

    c.    Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco and Firearms (BATF) regulations or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing the net explosive weight of individual articles does not exceed 1 pound.

    415.5.2Waterproof room. Rooms or areas used for the storage of water- reactive solids and liquids shall be constructed in a manner that resists the penetration of water through the use of waterproof materials. Piping carrying water for other than approved automatic fire sprinkler systems shall not be within such rooms or areas.

    415.6Group H-2. Occupancies in Group H-2 shall be constructed in accordance with Sections 415.6.1 through 415.6.4 and the "International Fire Code".

    415.6.1Combustible dusts, grain processing and storage. The provisions of Sections 415.6.1.1 through 415.6.1.6 shall apply to buildings in which materials that produce combustible dusts are stored or handled. Buildings that store or handle combustible dusts shall comply with the applicable provisions of NFPA 61, NFPA 120, NFPA 484, NFPA 654, NFPA 655, NFPA 664 and

    NFPA 85, and the fire code.

    415.6.1.1Type of construction and height exceptions. Buildings shall be constructed in compliance with the height and area limitations of Table 503 for Group H-2; except that where erected of Type I or II construction, the heights

    and areas of grain elevators and similar structures shall be unlimited, and where of Type IV construction, the maximum height shall be 65 feet (19 812 mm) and except further that, in isolated areas, the maxi-mum height of Type IV structures shall be increased to 85 feet (25 908 mm).

    415.6.1.2Grinding rooms. Every room or space occupied for grinding or other operations that produce combustible dusts shall be enclosed with fire barriers that have not less than a 2-hour fire-resistance rating where the area is not more than 3,000 square feet (279 m2), and not less than a 4-hour fire-resistance rating where the area is greater than 3,000 square feet (279 m2).

    415.6.1.3Conveyors. Conveyors, chutes, piping and similar equipment passing through the enclosures of rooms or spaces shall be constructed dirt tight and vapor tight, and be of approved noncombustible materials complying with Chapter 30.

    415.6.1.4Explosion control. Explosion control shall be provided as specified in the fire code, or spaces shall be equipped with the equivalent mechanical ventilation complying with the mechanical code.

    415.6.1.5   Grain elevators. Grain elevators, malt houses and buildings for similar occupancies shall not be located within 30 feet (9144 mm) of interior lot lines or structures on the same lot, except where erected along a railroad right-of-way.

    415.6.1.6   Coal pockets. Coal pockets located less than 30 feet (9144 mm) from interior lot lines or from structures on the same lot shall be constructed of not less than Type IB construction. Where more than 30 feet (9144 mm) from interior lot lines, or where erected along a railroad right- of-way, the minimum type of construction of such structures not more than 65 feet (19 812 mm) in height shall be Type IV.

    415.6.2Flammable and combustible liquids. The storage, handling, processing and transporting of flammable and combustible liquids shall be in accordance with the mechanical code and the "International Fire Code".

        Exception: The design, installation, registration, and inspection of regulated underground storage tanks shall be in accordance with the fire code and rules adopted by the state fire marshal and enforced by the fire official, in accordance with sections 3737.87 to 3737.89 of the Revised Code.

    415.6.2.1Mixed occupancies. Where the storage tank area is located in a building of two or more occupancies, and the quantity of liquid exceeds the maximum allowable quantity for one control area, the use shall be completely separated from adjacent fire areas in accordance with the requirements of

    Section 508.3.3.

    415.6.2.1.1 Height exception. Where storage tanks are located within only a single-story building, the height limitation of Section 503 shall not apply for Group H.

    415.6.2.2Tank protection. Storage tanks shall be noncombustible and protected from physical damage. A fire barrier wall or horizontal assemblies or both around the storage tank(s) shall be permitted as the method of protection from physical damage.

    415.6.2.3Tanks. Storage tanks shall be approved tanks conforming to the requirements of the "International Fire Code".

    415.6.2.4Suppression. Group H shall be equipped throughout with an approved automatic sprinkler system, installed in accordance with Section 903.

    415.6.2.5Leakage containment. A liquid-tight containment area compatible with the stored liquid shall be provided. The method of spill control, drainage control and secondary containment shall be in accordance with the fire code.

    Exception: Rooms where only double-wall storage tanks conforming to Section 415.6.2.3 are used to store Class I, II and IIIA flammable and combustible liquids shall not be required to have a leakage containment area.

    415.6.2.6Leakage alarm. An approved automatic alarm shall be provided to indicate a leak in a storage tank and room. The alarm shall sound an audible signal, 15 dBa above the ambient sound level, at every point of entry into the room in which the leaking storage tank is located. An approved sign shall be posted on every entry door to the tank storage room indicating the potential hazard of the interior room environment, or the sign shall state: WARNING, WHEN ALARM SOUNDS, THE ENVIRONMENT WITHIN THE ROOM

    MAY BE HAZARDOUS. The leakage alarm shall also be supervised in accordance with Chapter 9 to transmit a trouble signal.

    415.6.2.7Tank vent. Storage tank vents for Class I, II or IIIA liquids shall terminate to the outdoor air in accordance with the fire code.

    415.6.2.8Room ventilation. Storage tank areas storing Class I, II or IIIA liquids shall be provided with mechanical ventilation. The mechanical ventilation system shall be in accordance with the mechanical code and the  fire code.

    415.6.2.9Explosion venting. Where Class I liquids are being stored, explosion venting shall be provided in accordance with the fire code.

    415.6.2.10Tank openings other than vents. Tank openings other than vents

    from tanks inside buildings shall be designed to ensure that liquids or vapor concentrations are not released inside the building.

    415.6.3Liquefied petroleum gas-distribution facilities. The design and construction of propane, butane, propylene, butylene and other liquefied petroleum gas-distribution facilities shall conform to the applicable provisions of Sections 415.6.3.1 through 415.6.3.5.2. The storage and handling of liquefied petroleum gas systems shall conform to the "International Fire Code". The design and installation of piping, equipment and systems that utilize liquefied petroleum gas shall be in accordance with the "International Fuel Gas Code". Liquefied petroleum gas-distribution facilities shall be ventilated in accordance with the mechanical code and Section 415.6.3.1.

    415.6.3.1Air movement. Liquefied petroleum gas-distribution facilities shall be provided with air inlets and outlets arranged so that air movement across the floor of the facility will be uniform. The total area of both inlet and outlet openings shall be at least 1 square inch (645 mm2) for each 1 square foot (0.093 m2) of floor area. The bottom of such openings shall not be more than 6 inches (152 mm) above the floor.

    415.6.3.2Construction. Liquefied petroleum gas-distribution facilities shall be constructed in accordance with Section 415.6.3.3 for separate buildings, Section 415.6.3.4 for attached buildings or Section 415.6.3.5 for rooms within buildings.

    415.6.3.3Separate buildings. Where located in separate buildings, liquefied petroleum gas-distribution facilities shall be occupied exclusively for that purpose or for other purposes having similar hazards. Such buildings shall be limited to one story in height and shall con-form to Sections 415.6.3.3.1 through 415.6.3.3.3.

    415.6.3.3.1                     Floors. The floor shall not be located below ground level and any spaces beneath the floor shall be solidly filled or shall be unenclosed.

    415.6.3.3.2                     Materials. Walls, floors, ceilings, columns and roofs shall be constructed of noncombustible materials.

    415.6.3.3.3                     Explosion venting. Explosion venting shall be provided in accordance with the fire code.

    415.6.3.4Attached buildings. Where liquefied petroleum gas-distribution facilities are located in an attached structure, the attached perimeter shall not exceed 50 percent of the perimeter of the space enclosed and the facility shall comply with Sections 415.6.3.3 and 415.6.3.4.1. Where the attached perimeter exceeds 50 percent, such facilities shall comply with Section 415.6.3.5.

    415.6.3.4.1Fire separation. Separation of the attached structures shall be provided by fire barriers having a fire-resistance rating of not less than 1 hour and shall not have openings. Fire barriers between attached structures occupied only for the storage of LP-gas are permitted to have fire door assemblies that comply with Section 715. Such fire barriers shall be designed to withstand a static pressure of at least 100 pounds per square foot (psf) (4788 Pa), except where the building to which the structure is attached is occupied by operations or processes having a similar hazard.

    415.6.3.5Rooms within buildings. Where liquefied petroleum gas- distribution facilities are located in rooms within buildings, such rooms shall be located in the first story above grade plane and shall have at least one exterior wall with sufficient exposed area to provide explosion venting as required in the fire code. The building in which the room is located shall not have a basement or unventilated crawl space and the room shall comply with Sections 415.6.3.5.1 and 415.6.3.5.2.

    415.6.3.5.1Materials. Walls, floors, ceilings and roofs of such rooms shall be constructed of approved noncombustible materials.

    415.6.3.5.2Common construction. Walls and floor/ceiling assemblies common to the room and to the building where the room is located shall be fire barriers with not less than a 1-hour fire-resistance rating and without openings. Common walls for rooms occupied only for storage of LP-gas are permitted to have opening protectives complying with Section 715. The walls and ceilings shall be designed to with-stand a static pressure of at least 100 psf (4788 Pa).

    Exception: Where the building, within which the room is located, is occupied by operations or processes having a similar hazard.

    415.6.4Dry cleaning plants. The construction and installation of dry cleaning plants shall be in accordance with the requirements of this code, the mechanical code, the plumbing code and NFPA 32. Dry cleaning solvents and systems shall be classified in accordance with the fire code.

    415.7Groups H-3 and H-4. Groups H-3 and H-4 shall be constructed in accordance with the applicable provisions of this code and the "International Fire Code".

    415.7.1Gas rooms. When gas rooms are provided, such rooms shall be separated from other areas by not less than a 1-hour fire barrier.

    415.7.2Floors in storage rooms. Floors in storage areas for corrosive liquids and highly toxic or toxic materials shall be of liquid-tight, noncombustible construction.

    415.7.3Separation-highly toxic solids and liquids. Highly toxic solids and liquids not stored in approved hazardous materials storage cabinets shall be isolated from other hazardous materials storage by a fire barrier having a fire- resistance rating of not less than 1 hour.

    415.7.4Consumer fireworks facilities. In addition to other applicable provisions of this code and the fire code, this section shall apply to all structures where consumer fireworks, 1.4G are located for display, sales, or storage.

    415.7.4.1Area limitation. H-3 fire areas used for the display and sale of consumer fireworks, 1.4G shall not exceed five thousand square feet.

    415.7.4.2Fire separation. Areas used for the display and sale of consumer fireworks, 1.4G shall be separated from areas used for the storage of consumer fireworks, 1.4G with fire barriers that comply with section 706.

    415.7.4.3Smoke control. A smoke control system shall be provided throughout all display and sales areas in accordance with section 909.

    415.7.4.4Awnings, tents, and canopies.  Awnings, tents, and canopies shall not be used for the display, sale or storage of consumer fireworks, 1.4G.

    415.7.4.5Exits.  Horizontal exits shall not be used as a required exit leading from display and sale areas.

    415.8Group H-5.

    415.8.1General. In addition to the requirements set forth elsewhere in this code, Group H-5 shall comply with the provisions of Section 415.8 and the "International Fire Code".

    415.8.2Fabrication areas.

    415.8.2.1Hazardous materials in fabrication areas.

    415.8.2.1.1                     Aggregate quantities. The aggregate quantities of hazardous materials stored and used in a single fabrication area shall not exceed the quantities set forth in Table 415.8.2.1.1.

    Exception: The quantity limitations for any hazard category in Table 415.8.2.1.1 shall not apply where the fabrication area contains quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by Tables 307.1(1) and 307.1(2).

    415.8.2.1.2                     Hazardous production materials. The maximum quantities of hazardous production materials (HPM) stored in a single fabrication area shall not exceed the maximum allowable quantities per control area established by Tables 307.1(1) and 307.1(2).

    415.8.2.2Separation. Fabrication areas, whose sizes are limited by the quantity of hazardous materials allowed by Table 415.8.2.1.1, shall be separated from each other, from corridors and from other parts of the building by not less than 1-hour fire barriers.

    Exceptions:

    1. Doors within such fire barrier walls, including doors to corridors, shall be only self-closing fire door assemblies having a fire protection rating of not less than ¾ hour.

    2. Windows between fabrication areas and corridors are permitted to be fixed glazing listed and labeled for a fire protection rating of at least

    ¾ hour in accordance with Section 715.

    415.8.2.3Location of occupied levels. Occupied levels of fabrication areas shall be located at or above the first story above grade plane.

    415.8.2.4Floors. Except for surfacing, floors within fabrication areas shall be of noncombustible construction.

    Openings through floors of fabrication areas are permitted to be unprotected where the interconnected levels are used solely for mechanical equipment directly related to such fabrication areas (see also Section 415.8.2.5).

    Floors forming a part of an occupancy separation shall be liquid tight.

    415.8.2.5Shafts and openings through floors. Elevator shafts, vent shafts and other openings through floors shall be enclosed when required by Section 707. Mechanical, duct and piping penetrations within a fabrication area shall not extend through more than two floors. The annular space around penetrations for cables, cable trays, tubing, piping, conduit or ducts shall be sealed at the floor level to restrict the movement of air. The fabrication area, including the areas through which the ductwork and piping extend, shall be considered a single conditioned environment.

    415.8.2.6Ventilation. Mechanical exhaust ventilation at the rate of not less than 1 cubic foot per minute per square foot (0.044 L/s/m2) of floor area shall be provided throughout the portions of the fabrication area where HPM are used or stored. The exhaust air duct system of one fabrication area shall not connect to another duct system outside that fabrication area within the building.

    A ventilation system shall be provided to capture and exhaust gases, fumes and vapors at workstations.

    Two or more operations at a workstation shall not be connected to the same exhaust system where either one or the combination of the substances removed could constitute a fire, explosion or hazardous chemical reaction within the exhaust duct system.

    Exhaust ducts penetrating occupancy separations shall be contained in a shaft of equivalent fire-resistance-rated construction. Exhaust ducts shall not penetrate fire walls.

    Fire dampers shall not be installed in exhaust ducts.

    415.8.2.7Transporting hazardous production materials to fabrication areas.  HPM shall be transported to fabrication areas through enclosed piping or tubing systems that comply with Section 415.8.6.1, through service corridors complying with Section 415.8.4, or in corridors as permitted in the exception to Section 415.8.3. The handling or transporting of HPM within service corridors shall comply with the fire code.

    415.8.2.8Electrical.

    415.8.2.8.1General. Electrical equipment and devices within the fabrication area shall comply with Chapter 27. The requirements for hazardous locations need not be applied where the average air change is at least four times that set forth in Section 415.8.2.6 and where the number of air changes at any location is not less than three times that required by Section 415.8.2.6. The use of recirculated air shall be permitted.

    TABLE 415.8.2.1.1

    QUANTITY LIMITS FOR H A Z A R D O US M A TERIALS I N A SING LE FABRICATION AREA IN GROUP H-5a

    HAZARD CATEGORY

    SOLIDS

    (pounds per square feet)

    LIQUIDS

    (gallons per square feet)

    GAS

    (feet3 @ NTP/square feet)

    PHYSICAL-HAZARD MATERIALS

    Combustible dust                                                               Note b                                   Not Applicable                            Not Applicable

    Combustible fiber             Loose Baled

    Combustible liquid            II

    IIIA

    Note b

    Notes b, c                                Not Applicable                            Not Applicable

    0.01

    0.02

    IIIB

    Combination Class I, II and IIIA

    Cryogenic gas                Flammable

    Not Applicable

    Not Limited 0.04

    Not Applicable

    Note d

    Oxidizing                             Not Applicable                             Not Applicable

    1.25

    Explosives                                                                          Note b                                          Note b                                          Note b

    Flammable gas               Gaseous

    Liquefied                              Not Applicable                             Not Applicable

    Note d Note d

    Flammable liquid            IA IB IC

    Combination Class IA, IB and IC Combination Class I, II and IIIA

    Not Applicable

    0.0025

    0.025

    0.025

    0.025

    0.04

    Not Applicable

    Flammable solid                                                                  0.001                                    Not Applicable                            Not Applicable

    Organic peroxide Unclassified detonable

    Class I Class II Class III Class IV Class V

    Oxidizing gas          Gaseous Liquefied

    Note b Note b 0.025

    0.1

    Not Limited Not Limited

    Not Applicable                             Not Applicable

    1.25

    1.25

    Combination of gaseous and liquefied

    Not Applicable                             Not Applicable

    1.25

    Oxidizer                  Class 4

    Class 3

    Class 2

    Class 1

    Combination            Class 1, 2, 3

    Note b 0.003

    0.003

    0.003

    0.003

    Note b 0.003

    0.003

    0.003

    0.003

    Not Applicable

    Pyrophoric material                                                            Note b                                         0.00125                                   Notes d and e

    Unstable reactive    Class 4

    Class 3

    Class 2

    Class 1 Water reactive          Class 3

    Class 2

    Class 1

    Note b 0.025

    0.1

    Not Limited

    Note b 0.25

    Not Limited

    Note b 0.0025

    0.01

    Not Limited 0.00125

    0.025

    Not Limited

    Note b Note b Note b

    Not Limited Not Applicable

    HEALTH-HAZARD MATERIALS

    Corrosives                                                                     Not Limited                                 Not Limited                                 Not Limited

    Highly toxic                                                                   Not Limited                                 Not Limited                                      Note d

    Toxics                                                                            Not Limited                                 Not Limited                                      Note d

    For SI: 1 pound per square foot = 4.882 kg/m2, 1 gallon per square foot = 40.7 L/m2, 1 cubic foot @ NTP/square foot =

    0.305 m3 @ NTP/m2, 1 cubic foot = 0.02832 m3.

    a.    Hazardous materials within piping shall not be included in the calculated quantities.

    b.    Quantity of hazardous materials in a single fabrication shall not exceed the maximum allowable quantities per control area in Tables 307.1(1) and 307.1(2).

    c.    Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.

    d.   The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 cubic feet at NTP.

    e.    The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Table 415.3.2.

     415.8.2.8.2 Workstations. Workstations shall not be energized without adequate exhaust ventilation. See Section 415.8.2.6 for workstation exhaust ventilation requirements.

     415.8.3 Corridors. Corridors shall comply with Chapter 10 and shall be separated from fabrication areas as specified in Section 415.8.2.2. Corridors shall not contain HPM and shall not be used for transporting such materials, except through closed piping systems as provided in Section 415.8.6.3.

    Exception: Where existing fabrication areas are altered or modified, HPM is allowed to be transported in existing corridors, subject to the following conditions:

    1. Corridors. Corridors adjacent to the fabrication area where the alteration work is to be done shall comply with Section 1017 for a length determined as follows:

    1.1 The length of the common wall of the corridor and the fabrication area; and

    1.2.For the distance along the corridor to the point of entry of HPM into the corridor serving that fabrication area.

    2. Emergency alarm system. There shall be an emergency telephone system, a local manual alarm station or other approved alarm-initiating device within corridors at not more than 150-foot (45 720 mm) intervals and at each exit and doorway. The signal shall be relayed to an approved central, proprietary or remote station service or the emergency control station and shall also initiate a local audible alarm.

    3. Pass-throughs. Self-closing doors having a fire protection rating of not less than 1 hour shall separate pass-throughs from existing corridors. Pass- throughs shall be constructed as required for the corridors and protected by an approved automatic fire-extinguishing system.

     415.8.4 Service corridors.

     415.8.4.1 Occupancy. Service corridors shall be classified as Group H-5.

     415.8.4.2 Use conditions. Service corridors shall be separated from corridors as required by Section 415.8.2.2. Service corridors shall not be used as a required corridor.

     415.8.4.3 Mechanical ventilation. Service corridors shall be mechanically ventilated as required by Section 415.8.2.6 or at not less than six air changes per hour, whichever is greater.

     415.8.4.4 Means of egress. The maximum distance of travel from any point in a service corridor to an exit, exit access corridor or door into a fabrication area shall not exceed 75 feet (22 860 mm). Dead ends shall not exceed 4 feet (1219 mm) in length. There shall be not less than two exits, and not more than one- half of the required means of egress shall require travel into a fabrication area. Doors from service corridors shall swing in the direction of egress travel and shall be self-closing.

     415.8.4.5 Minimum width. The minimum clear width of a service corridor shall be 5 feet (1524 mm), or 33 inches (838 mm) wider than the widest cart or truck used in the corridor, whichever is greater.

     415.8.4.6 Emergency alarm system. Emergency alarm systems shall be provided in accordance with this section and Sections 414.7.1 and 414.7.2. The

    maximum allowable quantity per control area provisions shall not apply to emergency alarm systems required for HPM.

     415.8.4.6.1 Service corridors. An emergency alarm system shall be provided in service corridors, with at least one alarm device in each service corridor.

     415.8.4.6.2 Exit access corridors and exit enclosures. Emergency alarms for exit access corridors and exit enclosures shall comply with Section 414.7.2.

     415.8.4.6.3 Liquid storage rooms, HPM rooms and gas rooms. Emergency alarms for liquid storage rooms, HPM rooms and gas rooms shall comply with Section 414.7.1.

     415.8.4.6.4 Alarm-initiating devices. An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices.

     415.8.4.6.5 Alarm signals. Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station.

     415.8.5 Storage of hazardous production materials.

     415.8.5.1 General. Storage of HPM in fabrication areas shall be within approved or listed storage cabinets or gas cabinets or within a workstation. The storage of HPM in quantities greater than those listed in Section 1804.2 of the  fire code shall be in liquid storage rooms, HPM rooms or gas rooms as appropriate for the materials stored. The storage of other hazardous materials shall be in accordance with other applicable provisions of this code and the fire code.

     415.8.5.2 Construction.

     415.8.5.2.1 HPM rooms and gas rooms. HPM rooms and gas rooms shall be separated from other areas by not less than a 2-hour fire barrier where the area is 300 square feet (27.9 m2) or more and not less than a 1-hour fire barrier where the area is less than 300 square feet (27.9 m2).

     415.8.5.2.2  Liquid  storage  rooms.  Liquid  storage  rooms  shall  be constructed in accordance with the following requirements:

    1.    Rooms in excess of 500 square feet (46.5 m2) shall have at least one exterior door approved for fire department access.

    2. Rooms shall be separated from other areas by fire barriers having a fire-resistance rating of not less than 1-hour for rooms up to 150 square feet (13.9 m2) in area and not less than 2 hours where the room

    is more than 150 square feet (13.9 m2) in area.

    3. Shelving, racks and wainscoting in such areas shall be of noncombustible construction or wood of not less than 1inch (25 mm) nominal thickness.

    4.    Rooms used for the storage of Class I flammable liquids shall not be located in a basement.

     415.8.5.2.3 Floors. Except for surfacing, floors of HPM rooms and liquid storage rooms shall be of noncombustible liquid-tight construction. Raised grating over floors shall be of noncombustible materials.

     415.8.5.3 Location. Where HPM rooms, liquid storage rooms and gas rooms are provided, they shall have at least one exterior wall and such wall shall be not less than 30 feet (9144 mm) from lot lines, including lot lines adjacent to public ways.

     415.8.5.4 Explosion control. Explosion control shall be provided where required by Section 414.5.1.

     415.8.5.5 Exits. Where two exits are required from HPM rooms, liquid storage rooms and gas rooms, one shall be directly to the outside of the building.

     415.8.5.6 Doors. Doors in a fire barrier wall, including doors to corridors, shall be self-closing fire door assemblies having a fire-protection rating of not less than 3/4 hour.

     415.8.5.7 Ventilation. Mechanical exhaust ventilation shall be provided in liquid storage rooms, HPM rooms and gas rooms at the rate of not less than 1 cubic foot per minute per square foot (0.044 L/s/m2) of floor area or six air changes per hour, whichever is greater, for categories of material.

    Exhaust ventilation for gas rooms shall be designed to operate at a negative pressure in relation to the surrounding areas and direct the exhaust ventilation to an exhaust system.

     415.8.5.8 Emergency alarm system. An approved emergency alarm system shall be provided for HPM rooms, liquid storage rooms and gas rooms.

    Emergency alarm-initiating devices shall be installed outside of each interior exit door of such rooms.

    Activation of an emergency alarm-initiating device shall sound a local alarm and transmit a signal to the emergency control station.

    An approved emergency telephone system, local alarm manual pull stations or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices.

     415.8.6 Piping and tubing.

     415.8.6.1 General. Hazardous production materials piping and tubing shall comply with this section and the applicable ASME code, as determined by the registered design professional.

    In accordance with section 4104.42 of the Revised Code, the owner is responsible for ensuring compliance with the ASME codes. The construction documents shall identify the types and quantities of hazardous materials proposed to be used in the facility to the extent necessary to enable the building official to determine compliance with this code and the fire code. The building official is not authorized to request or review design calculations, material specifications or construction documents for the piping system or to ascertain compliance with the applicable ASME code.

    415.8.6.2Supply piping and tubing.

     415.8.6.2.1 HPM having a health-hazard ranking of 3 or 4. Systems supplying HPM liquids or gases having a health-hazard ranking of 3 or 4 shall be welded throughout, except for connections, to the systems that are within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for the connections if the material is a liquid.

     415.8.6.2.2 Location in service corridors. Hazardous production materials supply piping or tubing in service corridors shall be exposed to view.

     415.8.6.2.3 Excess flow control. Where HPM gases or liquids are carried in pressurized piping above 15 pounds per square inch gauge (psig) (103.4 kPa), excess flow control shall be provided. Where the piping originates from within a liquid storage room, HPM room or gas room, the excess flow control shall be located within the liquid storage room, HPM room or gas room. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical.

     415.8.6.3 Installations in corridors and above other occupancies. The installation of HPM piping and tubing within the space defined by the walls of corridors and the floor or roof above, or in concealed spaces above other occupancies, shall be in accordance with Section 415.8.6.2 and the following conditions:

    1.    Automatic sprinklers shall be installed within the space unless the space is less than 6 inches (152 mm) in the least dimension.

    2.    Ventilation not less than six air changes per hour shall be provided. The space shall not be used to convey air from any other area.

    3.    Where the piping or tubing is used to transport HPM liquids, a receptor

    shall be installed below such piping or tubing. The receptor shall be designed to collect any discharge or leakage and drain it to an approved location. The 1-hour enclosure shall not be used as part of the receptor.

    4. HPM supply piping and tubing and nonmetallic waste lines shall be separated from the corridor and from occupancies other than Group H-5 by fire barriers that have a fire-resistance rating of not less than 1 hour. Where gypsum wallboard is used, joints on the piping side of the enclosure are not required to be taped, provided the joints occur over framing members. Access openings into the enclosure shall be protected by approved fire protection-rated assemblies.

    5.Readily accessible manual or automatic remotely activated fail-safe emergency shutoff valves shall be installed on piping and tubing other than waste lines at the following locations:

    5.1.At branch connections into the fabrication area. 5.2. At entries into corridors.

    Exception: Transverse crossings of the corridors by supply piping that is enclosed within a ferrous pipe or tube for the width of the corridor need not comply with Items 1 through 5.

     415.8.6.4 Identification. Piping, tubing and HPM waste lines shall be identified in accordance with ANSI A13.1 to indicate the material being transported.

     415.8.7 Continuous gas detection systems. A continuous gas detection system shall be provided for HPM gases when the physiological warning threshold level of the gas is at a higher level than the accepted PEL for the gas and for flammable gases in accordance with this section.

     415.8.7.1 Where required. A continuous gas-detection system shall be provided in the areas identified in Sections 415.8.7.1.1 through 415.8.7.1.4.

     415.8.7.1.1 Fabrication areas. A continuous gas-detection system shall be provided in fabrication areas when gas is used in the fabrication area.

     415.8.7.1.2 HPM rooms. A continuous gas-detection system shall be provided in HPM rooms when gas is used in the room.

     415.8.7.1.3 Gas cabinets, exhausted enclosures and gas rooms. A continuous gas-detection system shall be provided in gas cabinets and exhausted enclosures. A continuous gas-detection system shall be provided in gas rooms when gases are not located in gas cabinets or exhausted enclosures.

     415.8.7.1.4 Corridors. When gases are trans-ported in piping placed within

    the space defined by the walls of a corridor and the floor or roof above the corridor, a continuous gas-detection system shall be provided where piping is located and in the corridor.

    Exception: A continuous gas-detection system is not required for occasional transverse crossings of the corridors by supply piping that is enclosed in a ferrous pipe or tube for the width of the corridor.

     415.8.7.2 Gas-detection system operation. The continuous gas-detection system shall be capable of monitoring the room, area or equipment in which the gas is located at or below the PEL or ceiling limit of the gas for which detection is provided. For flammable gases, the monitoring detection threshold level shall be vapor concentrations in excess of 20 percent of the lower explosive limit (LEL). Monitoring for highly toxic and toxic gases shall also comply with the requirements for such material in the fire code.

     415.8.7.2.1 Alarms. The gas detection system shall initiate a local alarm and transmit a signal to the emergency control station when a short-term hazard condition is detected. The alarm shall be both visual and audible and shall provide warning both inside and outside the area where the gas is detected. The audible alarm shall be distinct from all other alarms.

     415.8.7.2.2 Shutoff of gas supply. The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for which gas is detected when a short-term hazard condition is detected. Automatic closure of shutoff valves shall comply with the following:

    1. Where the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.

    2. Where the gas-detection sampling point initiating the gas detection system alarm is within a room and compressed gas containers are not in gas cabinets or an exhausted enclosure, the shutoff valves on all gas lines for the specific gas detected shall automatically close.

    3. Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve supplying the manifold for the compressed gas container of the specific gas detected shall automatically close.

    Exception: Where the gas-detection sampling point initiating the gas detection system alarm is at the use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold,

    the shutoff valve for the branch line located in the piping distribution manifold enclosure shall automatically close.

     415.8.8 Manual fire alarm system. An approved manual fire alarm system shall be provided throughout buildings containing Group H-5. Activation of the alarm system shall initiate a local alarm and transmit a signal to the emergency control station. The fire alarm system shall be designed and installed in accordance with Section 907.

    415.8.9Emergency control station. An emergency control station shall be provided in accordance with Sections 415.8.9.1 through 415.8.9.3.

    415.8.9.1Location. The emergency control station shall be located on the premises at an approved location outside the fabrication area.

    415.8.9.2Staffing. Trained personnel shall continuously staff the emergency control station.

    415.8.9.3Signals. The emergency control station shall receive signals from emergency equipment and alarm and detection systems. Such emergency equipment and alarm and detection systems shall include, but not be limited to, the following where such equipment or systems are required to be provided either in this chapter or else-where in this code:

    1.    Automatic fire sprinkler system alarm and monitoring systems.

    2.    Manual fire alarm systems.

    3.    Emergency alarm systems.

    4.    Continuous gas-detection systems.

    5.    Smoke detection systems.

    6.    Emergency power system.

    7. Automatic detection and alarm systems for pyrophoric liquids and Class 3 water-reactive liquids required in Section 1805.2.3.5 of the fire code.

    8. Exhaust ventilation flow alarm devices for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in Section 1805.2.3.5 of the fire code.

    415.8.10Emergency power system. An emergency power system shall be provided in Group H-5 occupancies where required in Section 415.8.10.1. The emergency power system shall be designed to supply power automatically to required electrical systems when the normal electrical supply system is interrupted.

     415.8.10.1 Required electrical systems. Emergency power shall be provided for electrically operated equipment and connected control circuits

    for the following systems:

    1.    HPM exhaust ventilation systems.

    2.    HPM gas cabinet ventilation systems.

    3.    HPM exhausted enclosure ventilation systems.

    4.    HPM gas room ventilation systems.

    5.    HPM gas detection systems.

    6.    Emergency alarm systems.

    7.    Manual fire alarm systems.

    8.    Automatic sprinkler system monitoring and alarm systems.

    9.    Automatic alarm and detection systems for pyrophoric liquids and Class 3 water-reactive liquids required in Section 1805.2.3.5 of the fire code.

    10.  Flow alarm switches for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in Section 1805.2.3.5 of the fire code.

    11. Electrically operated systems required elsewhere in this code or in the

    fire code applicable to the use, storage or handling of HPM.

     415.8.10.2 Exhaust ventilation systems. Exhaust ventilation systems are allowed to be designed to operate at not less than one-half the normal fan speed on the emergency power system where it is demonstrated that the level of exhaust will maintain a safe atmosphere.

     415.8.11  Automatic  sprinkler  system  protection  in  exhaust  ducts  for HPM.

     415.8.11.1 Exhaust ducts for HPM. An approved automatic sprinkler system shall be provided in exhaust ducts conveying gases, vapors, fumes, mists or dusts generated from HPM in accordance with this section and the  mechanical code.

     415.8.11.2 Metallic and noncombustible nonmetallic exhaust ducts. An approved automatic sprinkler system shall be provided in metallic and noncombustible nonmetallic exhaust ducts when all of the following con- ditions apply:

    1.    Where the largest cross-sectional diameter is equal to or greater than 10 inches (254 mm).

    2.    The ducts are within the building.

    3.    The ducts are conveying flammable gases, vapors or fumes.

     415.8.11.3 Combustible nonmetallic exhaust ducts. Automatic sprinkler system protection shall be provided in combustible nonmetallic exhaust ducts where the largest cross-sectional diameter of the duct is equal to or

    greater than 10 inches (254 mm).

    Exceptions:

    1.    Ducts listed or approved for applications with-out automatic fire sprinkler system protection.

    2.    Ducts not more than 12 feet (3658 mm) in length installed below ceiling level.

     415.8.11.4 Automatic sprinkler locations. Sprinkler systems shall be installed at 12-foot (3658 mm) intervals in horizontal ducts and at changes in direction. In vertical ducts, sprinklers shall be installed at the top and at alternate floor levels.

    SECTION 416 APPLICATION OF FLAMMABLE FINISHES

     416.1 General. The provisions of this section shall apply to the construction, installation and use of buildings and structures, or parts thereof, for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures or compounds used for painting, varnishing, staining or similar purposes. Such construction and equipment shall comply with the fire code.

     416.2 Spray rooms. Spray rooms shall be enclosed with fire barriers with not less than a 1-hour fire-resistance rating. Floors shall be waterproofed and drained in an approved manner.

     416.2.1 Surfaces. The interior surfaces of spray rooms shall be smooth and shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning, and shall be so designed to confine residues within the room. Aluminum shall not be

    used.

     416.3 Spraying spaces. Spraying spaces shall be ventilated with an exhaust system to prevent the accumulation of flammable mist or vapors in accordance with the mechanical code. Where such spaces are not separately enclosed, noncombustible spray curtains shall be provided to restrict the spread of flammable vapors.

     416.3.1 Surfaces. The interior surfaces of spraying spaces shall be smooth and continuous without edges; shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning; and shall be so designed to confine residues within the spraying space.

    Aluminum shall not be used.

     416.4 Fire protection. An automatic fire-extinguishing system shall be provided

    in all spray, dip and immersing spaces and storage rooms and shall be installed in accordance with Chapter 9.

    SECTION 417 DRYING ROOMS

     417.1 General. A drying room or dry kiln installed within a building shall be constructed entirely of approved noncombustible materials or assemblies of such materials regulated by the approved rules or as required in the general and specific sections of Chapter 4 for special occupancies and where applicable to the general requirements of Chapter 28.

     417.2 Piping clearance. Overhead heating pipes shall have a clearance of not less than 2 inches (51 mm) from combustible contents in the dryer.

     417.3 Insulation. Where the operating temperature of the dryer is 175°F (79°C) or more, metal enclosures shall be insulated from adjacent combustible materials by not less than 12 inches (305 mm) of airspace, or the metal walls shall be lined with ¼-inch (6.35 mm) insulating mill board or other approved equivalent insulation.

     417.4 Fire protection. Drying rooms designed for high-hazard materials and processes, including special occupancies as provided for in Chapter 4, shall be protected by an approved automatic fire-extinguishing system complying with the provisions of Chapter 9.

    SECTION 418 ORGANIC COATINGS

     418.1 Building features. Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements.

     418.2 Location. Organic coating manufacturing operations and operations incidental to or connected therewith shall not be located in buildings having other occupancies.

     418.3 Process mills. Mills operating with close clearances and that process flammable and heat-sensitive materials, such as nitrocellulose, shall be located in a detached building or noncombustible structure.

     418.4 Tank storage. Storage areas for flammable and combustible liquid tanks inside of structures shall be located at or above grade and shall be separated from the processing area by not less than 2-hour fire barriers.

     418.5 Nitrocellulose storage. Nitrocellulose storage shall be located on a

    detached pad or in a separate structure or a room enclosed with no less than 2- hour fire barriers.

     418.6 Finished products. Storage rooms for finished products that are flammable or combustible liquids shall be separated from the processing area by fire barriers having a fire-resistance rating of at least 2 hours, and openings in the walls shall be protected with approved opening protectives.

    SECTION 419 GROUP I-1, R-1, R-2, R-3

    419.1General. Occupancies in Groups I-1, R-1, R-2 and R-3 shall comply with the provisions of this section and other applicable provisions of this code.

    419.2Separation walls. Walls separating dwelling units in the same building and walls separating sleeping units in the same building shall comply with Section 708.

    419.3Horizontal separation. Floor/ceiling assemblies separating dwelling units in the same buildings and floor/ceiling assemblies separating sleeping units in the same building shall be constructed in accordance with Section 711.

    SECTION 420 HYDROGEN CUTOFF ROOMS

     420.1 General. When required by the fire code, hydrogen cutoff rooms shall be designed and constructed in accordance with this section.

     420.2 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein.

     GASEOUS HYDROGEN SYSTEM. An assembly of piping, devices and apparatus designed to generate, store, contain, distribute or transport a nontoxic, gaseous hydrogen-containing mixture having at least 95-percent hydrogen gas by volume and not more than 1-percent oxygen by volume. Gaseous hydrogen systems consist of items such as compressed gas containers, reactors and appurtenances, including pressure regulators, pressure relief devices, manifolds, pumps, compressors and interconnecting piping and tubing and controls.

     HYDROGEN CUTOFF ROOM. A room or space that is intended exclusively to house a gaseous hydrogen system.

     420.3 Location. Hydrogen cut-off rooms shall not be located below grade.

     420.4 Design and construction. Hydrogen cutoff rooms shall be classified with respect to occupancy in accordance with Section 302.1 and separated from other areas of the building by not less than 1-hour fire barriers or as required by Section

    508.2or 508.3 as applicable.

     420.4.1 Opening protectives. Doors within such fire barrier walls, including doors to corridors, shall be self-closing in accordance with Section 715. Interior door openings shall be electronically interlocked to prevent operation of the hydrogen system when doors are opened or ajar or the room shall be provided with a mechanical exhaust ventilation system designed in accordance with Section 420.4.1.1.

     420.4.1.1 Ventilation alternative. When an exhaust system is used in lieu of the interlock system required by Section 420.4, exhaust ventilation systems shall operate continuously and shall be designed to operate at a negative pressure in relation to the surrounding area. The average velocity of ventilation at the face of the door opening with the door in the fully open position shall not be less than 60 feet per minute (0.3048 m/s) with a mini- mum of 45 feet per minute (0.2287 m/s) at any point in the door opening.

     420.4.2 Windows. Operable windows in interior walls shall not be permitted. Fixed windows shall be permitted when in accordance with Section 715.

     420.5 Ventilation. Cutoff rooms shall be provided with mechanical ventilation in accordance with the applicable provisions for repair garages in Chapter 5 of the  mechanical code.

     420.6 Gas detection system. Hydrogen cutoff rooms shall be provided with an approved flammable gas-detection system in accordance with Sections 420.6.1 through 420.6.3.

     420.6.1 System design. The flammable gas-detection system shall be listed for use with hydrogen and any other flammable gases used in the room. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower flammability limit (LFL) for the gas or mixtures present at their anticipated temperature and pressure.

     420.6.2 Operation. Activation of the gas detection system shall result in all of the following:

    1. Initiation of distinct audible and visual alarm signals both inside and outside of the cutoff room.

    2. Activation of the mechanical ventilation system.

     420.6.3 Failure of the gas detection system. Failure of the gas detection system shall result in activation of the mechanical ventilation system, cessation of hydrogen generation and the sounding of a trouble signal in an approved location.

    420.7Explosion control. Explosion control shall be provided in accordance with Chapter 9 of the fire code.

    420.8Standby power. Mechanical ventilation and gas detection systems shall be connected to a standby power system in accordance with Chapter 27.

    Replaces:                                                     4101:1-4-02.3, 4101:1-4-02.8, 4101:1-4-06.2.2,

    4101:1-4-06.5.1, 4101:1-4-07.6, 4101:1-4-08.1.1,

    4101:1-4-11.4, 4101:1-4-12.1.6, 4101:1-4-12.3.1,

    4101:1-4-13.1, 4101:1-4-14.5.4, 4101:1-4-15.2,

    4101:1-4-15.3.1, 4101:1-4-15.6, 4101:1-4-15.7.1,

    4101:1-4-15.7.2, 4101:1-4-15.7.3, 4101:1-4-15.8.4,

    4101:1-4-15.8.4.1, 4101:1-4-15.8.4.2,

    4101:1-4-15.8.4.3, 4101:1-4-15.8.4.4,

    4101:1-4-15.8.4.5, 4101:1-4-15.9.2.8.1,

    4101:1-4-15.9.6.1

    Effective:                                                     07/01/2007

    R.C. 119.032 review dates:                         07/01/2012

    CERTIFIED ELECTRONICALLY

    Certification

    02/02/2007

    Date

    Promulgated Under:                           119.03

    Statutory Authority:                           3781.10(A)

    Rule Amplifies:                                  3737.87, 3737.88, 3737.89, 3781.10, 3781.11,

    3791.04, 4104.42(C)

    Prior Effective Dates:                         7/1/79, 7/1/82, 3/1/85, 1/1/89, 9/1/92, 7/1/95, 2/1/96,

    3/1/98, 1/1/02, 8/15/03, 3/1/05, 3/1/06

Document Information

Effective Date:
7/1/2007
File Date:
2007-02-02
Last Day in Effect:
2007-07-01
Rule File:
4101$1-4-01_PH_FF_N_RU_20070202_1303.pdf
Related Chapter/Rule NO.: (1)
Ill. Adm. Code 4101:1-4-01. Special detailed requirements based on use and occupancy