4101:1-9-01 Fire protection systems.  

  • Text Box: ACTION: Final Text Box: DATE: 02/02/2007 1:03 PM

     

     

     

     

     

     

    4101:1-9-01    Fire protection systems.

     

    [Comment: When a reference is made within this rule to a federal statutory  provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:1-35-01 of the Administrative Code.  The application of the referenced standards shall be limited and as prescribed in section 102.4 of rule 4101:1-1-01 of the Administrative Code.]

     

    SECTION 901

     GENERAL

    901.1Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and operation of  fire protection systems.

    901.2Fire protection systems. Fire protection systems shall be installed, repaired, operated and maintained in accordance with this code and the fire code.

    Any fire protection system for which an exception or reduction to the provisions of this code has been granted shall be considered to be a required system.

    Exception: Any fire protection system or portion thereof not required by this code shall be permitted to be installed for partial or complete protection provided that such system meets the requirements of this code.

     

    901.2.1Approval of fire protection systems. Prior to the start of fire protection system installation, alteration, repair, or removal, the owner or the  owner's agent shall make application and obtain plan approval from the building official for the proposed work in accordance with Section 106 of the building code.

    901.2.1.1Input from the fire official. In jurisdictions where the local fire official has requested the opportunity to provide input into the fire protection system approval process conducted by the building official, the  owner or the owner's agent is required to submit a copy of construction documents related to fire protection to the local fire official for review in accordance with Section 106.1.2 (5).

    901.2.1.2Coordination. When the building official or the fire official has  indicated an intention to have personnel witness acceptance testing conducted in accordance with Section 901.5, it is the responsibility of the  owner or the owner's representative to provide advance notice of when the tests are scheduled to both the building official and the fire official.

     

     

     

     

     

     

     

     

    901.3Modifications. No person shall remove or modify any  fire  protection system installed or maintained under the provisions of this code or the fire code  without approval by the building official.

    901.4Threads. Threads provided for fire department connections to sprinkler systems, standpipes, yard hydrants or any other fire hose connection shall be compatible with the connections used by the local fire department.

    901.5Acceptance tests. Fire protection systems shall be tested in accordance with the requirements of this code, the fire code, and the applicable standards  referenced in this code. Required acceptance tests shall be conducted at the expense of the owner or the owner's representative. The building official may require that the acceptance tests be conducted in the presence of a certified building inspector or certified fire protection inspector. Test results shall be documented and certificates shall be submitted to the building official upon  completion. Copies of test records and certificates shall also be maintained at the jobsite and made available to the inspector conducting the fire protection systems  final inspections. It shall be unlawful to occupy portions of a structure until the required fire protection systems within that portion of the structure have been tested, inspected, and approved.

    901.6Supervisory service. Where required, fire protection systems shall be monitored by an approved supervising station in accordance with NFPA 72.

    901.6.1Automatic sprinkler systems. Automatic sprinkler systems shall be monitored by an approved supervising station in accordance with  Section 903.4.

    901.6.2Fire alarm systems. Fire alarm systems required by the provisions of  Section 907.2 of this code shall be monitored by an approved supervising station in accordance with Section 907.14.

    901.6.3Group H. Manual fire alarm, automatic fire-extinguishing and emergency alarm systems in Group H occupancies shall be monitored by an approved supervising station.

    Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire department will be equal to those provided by an approved supervising station.

    901.7Fire areas. Where buildings, or portions thereof, are divided into fire areas  so as not to exceed the limits established for requiring a fire protection system in

    accordance with this chapter, such fire areas shall be separated by fire barriers having a fire-resistance rating of not less than that determined in accordance with Section 706.3.9.

    901.8 Welding and brazing. Welding and brazing of all metallic fire protection piping shall be done in accordance with Section 313 of the mechanical code.

    SECTION 902 DEFINITIONS

    902.1 Definitions. The following words and terms shall, for the purposes of this

    chapter, and as used elsewhere in this code, have the meanings shown herein.

    ALARM NOTIFICATION APPLIANCE. A fire alarm system component such  as a bell, horn, speaker, light or text display that provides audible, tactile or  visible outputs, or any combination thereof.

    ALARM SIGNAL. A signal indicating an emergency requiring immediate action, such as a signal indicative of fire.

    ALARM VERIFICATION FEATURE. A feature of automatic fire detection and alarm systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a minimum period of time, or confirm alarm conditions within a given time period, after being automatically reset, in order to be accepted  as a valid alarm-initiation signal.

    ANNUNCIATOR. A unit containing one or more indicator lamps, alphanumeric displays or other equivalent means in which each indication provides status  information about a circuit, condition or location.

    AUDIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the sense of hearing.

    AUTOMATIC. As applied to fire protection devices, is a device or system providing an emergency function without the necessity for human intervention  and activated as a result of a predetermined temperature rise, rate of temperature rise or combustion products.

    AUTOMATIC FIRE-EXTINGUISHING SYSTEM. An approved system of  devices and equipment which automatically detects a fire and discharges an approved fire-extinguishing agent onto or in the area of a fire.

    AUTOMATIC SPRINKLER SYSTEM. A sprinkler system, for fire protection  purposes, is an integrated system of underground and overhead piping designed in accordance with fire protection engineering standards. The system includes a suitable water supply. The portion of the system above the ground is a network of specially sized or hydraulically designed piping installed in a structure or area, generally over-head, and to which automatic sprinklers are connected in a sys-

    tematic pattern. The system is usually activated by heat from a fire and discharges  water over the fire area.

    AVERAGE AMBIENT SOUND LEVEL. The root mean square, A-weighted  sound pressure level measured over a 24-hour period.

    CARBON DIOXIDE EXTINGUISHING SYSTEMS. A system supplying carbon dioxide (CO2) from a pressurized vessel through fixed pipes and nozzles. The system includes a manual- or automatic-actuating mechanism.

    CEILING LIMIT. The maximum concentration of an air-borne contaminant to which one may be exposed, as published in DOL 29 CFR Part 1910.1000.

    CLEAN AGENT. Electrically nonconducting, volatile or gaseous fire extinguishant that does not leave a residue upon evaporation.

    CONSTANTLY ATTENDED LOCATION. A designated location at a facility staffed by trained personnel on a continuous basis where alarm or supervisory  signals are monitored and facilities are provided for notification of the fire department or other emergency services.

    DELUGE SYSTEM. A sprinkler system employing open sprinklers attached to a piping system connected to a water sup-ply through a valve that is opened by the operation of a detection system installed in the same areas as the sprinklers. When this valve opens, water flows into the piping system and discharges from all sprinklers attached thereto.

    DETECTOR, HEAT.  A  fire detector that  senses heat  produced  by burning substances. Heat is the energy produced by combustion that causes substances to rise in temperature.

    DRAFT CURTAIN. A structure arranged to limit the spread of smoke and heat along the underside of the ceiling or roof.

    DRY-CHEMICAL EXTINGUISHING AGENT. A powder composed of small particles, usually of sodium bicarbonate, potassium bicarbonate, urea-potassium-  based bicarbonate, potassium chloride or monoammonium phosphate, with added particulate material supplemented by special treatment to provide resistance to packing, resistance to moisture absorption (caking) and the proper flow  capabilities.

    EMERGENCY ALARM SYSTEM. A system to provide indication and warning of emergency situations involving hazardous materials.

    EMERGENCY VOICE/ALARM COMMUNICATIONS. Dedicated  manual  or automatic facilities for originating and distributing voice instructions, as well  as alert and evacuation signals pertaining to a fire emergency, to the occupants of

    a building.

    EXPLOSION. An effect produced by the sudden violent expansion of gases, that is accompanied by a shock wave or disruption of enclosing materials or  structures, or both.

    FIRE ALARM BOX, MANUAL. See "Manual Fire Alarm Box."

    FIRE ALARM CONTROL UNIT. A system component that receives inputs from automatic and manual fire alarm devices and is capable of supplying power  to detection devices and transponder(s) or off-premises transmitter(s). The control unit is capable of providing a transfer of power to the notification appliances and transfer of condition to relays or devices.

    FIRE ALARM SIGNAL. A signal initiated by a fire alarm-initiating device such as a manual fire alarm box, automatic fire detector, water flow switch, or other device whose activation is indicative of the presence of a fire or fire signature.

    FIRE ALARM SYSTEM. A system or portion of a combination system consisting of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signal-initiating devices and to initiate the appropriate response to those signals.

    FIRE COMMAND CENTER. The principal attended or unattended location where the status of detection, alarm communications and control systems is displayed, and from which the system(s) can be manually controlled.

    FIRE DETECTOR, AUTOMATIC. A device designed to detect the presence of  a fire signature and to initiate action.

    FIRE PROTECTION SYSTEM. Approved devices, equipment and systems or  combinations of systems used to detect a fire, activate an alarm, extinguish or  control a fire, control or manage smoke and products of a fire or any combination thereof.

    FIRE SAFETY FUNCTIONS. Building and fire control functions that are intended to increase the level of life safety for occupants or to control the spread  of harmful effects of fire.

    FOAM-EXTINGUISHING SYSTEM. A special system discharging a foam made from concentrates, either mechanically or chemically, over the area to be protected.

    HALOGENATED EXTINGUISHING SYSTEM. A fire-extinguishing system using one or more atoms of an element from the halogen chemical series: fluorine, chlorine, bromine and iodine.

    INITIATING DEVICE. A system component that originates transmission of a change-of-state condition, such as in a smoke detector, manual fire alarm box or supervisory switch.

    LISTED. Equipment, appliances, materials or services included in a directory  published by an approved agency whose listing states either that the equipment,  appliances, materials or service meets identified standards referenced in this code  or has been tested and found suitable for a specified purpose.

    MANUAL FIRE ALARM BOX. A manually operated device used to initiate an alarm signal.

    MULTIPLE-STATION ALARM DEVICE. Two or more single-station alarm devices that are capable of interconnection such that actuation of one causes all integral or separate audible alarms to operate. It also can consist of one single-sta- tion alarm device having connections to other detectors or to a manual fire alarm  box.

    MULTIPLE-STATION SMOKE ALARM. Two or more single-station alarm devices that are capable of interconnection such that actuation of one causes all integral or separate audible alarms to operate.

    NUISANCE ALARM. An alarm caused by mechanical failure, malfunction, improper installation or lack of proper maintenance, or an alarm activated by a cause that cannot be determined.

    RECORD DRAWINGS. Drawings ("as builts") that document the location of all devices, appliances, wiring sequences, wiring methods and connections of the components of a fire alarm system as installed.

    SINGLE-STATION SMOKE ALARM. An assembly incorporating the detector, the control equipment and the alarm-sounding device in one unit, operated from a power supply either in the unit or obtained at the point of installation.

    SMOKE ALARM. A single- or multiple-station alarm responsive to smoke and not connected to a system.

    SMOKE DETECTOR. A listed device that senses visible or invisible particles of combustion.

    SMOKEPROOF ENCLOSURE. An exit stairway designed and constructed so  that the movement of the products of combustion produced by a fire occurring in any part of the building into the enclosure is limited.

    STANDPIPE SYSTEM, CLASSES OF. Standpipe classes are as follows:

    Class I system. A system providing 21/2-inch (64 mm) hose connections to supply water for use by fire departments and those trained in handling heavy fire streams.

    Class II system. A system providing 11/2-inch (38 mm) hose stations to supply water for use primarily by the building occupants or by the fire department

    during initial response.

    Class III system. A system providing 11/2-inch (38 mm) hose stations to supply water for use by building occupants and 2.5-inch (64 mm) hose connections to supply a larger volume of water for use by fire departments and those trained in handling heavy fire streams.

    STANDPIPE, TYPES OF. Standpipe types are as follows:

    Automatic dry. A dry standpipe system, normally filled with pressurized air, that is arranged through the use of a device, such as dry pipe valve, to admit water into the system piping automatically upon the opening of a hose valve.

    The water supply for an automatic dry standpipe system shall be capable of  supplying the system demand.

    Automatic wet. A wet standpipe system that has a water supply that is capable  of supplying the system demand automatically.

    Manual dry. A dry standpipe system that does not have a permanent water supply attached to the system. Manual dry standpipe systems require water from a fire department pumper to be pumped into the system through the fire department connection in order to meet the system demand.

    Manual wet. A wet standpipe system connected to a water supply for the  purpose of maintaining water within the system but does not have a water supply capable of delivering the system demand attached to the system.  Manual-wet standpipe systems require water from a fire department pumper (or  the like) to be pumped into the system in order to meet the system demand.

    Semiautomatic dry. A dry standpipe system that is arranged through the use of  a device, such as a deluge valve, to admit water into the system piping upon  activation of a remote control device located at a hose connection. A remote control activation device shall be provided at each hose connection. The water supply for a semiautomatic dry standpipe system shall be capable of supplying the system demand.

    SUPERVISING STATION. A facility that receives signals and at which personnel are in attendance at all times to respond to these signals.

    SUPERVISORY SERVICE. The service required to monitor performance of  guard tours and the operative condition of fixed suppression systems or other systems for the protection of life and property.

    SUPERVISORY SIGNAL. A signal indicating the need of action in connection with the supervision of guard tours, the fire suppression systems or equipment or  the maintenance features of related systems.

    SUPERVISORY SIGNAL-INITIATING DEVICE. An initiation device, such

    as a valve supervisory switch, water-level indicator or low-air pressure switch on  a dry-pipe sprinkler system, whose change of state signals an off-normal condition and its restoration to normal of a fire protection or life safety system, or  a need for action in connection with guard tours, fire suppression systems or  equipment or maintenance features of related systems.

    TIRES, BULK STORAGE OF. Storage of tires where the area available for storage exceeds 20,000 cubic feet (566 m3).

    TROUBLE SIGNAL. A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component.

    VISIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the sense of sight.

    WET-CHEMICAL EXTINGUISHING SYSTEM. A solution of water and potassium-carbonate-based chemical, potassium-acetate-based chemical or a combination thereof, forming an extinguishing agent.

    WIRELESS PROTECTION SYSTEM. A system or a part of a system that can transmit and receive signals without the aid of wire.

    ZONE. A defined area within the protected premises. A zone can define an area from which a signal can be received, an area to which a signal can be sent or an area in which a form of control can be executed.

    SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

    903.1General. Automatic sprinkler systems shall comply with this section.

    903.1.1Alternative protection. Alternative automatic fire-extinguishing  systems complying with Section 904 shall be permitted in lieu of automatic sprinkler protection where recognized by the applicable standard and approved  by the building official.

    903.2Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section.

    Exception: Spaces or areas in telecommunications buildings used exclusively  for telecommunications equipment, associated electrical power distribution  equipment, batteries and standby engines, provided those spaces or areas are equipped throughout with an automatic fire alarm system and are separated from the remainder of the building by fire barriers consisting of not less than 1- hour fire-resistance-rated walls and 2-hour fire-resistance-rated floor/ ceiling assemblies.

    903.2.1 Group A. An automatic sprinkler system shall be provided throughout

    buildings and portions thereof used as Group A occupancies as provided in this section. For Group A-1, A-2, A-3 and A-4 occupancies, the automatic sprinkler system shall be provided throughout the floor area where the Group A-1, A-2, A-3 or A-4 occupancy is located, and in all floors between the Group A  occupancy and the level of exit discharge. For Group A-5 occupancies, the automatic sprinkler system shall be provided in the spaces indicated in Section  903.2.1.5.

    903.2.1.1Group A-1. An automatic sprinkler system shall be provided for Group A-1 occupancies where one of the following conditions exists:

    1.    The fire area exceeds 12,000 square feet (1115 m2).

    2.    The fire area has an occupant load of 300 or more.

    3.    The fire area is located on a floor other than the level of exit discharge.

    4.    The fire area contains a multitheater complex.

    903.2.1.2Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists:

    1.    The fire area exceeds 5,000 square feet (465 m2);

    2.    The fire area has an occupant load of 100 or more;  or

    3.The fire area is located on a floor other than the level of exit discharge.

    903.2.1.3Group A-3. An automatic sprinkler system shall be provided for Group A-3 occupancies where one of the following conditions exists:

    1. The fire area exceeds 12,000 square feet (1115 m2).

    Exception:

    1.1Fire areas used exclusively for religious worship services with fixed seating.

    2. The fire area has an occupant load of 300 or more.

    Exceptions:

    2.1Fire areas used primarily for worship with fixed seating.

                2.2 Fire areas without fixed seating not used for exhibition or display.

    3. The fire area is located on a floor other than the level of exit discharge.

    Exception: Areas used exclusively as participant sports areas where the main floor area is located at the same level as the level of exit discharge of  the main entrance and exit.

    903.2.1.4Group A-4. An automatic sprinkler system shall be provided for Group A-4 occupancies where one of the following conditions exists:

    1. The fire area exceeds 12,000 square feet (1115 m2).

    2. The fire area has an occupant load of 300 or more.

    3. The fire area is located on a floor other than the level of exit discharge.

    Exception: Areas used exclusively as participant sports areas where the main floor area is located at the same level as the level of exit discharge of  the main entrance and exit.

    903.2.1.5Group A-5. An automatic sprinkler system shall be provided for Group A-5 occupancies in the following areas: concession stands, retail areas,  press boxes and other accessory use areas in excess of 1,000 square feet (93 m2).

    903.2.2Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows:

    1.   Throughout all Group E fire areas greater than 20,000 square feet (1858 m2)  in area.

    2.Throughout every portion of educational buildings below the level of exit discharge.

    Exception: An automatic sprinkler system is not required in any fire area or  area below the level of exit discharge where every classroom throughout the building has at least one exterior exit door at ground level.

    903.2.3Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following condi- tions exists:

    1.    Where a Group F-1 fire area exceeds 12,000 square feet (1115 m2);

    2.    Where a Group F-1 fire area is located more than three stories above grade plane; or

    3.    Where the combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).

    903.2.3.1 Woodworking operations. An automatic sprinkler system shall be provided throughout all Group F-1 occupancy fire areas that contain woodworking operations in excess of 2,500 square feet (232 m2) in area which generate finely divided combustible waste or use finely divided combustible materials.

    903.2.4Group H. Automatic sprinkler systems shall be provided in high- hazard occupancies as required in Sections 903.2.4.1 through 903.2.4.3.

    903.2.4.1

     

     
    General. An automatic sprinkler system shall be installed in Group H occupancies.

    903.2.4.2Group H-5. An automatic sprinkler system shall be installed throughout buildings containing Group H-5 occupancies. The design of the sprinkler system shall not be less than that required by this code for the occupancy hazard classifications in accordance with Table 903.2.4.2. Where the design area of the sprinkler system consists of a corridor protected by one

    175

    row  of  sprinklers,  the  maximum  number  of  sprinklers  required  to  be calculated is 13.

    TABLE 903.2.4.2

    GROUP H-5 SPRINKLER DESIGN CRITERIA

     

    LOCATION

    OCCUPANCY HAZARD CLASSIFICATION

    Fabrication areas

    Ordinary Hazard Group 2

    Service corridors

    Ordinary Hazard Group 2

    Storage rooms without dispensing

    Ordinary Hazard Group 2

    Storage rooms with dispensing

    Extra Hazard Group 2

    Corridors

    Ordinary Hazard Group 2

    903.2.4.3Pyroxylin plastics. An automatic sprinkler system shall be provided in buildings, or portions thereof, where cellulose nitrate film or  pyroxylin plastics are manufactured, stored or handled in quantities exceeding 100 pounds (45 kg).

    903.2.5Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area.

    Exception: An automatic sprinkler system installed in accordance with Section 903.3.1.2 or 903.3.1.3 shall be allowed in Group I-1 facilities.

    903.2.6Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists:

    1.    Where a Group M fire area exceeds 12,000 square feet (1115 m2);

    2.    Where a Group M fire area is located more than three stories above grade plane; or

    3.    Where the combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).

    903.2.6.1 High-piled storage. An automatic sprinkler system shall be provided in accordance with the fire code in all buildings of Group M where storage of merchandise is in high-piled or rack storage arrays.

    903.2.7Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.

                Exceptions:

    1.An automatic sprinkler system installed in accordance with section  903.3.1.2 shall be allowed in buildings, or portions thereof, of  Group R.

    2.An automatic sprinkler system installed in accordance with Section  903.3.1.3 shall be allowed in buildings of Group R-3 and R-4.

    3.An automatic sprinkler system installed in accordance with Section

    903.3.1.2 or Section 903.3.1.3 shall be allowed in one-, two-, or  three-family dwellings.

    4.Buildings of Group R-2 permitted to have a single exit per Section 1018.2 where:

    a. The exit is constructed as an exterior stair per Section 1022, and

          b. The dwellings egress directly into an exit, and

    c.Two hour fire barriers divide the building into fire areas with a maximum of two dwelling units per floor and not more than six units per fire area, and

    d.      All units in the fire area must have separations as required by section 708.1 for dwelling units.

    903.2.8Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:

    1.    A Group S-1 fire area exceeds 12,000 square feet (1115 m2);

    2.    A Group S-1 fire area is located more than three stories above grade plane;  or

    3.    The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2).

    903.2.8.1Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406, as shown:

    1. Buildings two or more stories in height, including basements, with a fire area containing a repair garage exceeding 10,000 square feet (929 m2).

    2. One-story buildings with a fire area containing a repair garage exceeding 12,000 square feet (1115 m2).

    3. Buildings with a repair garage servicing vehicles parked in the basement.

    903.2.8.2Bulk storage of tires. Buildings and structures where the area for the storage of tires exceeds 20,000 cubic feet (566 m3) shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

    903.2.9Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as enclosed parking garages in accordance with Section 406.4 or where located beneath other groups.

    Exception: Enclosed parking garages located beneath Group R-3 occupancies  903.2.9.1 Commercial parking garages. An automatic sprinkler system shall

    be provided throughout buildings used for storage of commercial trucks or buses where the fire area exceeds 5,000 square feet (464 m2).

    903.2.10Windowless stories in all occupancies. An automatic sprinkler system shall be installed in the locations set forth in Sections 903.2.10.1 through  903.2.10.1.3.

    Exception: Group R-3 and Group U.

    903.2.10.1Stories and basements without openings. An automatic sprinkler system shall be installed throughout every story or basement of all buildings where the floor area exceeds 1,500 square feet (139.4 m2) and where there is not provided at least one of the following types of exterior wall openings:

    1.Openings below grade that lead directly to ground level by an exterior stairway complying with Section 1009 or an outside ramp complying with Section 1010. Openings shall be located in each 50

    linear feet (15 240 mm), or fraction thereof, of exterior wall in the story on  at least one side.

    2.Openings entirely above the adjoining ground level totaling at least 20 square feet (1.86 m2) in each 50 linear feet (15 240 mm), or fraction  thereof, of exterior wall in the story on at least one side.

    903.2.10.1.1Opening dimensions and access. Openings shall have a minimum dimension of not less than 30 inches (762 mm). Such openings shall be accessible to the fire department from the exterior and shall not be obstructed in a manner that fire fighting or rescue cannot be accomplished from the exterior.

    903.2.10.1.2Openings on one side only. Where openings in a story are provided on only one side and the opposite wall of such story is more than  75 feet (22 860 mm) from such openings, the story shall be equipped throughout with an approved automatic sprinkler system, or openings as  specified above shall be provided on at least two sides of the story.

    903.2.10.1.3Basements. Where any portion of a basement is located more than 75 feet (22 860 mm) from openings required by Section 903.2.10.1, the basement shall be equipped throughout with an approved automatic sprinkler system.

    903.2.10.2Rubbish and linen chutes. An automatic sprinkler system shall be installed at the top of rubbish and linen chutes and in their terminal rooms.  Chutes extending through three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors. Chute sprinklers shall be accessible for

    servicing.

    903.2.10.3Buildings  55  feet  or  more  in  height.  An  automatic  sprinkler

    system shall be installed throughout buildings with a floor level having an occupant load of 30 or more that is located 55 feet (16 764 mm) or more above the lowest level of fire department vehicle access.

    Exceptions:

    1.    Airport control towers.

    2.    Open parking structures.

    3.    Occupancies in Group F-2.

    903.2.11During construction. Automatic sprinkler systems required during construction, alteration and demolition operations shall be provided in accordance with Section 3312.

    903.2.12Other hazards. Automatic sprinkler protection shall be provided for the hazards indicated in Sections 903.2.12.1 and 903.2.12.2.

    903.2.12.1Ducts conveying hazardous exhausts. Where required by the  mechanical code, automatic sprinklers shall be provided in ducts conveying hazardous exhaust, or flammable or combustible materials.

    Exception: Ducts in which the largest cross-sectional diameter of the duct is  less than 10 inches (254 mm).

    903.2.12.2Commercial cooking operations. An automatic sprinkler system shall be installed in commercial kitchen exhaust hood and duct system where an automatic sprinkler system is used to comply with Section 904.

    903.2.13Other required suppression systems. In addition to the requirements  of Section 903.2, the provisions indicated in Table 903.2.13 also require the installation of a suppression system for certain buildings and areas.

    TABLE 903.2.13

    ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

    SECTION

    SUBJECT

    402.8

    Covered malls

    403.2, 403.3

    High-rise buildings

    404.3

    Atriums

    405.3

    Underground structures

    407.5

    Group I-2

    410.6

    Stages

    411.4

    Special amusement buildings

    412.2.5, 412.2.6

    Aircraft hangars

    415.6.2.4

    Group H-2

    416.4

    Flammable finishes

    417.4

    Drying rooms

    507

    Unlimited area buildings

    508.2

    Incidental use areas

    1025.6.2.3

    Smoke-protected assembly seating

     

    IFC

    Sprinkler system requirements as set forth in Section 903.2.13 of the

     fire code

    903.3Installation requirements. Automatic sprinkler systems shall be designed and installed in accordance with Sections 903.3.1 through 903.3.7.

    903.3.1Standards.  Sprinkler  systems  shall  be  designed  and  installed  in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.

    903.3.1.1NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1.

    903.3.1.1.1Exempt locations. Automatic sprinklers shall not be required  in the following rooms or areas where such rooms or areas are protected with an approved  automatic fire detection system, in accordance  with Section 907.2, that will respond to visible or invisible particles of  combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment.

    1.    Any room where the application of water, or flame and water, constitutes a serious life or fire hazard.

    2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the building  official.

    3. Generator and transformer rooms separated from the remainder of  the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours.

    4.    In rooms or areas that are of noncombustible construction with wholly noncombustible contents.

    903.3.1.2NFPA 13R sprinkler systems. Where allowed in buildings of  Groups I-1 and R, up to and including four stories in height, automatic sprinkler systems shall be installed throughout in accordance with NFPA  13R.

    903.3.1.2.1Balconies and decks. Sprinkler protection shall be provided  for exterior balconies, decks and ground floor patios of dwelling units where the building is of Type V construction. Sidewall sprinklers that are  used to protect such areas shall be permitted to be located such that their deflectors are within 1 inch (25 mm) to 6 inches (152 mm) below the structural members and a maximum distance of 14 inches (356 mm) below the deck of the exterior balconies and decks that are constructed of open  wood joist construction.

    903.3.1.3NFPA 13D sprinkler systems. Where permitted in Groups I-1 and  R, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13D.

    903.3.2Quick-response and residential sprinklers. Where  automatic sprinkler systems are required by this code, quick-response or residential automatic sprinklers shall be installed in the following areas in accordance with Section 903.3.1 and their listings:

    1.    Throughout all spaces within a smoke compartment containing patient sleeping units in Group I-2 in accordance with this code.

    2.    Dwelling units, and sleeping units in Group R and I-1 occupancies.

    3.    Light-hazard occupancies as defined in NFPA 13.

    903.3.3Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered  kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet  (1219 mm) in width. Not less than a 3-foot (914 mm)  clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.

    Exception: Kitchen equipment under exhaust hoods protected with a fire- extinguishing system in accordance with Section 904.

    903.3.4Actuation. Automatic sprinkler systems shall be automatically actuated  unless specifically provided for in this code.

    903.3.5Water supplies. Water supplies for automatic sprinkler systems shall comply with this section and the standards referenced in Section 903.3.1. Fire  pumps, when provided, shall be installed in accordance with Section 913 of the fire code and NFPA 20, as referenced in Chapter 35. The potable water supply shall be protected against backflow in accordance with the requirements of this

    section and the plumbing code.

    903.3.5.1Domestic services. Where the domestic service provides the water supply for the automatic sprinkler system, the supply shall be in accordance with this section.

    903.3.5.1.1Limited area sprinkler systems. Limited area sprinkler systems serving fewer than 20 sprinklers on any single connection are permitted to be connected to the domestic service where a wet automatic standpipe is not available. Limited area sprinkler systems connected to domestic water supplies shall comply with each of the following require- ments:

    1.    Valves shall not be installed between the domestic water riser control valve and the sprinklers.

    Exception: An approved indicating control valve supervised in the open position in accordance with Section 903.4.

    2.    The domestic service shall be capable of supplying the simultaneous domestic demand and the sprinkler demand required to be hydrauli- cally calculated by NFPA 13, NFPA 13R or NFPA 13D.

    903.3.5.1.2Residential combination services. A single combination water supply shall be allowed provided that the domestic demand is added to the sprinkler demand as required by NFPA 13R.

    903.3.5.2Secondary water supply. A secondary on-site water supply equal to the hydraulically calculated sprinkler demand, including the hose stream requirement, shall be provided for high-rise buildings in Seismic Design  Category C, D, E or F as determined by this code. The secondary water supply shall have a duration of not less than 30 minutes as determined by the occupancy hazard classification in accordance with NFPA 13.

    Exception: Existing buildings.

    903.3.6Hose threads. Fire hose threads and fittings used in connection with automatic sprinkler systems shall be approved and compatible with the  responding fire department hose threads.

    903.4Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and water-flow switches on all sprinkler systems shall be electrically supervised.

    Exceptions:

    1. Automatic sprinkler systems protecting one-, two-, and three-family dwellings.

    2. Limited area systems serving fewer than 20 sprinklers.

    3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler systems and a separate shutoff valve for the automatic sprinkler system is not provided.

    4. Jockey pump control valves that are sealed or locked in the open position.

    5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.

    6. Valves controlling the fuel supply to fire pump engines that are sealed or  locked in the open position.

    7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position.

    903.4.1Signals. Alarm, supervisory and trouble signals shall be distinctly different and automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the building official, shall sound an audible signal at a constantly attended location.

    Exceptions:

    1.    Underground key or hub valves in roadway boxes provided by the municipality or public utility are not required to be monitored.

    2. Backflow prevention device test valves located in limited area sprinkler  system supply piping shall be locked in the open position. In occupancies required to be equipped with a fire alarm system, the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated.

    903.4.2Alarms. Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the small- est orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.

            Exception: Water-flow alarms are not required for limited area sprinkler  systems installed in accordance with Section 903.3.5.1.1.

    903.4.3Floor control valves. Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high- rise buildings.

    903.5Testing  and  maintenance.  Sprinkler  systems  shall  be  tested  and maintained in accordance with the fire code.

    SECTION 904 ALTERNATIVE AUTOMATIC

    FIRE-EXTINGUISHING SYSTEMS

    904.1General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and  the applicable referenced standards.

    904.2Where required. Automatic fire-extinguishing  systems installed  as an alternative to the required automatic sprinkler systems of Section 903 shall be approved by the building official. Automatic fire-extinguishing systems shall not be considered alternatives for the purposes of exceptions or reductions allowed by  other requirements of this code.

    904.2.1Commercial hood and duct systems. Each required commercial kitchen exhaust hood and duct system required by the mechanical code to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with this code.

    904.3Installation. Automatic fire-extinguishing systems shall be installed in accordance with this section.

    904.3.1Electrical  wiring.  Electrical  wiring  shall  be  in  accordance  with

    Chapter 27.

    904.3.2Actuation. Automatic fire-extinguishing systems shall be automatically actuated and provided with a manual means of actuation in accordance with Section 904.11.1.

    904.3.3System interlocking. Automatic equipment interlocks with fuel  shutoffs, ventilation controls, door closers, window shutters, conveyor openings, smoke and heat vents and other features necessary for proper operation of the fire-extinguishing system shall be provided as required by the design and installation standard utilized for the hazard.

    904.3.4Alarms and warning signs. Where alarms are required to indicate the operation of automatic fire-extinguishing systems, distinctive audible and visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to  persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Audible signals shall be in accordance with Section 907.9.2.

    904.3.5Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72.

    904.4Inspection and testing. Automatic fire-extinguishing systems shall be inspected and tested in accordance with the provisions of this section prior to acceptance.

    904.4.1Inspection. Prior to conducting final acceptance tests, the following  items shall be inspected:

    1.Hazard specification for consistency with design hazard.

    2. Type, location and spacing of automatic- and manual-initiating devices.

    3. Size, placement and position of nozzles or discharge orifices.

    4. Location and identification of audible and visible alarm devices.

    5. Identification of devices with proper designations.

    6. Operating instructions.

    904.4.2Alarm testing. Notification appliances, connections to fire alarm systems and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.

    904.4.2.1 Audible and visible signals. The audibility and visibility of  notification appliances signaling agent discharge or system operation, where required, shall be verified.

    904.4.3Monitor testing. Connections to protected premises and supervising station fire alarm systems shall be tested to verify proper identification and retransmission of alarms from automatic fire-extinguishing systems.

    904.5Wet-chemical systems. Wet-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17A and their listing.

    904.6Dry-chemical systems. Dry-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17 and their listing.

    904.7Foam systems. Foam-extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 11 and NFPA 16 and their listing.

    904.8Carbon dioxide systems. Carbon dioxide extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 12 and their listing.

    904.9Halon systems. Halogenated extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 12A and their listing.

    904.10Clean-agent systems. Clean-agent fire-extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA

    2001 and their listing.

    904.11Commercial cooking systems. The automatic fire-extinguishing system  for commercial cooking systems shall be of a type recognized for protection of  commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical extinguishing systems  shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Automatic fire-extinguishing systems of  the following types shall be installed in accordance with the referenced standard indicated, as follows:

    1.    Carbon dioxide extinguishing systems, "NFPA 12".

    2.    Automatic sprinkler systems, "NFPA 13".

    3.    Foam-water sprinkler system or foam-water spray systems, "NFPA 16".

    4.    Dry-chemical extinguishing systems, "NFPA 17".

    5.    Wet-chemical extinguishing systems, "NFPA 17A".

    Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with "UL 710B" and listed, labeled and installed in accordance with Section 304.1 of the mechanical code.

    904.11.1Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10  feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches  (1200 mm) or less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system.

    Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means.

    904.11.2System interconnection. The actuation of the fire suppression system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual.

    904.11.3Carbon dioxide systems. When carbon dioxide systems are used,  there shall be a nozzle at the top of the ventilating duct. Additional nozzles that are symmetrically arranged to give uniform distribution shall be installed within vertical ducts exceeding 20 feet (6096 mm) and horizontal ducts exceeding 50  feet (15 240 mm). Dampers shall be installed at either the top or the bottom of  the duct and shall be arranged to operate automatically upon activation of the

    fire-extinguishing system. Where the damper is installed at the top of the duct, the top nozzle shall be immediately below the damper. Automatic carbon dioxide fire-extinguishing systems shall be sufficiently sized to protect against all hazards venting through a common duct simultaneously.

    904.11.3.1Ventilation system. Commercial-type cooking equipment protected by an automatic carbon dioxide-extinguishing system shall be arranged to shut off the ventilation system upon activation.

    904.11.4Special provisions for automatic sprinkler systems. Automatic sprinkler systems protecting commercial-type cooking equipment shall be supplied from a separate, readily accessible, indicating-type control valve that is identified.

    904.11.4.1Listed sprinklers. Sprinklers used for the protection of fryers  shall be tested in accordance with "UL 199E", listed for that application and installed in accordance with their listing.

    SECTION 905 STANDPIPE SYSTEMS

    905.1General. Standpipe systems shall be provided in new buildings and structures in accordance with this section. Fire hose threads used in connection  with standpipe systems shall be approved and shall be  compatible  with fire department hose threads. The location of fire department hose connections shall be approved by the building official. In buildings used for high-piled combustible storage, fire protection shall be in accordance with the fire code.

    905.2Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14.

    905.3Required installations. Standpipe systems shall be installed when required  by Sections 905.3.1 through 905.3.7 in the locations indicated in Sections 905.4, 905.5 and 905.6. Standpipe systems are allowed to be combined with automatic sprinkler systems.

    Exception: Standpipe systems are not required in Group R-3 occupancies.

    905.3.1Building height. Class III standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet (9144 mm) above the lowest level of fire department vehicle access, or where the floor level of the lowest story is located more than 30 feet  (9144 mm) below the highest level of fire department vehicle access.

    Exceptions:

    1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance  with Section 903.3.1.1 or 903.3.1.2.

    2. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 150 feet (45 720 mm) above the lowest level of fire department vehicle access.

    3. Class I manual dry standpipes are allowed in open parking garages that are subject to freezing temperatures, provided that the hose connections  are located as required for Class II standpipes in accordance with Section 905.5.

    4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system.

    5. In determining the lowest level of fire department vehicle access, it shall not be required to consider:

    5.1.Recessed loading docks for four vehicles or less; and

    5.2.Conditions  where  topography  makes  access  from  the  fire department vehicle to the building impractical or impossible.

    905.3.2Group A. Class I automatic wet standpipes shall be provided in nonsprinklered Group A buildings having an occupant load exceeding 1,000 persons.

    Exceptions:

    1. Open-air-seating spaces without enclosed spaces.

    2. Class I automatic dry and semiautomatic dry standpipes or manual wet standpipes are allowed in buildings where the highest floor surface used for human occupancy is 75 feet (22 860 mm) or less above the lowest level of fire department vehicle access.

    905.3.3Covered mall buildings. A covered mall building shall be equipped throughout with a standpipe system where required by Section 905.3.1. Covered mall buildings not required to be equipped with a standpipe system by Section  905.3.1 shall be equipped with Class I hose connections connected to a system sized to deliver water at 250 gallons per minute (946.4 L/min) at the most hydraulically remote outlet. Hose connections shall be provided at each of the fol- lowing locations:

    1.    Within the mall at the entrance to each exit passage-way or corridor.

    2.    At each floor-level landing within enclosed stairways opening directly on the mall.

    3.    At exterior public entrances to the mall.

    905.3.4    Stages. Stages greater than 1,000 square feet in area (93 m2) shall be

    equipped with a Class III wet standpipe system with 11/2-inch and 21/2-inch (38  mm and 64 mm) hose connections on each side of the stage.

    Exception: Where the building or area is equipped throughout with an automatic sprinkler system, a 11/2-inch (38 mm) hose connection shall be installed in accordance with NFPA 13 or in accordance with NFPA 14 for Class  II or III standpipes.

    905.3.4.1 Hose and cabinet. The 11/2-inch (38 mm) hose connections shall be equipped with sufficient lengths of 11/2-inch (38 mm) hose to provide fire protection for the stage area. Hose connections shall be equipped with an approved adjustable fog nozzle and be mounted in a cabinet or on a rack.

    905.3.5Underground buildings. Underground buildings shall be equipped throughout with a Class I automatic wet or manual wet standpipe system.

    905.3.6Helistops and heliports. Buildings with a helistop or heliport that are equipped with a standpipe shall extend the standpipe to the roof level on which the helistop or heliport is located in accordance with Section 1107.5 of the fire code.

    905.3.7Marinas and boatyards. Deleted.

    905.4Location of Class I standpipe hose connections. Class I standpipe hose  connections shall be provided in all of the following locations:

    1.    In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved  by the building official.

    2.    On each side of the wall adjacent to the exit opening of a horizontal exit.

    Exception: Where floor areas adjacent to a horizontal exit are reachable from exit stairway hose connections by a 30-foot (9144 mm) hose stream from a nozzle attached to 100 feet (30480 mm) of hose, a hose connection shall not be required at the horizontal exit.

    3.    In every exit passageway at the entrance from the exit passageway to other areas of a building.

    4.    In covered mall buildings, adjacent to each exterior public entrance to the mall and adjacent to each entrance from an exit passageway or exit corridor to the mall.

    5.    Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a hose  connection located either on the roof or at the highest landing of stairways with stair access to the roof. An additional hose connection shall be provided

    at the top of the most hydraulically remote standpipe for testing purposes.

    6.    Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960 mm) from a hose connection, the building official is authorized to require that additional hose connections be provided in approved locations.

    905.4.1Protection. Risers and laterals of Class I standpipe systems not located within an enclosed stairway or pressurized enclosure shall be protected by a degree of fire resistance equal to that required for vertical enclosures in the building in which they are located.

    Exception: In buildings equipped throughout with an approved automatic sprinkler system, laterals that are not located within an enclosed stairway or  pressurized enclosure are not required to be enclosed within fire-resistance- rated construction.

    905.4.2Interconnection. In buildings where more than one standpipe is provided, the standpipes shall be interconnected in accordance with NFPA 14.

    905.5Location of Class II standpipe hose connections. Class II standpipe hose  connections shall be accessible and located so that all portions of the building are within 30 feet (9144 mm) of a nozzle attached to 100 feet (30 480 mm) of hose.

    905.5.1Groups A-1 and A-2. In Group A-1 and A-2 occupancies with occupant loads of more than 1,000, hose connections shall be located on each side of any stage, on each side of the rear of the auditorium, on each side of the balcony and on each tier of dressing rooms.

    905.5.2Protection. Fire-resistance-rated protection of risers and laterals of  Class II standpipe systems is not required.

    905.5.3Class II system 1-inch hose. A minimum 1-inch (25 mm) hose shall be permitted to be used for hose stations in light-hazard occupancies where investigated and listed for this service and where approved by the building  official.

    905.6Location of Class III standpipe hose connections. Class III standpipe systems shall have hose connections located as required for Class I standpipes in Section 905.4 and shall have Class II hose connections as required in Section  905.5.

    905.6.1Protection. Risers and laterals of Class III standpipe systems shall be protected as required for Class I systems in accordance with Section 905.4.1.

    905.6.2Interconnection. In buildings where more than one Class III standpipe

    is provided, the standpipes shall be interconnected at the bottom.

    905.7Cabinets. Cabinets containing fire-fighting equipment such as standpipes, fire hoses, fire extinguishers or fire department valves shall not be blocked from  use or obscured from view.

    905.7.1Cabinet equipment identification. Cabinets shall be identified in an approved manner by a permanently attached sign with letters not less than 2  inches (51 mm) high in a color that contrasts with the background color, indicating the equipment contained therein.

    Exceptions:

    1.    Doors not large enough to accommodate a written sign shall be marked with a permanently attached pictogram of the equipment contained therein.

    2.    Doors that have either an approved visual identification clear glass  panel or a complete glass door panel are not required to be marked.

    905.7.2Locking cabinet doors. Cabinets shall be unlocked.

    Exceptions:

    1.    Visual identification panels of glass or other approved transparent frangible material that is easily broken and allows access.

    2.    Approved locking arrangements.

    3.    Group I-3.

    905.8Dry standpipes. Dry standpipes shall not be installed.

    Exception: Where subject to freezing and in accordance with NFPA 14.

    905.9Valve supervision. Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 903.4.  Where a fire alarm system is provided, a signal shall also be transmitted to the control unit.

    Exceptions:

    1. Valves to underground key or hub valves in roadway boxes provided by  the municipality or public utility do not require supervision.

    2. Valves locked in the normal position and inspected as provided in this code in buildings not equipped with a fire alarm system.

    905.10During construction. Standpipe systems required during construction and demolition operations shall be provided in accordance with Section 3311.

    SECTION 906

    PORTABLE FIRE EXTINGUISHERS

    906.1 General. Portable fire extinguishers shall be provided in occupancies and locations as required by the "International Fire Code".

    SECTION 907

    FIRE ALARM AND DETECTION SYSTEMS

    907.1General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components.

    907.1.1Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the follow- ing:

    1.    A floor plan which indicates the use of all rooms.

    2.    Locations of alarm-initiating and notification appliances.

    3.    Alarm control and trouble signaling equipment.

    4.    Annunciation.

    5.    Power connection.

    6.    Battery calculations.

    7.    Conductor type and sizes.

    8.    Voltage drop calculations.

    9.    Manufacturers, model numbers and listing information for equipment, devices and materials.

    10.  Details of ceiling height and construction.

    11.  The interface of fire safety control functions.

    907.1.2Equipment. Systems and their components shall be listed and approved for the purpose for which they are installed.

    907.2Where required. An approved manual, automatic or manual and automatic fire alarm system installed in accordance with the provisions of this code and  NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant notification in accordance with Section 907.9, unless other requirements are provided by another section of this code. Where automatic sprinkler protection installed in accordance with Section 903.3.1.1 or 903.3.1.2 is provided and connected to the building fire alarm system, automatic heat detection required by this section shall not be required.

    The automatic fire detectors shall be smoke detectors. Where ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be allowed.

    907.2.1Group A. A manual fire alarm system shall be installed in Group A  occupancies having an occupant load of 300 or more. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy.

    Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow.

    907.2.1.1System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm communications system in accordance with NFPA 72.

    Exception: Where approved, the prerecorded announcement is allowed to be manually deactivated for a period of time, not to exceed 3 minutes, for  the sole purpose of allowing a live voice announcement from an approved, constantly attended location.

    907.2.1.2Emergency power. Emergency voice/alarm communications systems shall be provided with an approved emergency power source.

    907.2.2Group B. A manual fire alarm system shall be installed in Group B occupancies having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.

    Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow.

    907.2.3Group E. A manual fire alarm system shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system.

    Exceptions:

    1.    Group E occupancies with an occupant load of less than 50.

    2.    Manual fire alarm boxes are not required in Group E occupancies where all the following apply:

    2.1.Interior corridors are protected by smoke detectors with alarm verification.

    2.2.Auditoriums, cafeterias, gymnasiums and the like are protected  by heat detectors or other approved detection devices.

    2.3.Shops and laboratories involving dusts or vapors are protected by

    heat detectors or other approved detection devices.

    2.4.Off-premises monitoring is provided.

                      2.5. The capability to activate the evacuation signal from a central point is provided.

    2.6.In buildings where normally occupied spaces are provided with a  two-way communication system between such spaces and a constantly attended receiving station from where a general evacuation alarm can be sounded, except in locations specifically designated by the building official.

    3. Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location.

    907.2.4Group F. A manual fire alarm system shall be installed in Group F  occupancies that are two or more stories in height and have an occupant load of 500 or more above or below the lowest level of exit discharge.

    Exception: Manual fire alarm boxes are not required when the building is equipped throughout with an automatic sprinkler system and the notification appliances will activate upon sprinkler water flow.

    907.2.5Group H. A manual fire alarm system shall be installed in Group H-5  occupancies and in occupancies used for the manufacture of organic coatings.  An automatic smoke detection system shall be installed for highly toxic gases,  organic peroxides and oxidizers in accordance with Chapters 37, 39 and 40,  respectively, of the fire code.

    907.2.6Group I. A manual fire alarm system shall be installed in Group I  occupancies. An electrically supervised, automatic smoke  detection  system shall be provided in accordance with Sections 907.2.6.1 and 907.2.6.2.

    Exception: Manual fire alarm boxes in resident or patient sleeping areas of Group I-1 and I-2 occupancies shall not be required at exits if located at all nurses' control stations or other constantly attended staff locations, provided  such stations are visible and continuously accessible and that travel distances required in Section 907.3.1 are not exceeded.

    907.2.6.1Group I-1. Corridors, habitable spaces other than sleeping units and kitchens and waiting areas that are open to corridors shall be equipped with an automatic smoke detection system.

    Exceptions:

    1.    Smoke detection in habitable spaces is not required where the facility is

    equipped through-out with an automatic sprinkler system.

    2.    Smoke detection is not required for exterior balconies.

    907.2.6.2Group I-2. Corridors in nursing homes (both intermediate care and skilled nursing facilities), detoxification facilities and spaces permitted to be open to the corridors by Section 407.2 shall be equipped with an automatic fire detection system. Hospitals shall be equipped with smoke detection as required in Section 407.2.

    Exceptions:

    1. Corridor smoke detection is not required in smoke compartments that contain patient sleeping units where patient sleeping units are provided with smoke  detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each patient sleeping unit and an audible and visual alarm at the nursing station attending each unit.

    2. Corridor smoke detection is not required in smoke compartments that contain patient sleeping units where patient sleeping unit doors are equipped with automatic door-closing devices with integral smoke detectors on the unit sides installed in accordance with their listing, pro-  vided that the integral detectors perform the required alerting function.

    907.2.6.3Group I-3. Group I-3 occupancies shall be equipped with a manual and automatic fire alarm system installed for alerting staff.

    907.2.6.3.1System initiation. Actuation of an automatic fire-extinguishing system, a manual fire alarm box or a fire detector shall initiate an approved fire alarm signal which automatically notifies staff. Presignal systems shall not be  used.

    907.2.6.3.2Manual fire alarm boxes. Manual fire alarm boxes are not required to be located in accordance with Section 907.3 where the fire alarm boxes are provided at staff-attended locations having direct supervision over areas where manual fire alarm boxes have been omitted.

    Manual fire alarm boxes shall be permitted to be locked in areas occupied by  detainees, provided that staff members are present within the subject area and have keys readily available to operate the manual fire alarm boxes.

    907.2.6.3.3Smoke detectors. An approved automatic smoke detection system shall be installed throughout resident housing areas, including sleeping units and contiguous day rooms, group activity spaces and other common spaces normally accessible to residents.

    Exceptions:

    1.    Other approved smoke detection arrangements providing equivalent protection including, but not limited to, placing detectors in exhaust ducts from cells or behind protective guards listed for the purpose are

    allowed when necessary to prevent damage or tampering.

    2.    Sleeping units in Use Conditions 2 and 3.

    3.    Smoke detectors are not required in sleeping units with four or fewer occupants in smoke compartments that are equipped throughout with an approved automatic sprinkler system.

    907.2.7Group M. A manual fire alarm system shall be installed in Group M  occupancies having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. The initiation of a signal from a manual fire alarm box shall initiate alarm notification appliances as  required by Section 907.9.

    Exceptions:

    1. Covered mall buildings complying with Section 402.

    2. Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will automatically activate upon sprinkler water flow.

    907.2.7.1 Occupant notification. During times that the building is occupied, the initiation of a signal from a manual fire alarm box or from a water flow  switch shall not be required to activate the alarm notification appliances when  an alarm signal is activated at a constantly attended location from which evacuation instructions shall be initiated over an emergency voice/alarm com-  munication system installed in accordance with Section 907.2.12.2.

    The emergency voice/alarm communication system shall be allowed to be  used for other announcements provided the manual fire alarm use takes precedence over any other use.

    907.2.8Group R-1. Fire alarm systems shall be installed in Group R-1  occupancies as required in Sections 907.2.8.1 through 907.2.8.3.

    907.2.8.1Manual fire alarm system. A manual fire alarm system shall be installed in Group R-1 occupancies.

    Exceptions:

    1. A manual fire alarm system is not required in buildings not more than  two stories in height where all individual sleeping units and contiguous attic and crawl spaces are separated from each other and public or  common areas by at least 1-hour fire partitions and each individual sleeping unit has an exit directly to a public way, exit court or yard.

    2. Manual fire alarm boxes are not required throughout the building when  the following conditions are met:

    2.1.The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2;

    2.2.The notification appliances will activate upon sprinkler water flow; and

    2.3.At least one manual fire alarm box is installed at an approved location.

    907.2.8.2Automatic fire alarm system. An automatic fire alarm system shall be installed throughout all interior corridors serving sleeping units.

    Exception: An automatic fire detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exterior exit access that leads directly to an exit.

    907.2.8.3Smoke alarms. Smoke alarms shall  be  installed as  required  by  Section 907.2.10. In buildings that are not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the smoke alarms in sleeping units shall be connected to an emergency electrical system and shall be annunciated by sleeping unit at a con- stantly attended location from which the fire alarm system is capable of being manually activated.

    907.2.9Group R-2. A manual fire alarm system shall be installed in Group R-2  occupancies where:

    1.    Any dwelling unit or sleeping unit is located three or more stories above the lowest level of exit discharge;

    2.    Any dwelling unit or sleeping unit is located more than one story below the highest level of exit discharge of exits serving the dwelling unit or sleeping unit; or

    3.    The building contains more than 16 dwelling units or sleeping units.

    Exceptions:

    1.    A fire alarm system is not required in buildings not more than two  stories in height where all dwelling units or sleeping units and  contiguous attic and crawl spaces are separated from each other and  public or common areas by at least 1-hour fire partitions and each dwelling unit or sleeping unit has an exit directly to a public way,  exit court or yard.

    2.    Manual fire alarm boxes are not required throughout the building  when the following conditions are met:

    2.1.The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or  Section 903.3.1.2; and

    2.2.The  notification  appliances  will  activate  upon  sprinkler  flow.

    3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1023.6, Exception 4.

    907.2.10Single- and multiple-station smoke alarms. Listed single- and multiple-station smoke alarms complying with UL 217 shall be installed in accordance with the provisions of this code and the household fire-warning equipment provisions of NFPA 72.

    907.2.10.1Where required. Single- or multiple-station smoke alarms shall be installed in the locations described in Sections 907.2.10.1.1 through  907.2.10.1.3.

    907.2.10.1.1                 Group R-1. Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1:

    1.    In sleeping areas.

    2.    In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit.

    3. In each story within the sleeping unit, including basements. For  sleeping units with split levels and without an intervening door  between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.

    907.2.10.1.2                 Groups R-2, R-3, R-4 and I-1. Single- or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4  and I-1, regardless of occupant load at all of the following locations:

    1.    On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bed-rooms.

    2.    In each room used for sleeping purposes.

    3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or  dwelling units with split levels and without an intervening door  between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.

    907.2.10.1.3Group I-1. Single- or multiple-station smoke alarms shall be installed and maintained in sleeping areas in Group I-1 occupancies.

    Exception: Single- or multiple-station smoke alarms shall not be required  where the building is equipped throughout with an automatic fire detection system in accordance with Section 907.2.6.

    907.2.10.2Power source. In new construction, required smoke alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for  overcurrent protection.

    Exception: Smoke alarms are not required to be equipped with battery backup in Group R-1 where they are connected to an emergency electrical system.

    907.2.10.3Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit in Group R-2, R-3 or R-4, or  within an individual dwelling unit or sleeping unit in Group R-1, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly  audible in all bedrooms over background noise levels with all intervening doors  closed.

    907.2.10.4Acceptance testing. When the installation of the alarm devices is complete, each detector and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the household fire warning equipment provisions of NFPA 72.

    907.2.11Special amusement buildings. An approved automatic smoke detection system shall be provided in special amusement buildings in accordance with this section.

    Exception: In areas where ambient conditions will cause a smoke detection system to alarm, an approved alternative type of automatic detector shall be installed.

    907.2.11.1Alarm. Activation of any  single smoke  detector, the  automatic sprinkler system or any other automatic fire detection device shall immediately  sound an alarm at the building at a constantly attended location from which emergency action can be initiated, including the capability of manual initiation  of requirements in Section 907.2.11.2.

    907.2.11.2System response. The activation of two or more smoke detectors, a single smoke detector with alarm verification, the automatic sprinkler system or

    other approved fire detection device shall automatically:

    1.Cause illumination of the means of egress with light of not less than 1  foot-candle (11 lux) at the walking surface level;

    2.    Stop any conflicting or confusing sounds and visual distractions; and

    3. Activate an approved directional exit marking that will become apparent in an emergency.

    Such system response shall also include activation of a prerecorded message, clearly audible throughout the special amusement building, instructing patrons to proceed to the nearest exit. Alarm signals used in conjunction with the prerecorded message shall produce a sound which is distinctive from other sounds used during normal operation.

    The wiring to the auxiliary devices and equipment used to accomplish the above fire safety functions shall be monitored for integrity in accor- dance with NFPA 72.

    907.2.11.3Emergency voice/alarm communication system. An emergency voice/alarm communication system, which is also allowed to serve as a public  address system, shall be installed in accordance with NFPA 72, and shall be audible throughout the entire special amusement building.

    907.2.12High-rise buildings. Buildings with a floor used for human occupancy located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communication system in accordance with Section  907.2.12.2.

    Exceptions:

    1. Airport traffic control towers in accordance with Sections 412 and  907.2.22.

    2. Open parking garages in accordance with Section 406.3.

    3. Buildings with an occupancy in Group A-5.

    4. Low-hazard special occupancies in accordance with Section 503.1.1.

    5. Buildings with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 415.

    907.2.12.1Automatic fire detection. Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows:

    1. In   each   mechanical   equipment,   electrical,   trans-former,   telephone

    equipment  or  similar  room  which  is  not  provided  with  sprinkler  protection, elevator machine rooms and in elevator lobbies.

    2. In the main return air and exhaust air plenum of each air-conditioning  system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.

    3. At each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. In Group R-1 and R-2 occupancies a listed smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and  serving not more than 10 air inlet openings.

    907.2.12.2Emergency voice/alarm communication system. The operation of  any automatic fire detector, sprinkler water-flow device or manual fire alarm  box shall automatically sound an alert tone followed by voice instructions giving approved information and directions for a general or staged evacuation  on a minimum of the alarming floor, the floor above and the floor below in accordance with the building's fire safety and evacuation plans required by  Section 404 of the fire code. Speakers shall be provided throughout the building  by paging zones. As a minimum, paging zones shall be provided as follows:

    1. Elevator groups.

    2. Exit stairways.

    3. Each floor.

    4. Areas of refuge as defined in Section 1002.1.

    Exception: In Group I-1 and I-2 occupancies, the alarm shall sound in a constantly attended area and a general occupant notification shall be broadcast over the overhead page.

    907.2.12.2.1Manual override. A manual over-ride for emergency voice communication shall be provided on a selective and all-call basis for all paging zones.

    907.2.12.2.2Live voice messages. The emergency voice/alarm communication system shall also have the capability to broadcast live voice messages through paging zones on a selective and all-call basis.

    907.2.12.2.3Standard. The emergency voice/ alarm communication system shall be designed and installed in accordance with NFPA 72.

    907.2.12.3 Fire department communication system. An approved two-way,  fire department communication system designed and installed in accordance with NFPA 72 shall be provided for fire department use. It shall operate between a fire command center complying with Section 911 and elevators, elevator lobbies, emergency and standby power rooms, fire pump rooms, areas

    of refuge and inside enclosed exit stairways. The fire department communication device shall be provided at each floor level within the enclosed stairway.

    Exception:  Fire  department  radio  systems  where  approved  by  the  fire department.

    907.2.13Atriums connecting more than two stories. A fire alarm system shall be installed in occupancies with an atrium that connects more than two stories. The system shall be activated in accordance with Section 907.6. Such occupancies in Group A, E or M shall be provided with an emergency voice/alarm communication system complying with the requirements of Section 907.2.12.2.

    907.2.14High-piled combustible storage areas. An automatic fire detection system shall be installed through-out high-piled combustible storage areas where required by Section 2306.5 of the fire code.

    907.2.15Delayed egress locks. Where delayed egress locks are installed on  means of egress doors in accordance with Section 1008.1.8.6, an automatic smoke or heat detection system shall be installed as required by that section.

    907.2.16Aerosol storage uses. Aerosol storage rooms and general-purpose  warehouses containing aerosols shall be provided with an approved manual fire alarm system where required by the fire code.

    907.2.17Lumber, wood structural panel and veneer mills. Lumber, wood  structural panel and veneer mills shall be provided with a manual fire alarm system.

    907.2.18Underground buildings with smoke exhaust system. Where a smoke exhaust system is installed in an underground building in accordance with this code, automatic fire detectors shall be provided in accordance with this section.

    907.2.18.1Smoke detectors. A minimum of one smoke detector listed for  the intended purpose shall be installed in the following areas:

    1.    Mechanical equipment, electrical, transformer, telephone equipment, elevator machine or similar rooms.

    2.    Elevator lobbies.

    3.    The main return and exhaust air plenum of each air-conditioning system serving more than one story and located in a serviceable area downstream of the last duct inlet.

    4.    Each connection to a vertical duct or riser serving two or more floors from return air ducts or plenums of heating, ventilating and air- conditioning  systems,  except  that in  Group  R  occupancies,  a  listed

    smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air inlet openings.

    907.2.18.2Alarm required. Activation of the smoke exhaust system shall activate an audible alarm at a constantly attended location.

    907.2.19Underground buildings. Where the lowest level of a structure is more than 60 feet (18 288 mm) below the lowest level of exit discharge, the structure shall be equipped throughout with a manual fire alarm system,  including an emergency voice/alarm communication system installed in accordance with Section 907.2.12.2.

    907.2.19.1Public address system. Where a fire alarm system is not required by Section 907.2, a public address system shall be provided that shall be capable of transmitting voice communications to the highest level of exit discharge serving the underground portions of the structure and all levels below.

    907.2.20Covered mall buildings. Covered mall buildings exceeding 50,000 square feet (4645 m2) in total floor area shall be provided with an emergency voice/alarm communication system. An emergency voice/alarm communication system serving a mall, required or otherwise, shall be accessible to the fire department. The system shall be provided in accordance with Section  907.2.12.2.

    907.2.21Residential aircraft hangars. A minimum of one listed smoke alarm shall be installed within a residential aircraft hangar as defined in Section  412.3.1 and shall be interconnected into the residential smoke alarm or other sounding device to provide an alarm that will be audible in all sleeping areas of  the dwelling.

    907.2.22Airport traffic control towers. An automatic fire detection system shall be provided in airport traffic control towers.

    907.2.23Battery rooms. An approved automatic smoke detection system shall be installed in areas containing stationary storage battery systems having a liquid capacity of more than 50 gallons (189.3 L). The detection system shall be supervised by an approved central, proprietary or remote station service or a local alarm that will sound an audible signal at a constantly attended location.

    907.3Manual fire alarm boxes. Manual fire alarm boxes shall be installed in accordance with Sections 907.3.1 through 907.3.5.

    907.3.1Location. Manual fire alarm boxes shall be located not more than 5  feet (1524 mm) from the entrance to each exit. Additional manual fire alarm  boxes shall be located so that travel distance to the nearest box does not exceed

    200 feet (60 960 mm).

    907.3.2Height. The height of the manual fire alarm boxes shall be a minimum  of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm), measured vertically, from the floor level to the activating handle or lever of the box.

    907.3.3Color. Manual fire alarm boxes shall be red in color.

    907.3.4Signs. Where fire alarm systems are not monitored by a supervising station, an approved permanent sign shall be installed adjacent to each manual fire alarm box that reads: WHEN ALARM SOUNDS-CALL FIRE DEPARTMENT.

    Exception:   Where   the   manufacturer   has   permanently   provided   this information on the manual fire alarm box.

    907.3.5Protective covers. The building official is authorized to require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or to provide the manual fire alarm box with protection from physical damage. The protective cover shall be transparent or red in color with a transparent face to permit visibility of the manual fire alarm box. Each cover shall include proper operating instructions. A protective cover that emits a local alarm signal shall not be installed unless approved.

    907.4Power supply. The primary and secondary power supplies for the fire alarm system shall be provided in accordance with NFPA 72.

    907.5Wiring. Wiring shall comply with the requirements of Chapter 27 and  NFPA 72. Wireless protection systems utilizing radio-frequency transmitting devices shall comply with the special requirements for supervision of low-power  wireless systems in NFPA 72.

    907.6Activation. Where an alarm notification system is required by another section of this code, it shall be activated by:

    1.    A required automatic fire alarm system.

    2.    Sprinkler water-flow devices.

    3.    Required manual fire alarm boxes.

    907.7Presignal system. Presignal systems shall not be installed unless approved  by the building official and the fire department. Where a presignal system is installed, 24-hour personnel supervision shall be provided at a location approved  by the fire department, in order that the alarm signal can be actuated in the event  of fire or other emergency.

    907.8Zones. Each floor shall be zoned separately and a zone shall not exceed 22,500 square feet (2090 m2). The length of any zone shall not exceed 300 feet  (91 440 mm) in any direction.

    Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13.

    907.8.1Zoning indicator panel. A zoning indicator panel and the associated controls shall be provided in an approved location. The visual zone indication shall lock in until the system is reset and shall not be canceled by the operation  of an audible alarm-silencing switch.

    907.8.2High-rise buildings. In buildings with a floor used for human  occupancy that is located more than 75 feet (22 860 mm) above the lowest level  of fire department vehicle access, a separate zone by floor shall be provided for  all of the following types of alarm-initiating devices where provided:

    1.    Smoke detectors.

    2.    Sprinkler water-flow devices.

    3.    Manual fire alarm boxes.

    4.    Other approved types of automatic fire detection devices or suppression  systems.

    907.9Alarm notification appliances. Alarm notification appliances shall be provided and shall be listed for their purpose. Audible and visual alarms shall be installed in accordance with the "ADAAG" and NFPA 72 as referenced in Chapter 35.

    1.  907.9.1 Visible alarms. Deleted. 907.9.1.1 Public and common areas. Deleted. 907.9.1.2 Employee work areas. Deleted.  907.9.1.3 Groups I-1 and R-1. Deleted.  907.9.1.4 Group R-2. Deleted.

    907.9.2 Audible alarms. Audible alarm notification appliances shall be provided and shall sound a distinctive sound that is not to be used for any  purpose other than that of a fire alarm. The audible alarm notification appliances  shall provide a sound pressure level of 15 decibels (dBA) above the average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space within the building. The minimum sound pressure levels shall be: 70 dBA in  occupancies in Groups R and I-1; 90 dBA in mechanical equipment rooms and  60 dBA in other occupancies. The maximum sound pressure level for audible alarm notification appliances shall be 120 dBA at the minimum hearing distance from the audible appliance. Where the average ambient noise is greater than 105 dBA, visible alarm notification appliances shall be provided in accordance with  NFPA 72 and audible alarm notification appliances shall not be required.

    Exception: Deleted.

    907.10Fire safety functions. Automatic fire detectors utilized for the purpose of  performing fire safety functions shall be connected to the building's fire alarm control panel where a fire alarm system is required by Section 907.2. Detectors shall, upon actuation, perform the intended function and activate the alarm notification appliances or a visible and audible supervisory signal at a constantly attended location. In buildings not required to be equipped with a fire alarm system, the automatic fire detector shall be powered by normal electrical service and, upon actuation, perform the intended function. The detectors shall be located in accordance with NFPA 72.

    907.11Duct smoke detectors. Duct smoke detectors shall be connected to the building's fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory  signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open-area detection.

    Exceptions:

    1. The supervisory signal at a constantly attended location is not required  where duct smoke detectors activate the building's alarm notification appliances.

    2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as  air duct detector trouble.

    907.12Access. Access shall be provided to each detector for periodic inspection, maintenance and testing.

    907.13Fire-extinguishing systems. Automatic fire-extinguishing systems shall be connected to the building fire alarm system where a fire alarm system is required by another section of this code or is otherwise installed.

    907.14Monitoring. Fire alarm systems required by this chapter shall be monitored by an approved supervising station in accordance with NFPA 72.

    Exception: Supervisory service is not required for:

    1.    Single- and multiple-station smoke alarms required by Section 907.2.10.

    2.    Smoke detectors in Group I-3 occupancies.

    3.    Automatic sprinkler systems in one-, two-, and three-family dwellings.

    907.15Automatic telephone-dialing devices. Automatic telephone-dialing devices used to transmit an emergency alarm shall not be connected to any fire department telephone number unless approved by the fire chief.

    907.16Acceptance tests. Upon completion of the installation of the fire alarm

    system, alarm notification appliances and circuits, alarm-initiating devices and circuits, supervisory-signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in accordance with  NFPA 72.

    907.17Record of completion. A record of completion in accordance with NFPA 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided.

    907.18Instructions. Operating, testing and maintenance instructions, and record  drawings ("as builts") and equipment specifications shall be provided at an approved location.

    907.19Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with the fire code.

    SECTION 908 EMERGENCY ALARM SYSTEMS

    908.1Group H occupancies. Emergency alarms for the  detection  and notification of an emergency condition in Group H occupancies shall be provided in accordance with Section 414.7.

    908.2Group H-5 occupancy. Emergency alarms for notification of an emergency condition in an HPM facility shall be provided as required in Section  415.8.4.6. A continuous gas-detection system shall be provided for HPM gases in accordance with Section 415.8.7.

    908.3Highly toxic and toxic materials. A gas detection system shall be provided to detect the presence of gas at or below the permissible exposure limit (PEL) or  ceiling limit of the gas for which detection is provided. The system shall be capable of monitoring the discharge from the treatment system at or below one- half the immediately dangerous to life and health (IDLH) limit.

    Exception: A gas-detection system is not required for toxic gases when the physiological warning threshold level for the gas is at a level below the accepted PEL for the gas.

    908.3.1Alarms. The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is detected. The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected. The audible alarm shall be distinct from all other alarms.

    Exception: Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is

    stored.

    908.3.2Shutoff of gas supply. The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected.

    Exception: Automatic shutdown is not required for reactors utilized for the production of highly toxic or toxic compressed gases where such reactors are:

    1.    Operated at pressures less than 15 pounds per square inch gauge (psig) (103.4 kPa).

    2.    Constantly attended.

    3.    Provided with readily accessible emergency shut-off valves.

    908.3.3Valve closure. The automatic closure of shutoff valves shall be in accordance with the following:

    1. When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.

    2. Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas  cabinets or exhausted enclosures, the shutoff valves on all gas lines for the specific gas detected shall automatically

    close.

    3. Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve  for the compressed container of specific gas detected supplying the manifold shall automatically close.

    Exception: When the gas-detection sampling point initiating the gas-  detection system alarm is at a use location or within a gas valve enclosure of  a branch line down-stream of a piping distribution manifold, the shutoff  valve in the gas valve enclosure for the branch line located in the piping distribution manifold enclosure shall automatically close.

    908.4Ozone gas-generator rooms. Ozone gas-generator rooms shall be equipped with a continuous gas-detection system that will shut off the generator and sound a local alarm when concentrations above the PEL occur.

    908.5Repair garages. A flammable-gas detection system shall be provided in

    repair  garages  for  vehicles  fueled  by  nonodorized  gases  in  accordance  with Section 406.6.6.

    908.6Refrigerant detector. Machinery rooms shall contain a refrigerant detector  with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classification indicated in the mechanical code. Detectors and alarms shall be placed in approved locations.

    SECTION 909 SMOKE CONTROL SYSTEMS

    909.1Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required by other provisions of this code. The  purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by this section serve a different  purpose than the smoke- and heat-venting provisions found in Section 910.  Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the mechanical code.

    909.2General design requirements. Buildings, structures or parts thereof required by this code to have a smoke control system or systems shall have such  systems designed in accordance with the applicable requirements of Section 909  and the generally accepted and well-established principles of engineering relevant to the design. The construction documents shall include sufficient information and detail to adequately describe the elements of the design necessary for the proper implementation of the smoke control systems. These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions.

    909.3Special inspection and test requirements. In addition to the ordinary inspection and test requirements which buildings, structures and parts thereof are required to undergo, smoke control systems subject to the provisions of Section  909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its final installed condition. The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests.  Such  commissioning  shall  be  in  accordance  with  generally  accepted

    engineering practice and, where possible, based on published standards for the particular testing involved. The special inspections and tests required by this sec- tion shall be conducted in accordance with Section 1704.

    909.4Analysis. A rational analysis supporting the types of smoke control systems  to be employed, their methods of operation, the systems supporting them and the methods of construction to be utilized shall accompany the submitted construction  documents and shall include, but not be limited to, the items indicated in Sections  909.4.1 through 909.4.6.

    909.4.1Stack effect. The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the system's capabilities. In determining the maximum probable stack effect, altitude, elevation, weather history and interior temperatures shall be used.

    909.4.2Temperature effect of fire. Buoyancy and expansion caused by the design fire in accordance with Section 909.9 shall be analyzed. The system shall be designed

    such that these effects do not adversely interfere with the system's capabilities.

    909.4.3Wind effect. The design shall consider the adverse effects of wind. Such consideration shall be consistent with the wind-loading provisions of  Chapter 16.

    909.4.4HVAC systems. The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis shall include all permutations of systems status. The design shall consider the effects of the fire on the HVAC systems.

    909.4.5Climate. The design shall consider the effects of low temperatures on  systems, property and occupants. Air inlets and exhausts shall be located so as  to prevent snow or ice blockage.

    909.4.6Duration of operation. All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event  for a period of not less than either 20 minutes or 1.5 times the calculated egress  time, whichever is less.

    909.5Smoke barrier construction. Where provided, smoke barriers shall comply  with Section 709, and shall be constructed and sealed to limit leakage areas exclusive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios:

    1. Walls:                                           A/Aw = 0.00100

    2.Exit enclosures:                             A/Aw = 0.00035

    3.All other shafts:                            A/Aw = 0.00150

    4.Floors and roofs:                          A/AF = 0.00050

    Where:

    A = Total leakage area, square feet (m2).

    AF = Unit floor or roof area of barrier, square feet (m2). Aw = Unit wall area of barrier, square feet (m2).

    The leakage area ratios shown do not include openings due to doors, operable  windows or similar gaps. These shall be included in calculating the total leakage area.

    909.5.1Leakage area. The total leakage area of the barrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio, plus the area of other openings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official.

    909.5.2Opening protection. Openings in smoke barriers shall be protected by  automatic-closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by fire door assemblies complying with Section 715.4.3.

    Exceptions:

    1. Passive smoke control systems with automatic-closing devices actuated  by spot-type smoke detectors listed for releasing service installed in accordance with Section 907.10.

    2. Fixed openings between smoke zones that are protected utilizing the airflow method.

    3. In Group I-2, where such doors are installed across corridors, a pair of  opposite-swinging doors with-out a center mullion shall be installed having vision panels with fire protection-rated glazing materials in fire protection-rated frames, the area of which shall not exceed that tested. The doors shall be close-fitting within operational tolerances and shall not have undercuts, louvers or grilles. The doors shall have head and  jamb stops, astragals or rabbets at meeting edges and shall be automatic- closing  by  smoke  detection  in  accordance  with  Section  715.4.7.3.

    Positive-latching devices are not required.

    4. Group I-3.

    5. Openings between smoke zones with clear ceiling heights of 14 feet  (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size.

    909.5.2.1 Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250°F (121°C) smoke damper complying with Section 716.

    909.6Pressurization method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke control zone of fire origin.

    909.6.1Minimum pressure difference. The minimum pressure difference  across a smoke barrier shall be 0.05-inch water gage (0.0124 kPa) in fully sprinklered buildings.

    In buildings permitted to be other than fully sprinklered, the smoke control system shall be designed to achieve pressure differences at least two times the maximum calculated pressure difference produced by the design fire.

    909.6.2Maximum pressure difference. The maximum air pressure difference  across a smoke barrier shall be determined by required door-opening or closing forces. The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 1008.1.2. Opening and closing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reactions. The calculated force to set a side-hinged, swinging door in motion shall be determined by:

    F = Fdc + K(WA ∆P)/2(W- d)                                            (Equation 9-1)

    where:

    A = Door area, square feet (m2).

    d = Distance from door handle to latch edge of door, feet (m).  F = Total door opening force, pounds (N).

    Fdc = Force required to overcome closing device, pounds (N).

    K = Coefficient 5.2 (1.0). W = Door width, feet (m).

    ∆P = Design pressure difference, inches of water (Pa).

    909.7Airflow design method. When approved by the building official, smoke migration through openings fixed in a permanently open position, which are located between smoke control zones by the use of the airflow method, shall be permitted. The design airflow shall be in accordance with this section. Airflow  shall be directed to limit smoke migration from the fire zone. The geometry of  openings shall be considered to prevent flow reversal from turbulent effects.

    909.7.1Velocity. The minimum average velocity through a fixed opening shall not be less than:

    v = 217.2 [h (Tf - To)/(Tf+ 460)]1/2                                                   (Equation 9-2)

    For SI: v = 119.9 [h (Tf - To)/Tf]1//2  where:

    h = Height of opening, feet (m). Tf= Temperature of smoke, °F (K).

    To= Temperature of ambient air, °F (K).

    v = Air velocity, feet per minute (m/minute).

    909.7.2Prohibited conditions. This method shall not be  employed where either the quantity of air or the velocity of the airflow will adversely affect other  portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. In no case shall airflow toward the fire exceed 200 feet per minute (1.02 m/s). Where the formula in Section 909.7.1  requires airflow to exceed this limit, the airflow method shall not be used.

    909.8Exhaust method. When approved by the building official, mechanical smoke control for large enclosed volumes, such as in atriums or malls, shall be permitted to utilize the exhaust method. Smoke control systems using the exhaust method shall be designed in accordance with NFPA 92B.

    909.8.1Smoke layer. The height of the lowest horizontal surface of the accumulating smoke layer shall be maintained at least 6 feet (1829 mm) above any walking surface that forms a portion of a required egress system within the smoke zone.

     909.9 Design fire. The design fire shall be based on a rational analysis performed by the registered design professional and approved by the building official. The design fire shall be based on the analysis in accordance with Section 909.4 and this section.

    909.9.1Factors considered. The engineering analysis shall include the characteristics of the fuel, fuel load, effects included by the fire and whether the fire is likely to be steady or unsteady.

    909.9.2Separation distance. Determination of the design fire shall include consideration of the type of fuel, fuel spacing and configuration.

    R = [Q/(12?q")]1/2                                                                                    (Equation 9-8)

    Where:

    q" = Incident radiant heat flux required for nonpiloted ignition, Btu/ft2 s (W/m2).

    Q = Heat release from fire, Btu/s (kW).

    R = Separation distance from target to center of fuel package, feet (m).

    909.9.3Heat-release assumptions. The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material.

    909.9.4Sprinkler effectiveness assumptions. A documented engineering analysis shall be provided for conditions that assume fire growth is halted at the time of sprinkler activation.

    909.10Equipment. Equipment including, but not limited to, fans, ducts, automatic dampers and balance dampers, shall be suitable for its intended use,  suitable for the probable expo-sure temperatures that the rational analysis indicates and as approved by the building official.

    909.10.1Exhaust fans. Components of exhaust fans shall be rated and certified  by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by:

    Ts = (Qc/mc) + (Ta)                                                             (Equation 9-9)

    where:

    c = Specific heat of smoke at smoke layer temperature, Btu/lb°F (kJ/kg K).  m = Exhaust rate, pounds per second (kg/s).

    Qc = Convective heat output of fire, Btu/s (kW). Ta = Ambient temperature, °F (K).

    Ts = Smoke temperature, °F (K).

    Exception: Reduced Ts as calculated based on the assurance of adequate dilution air.

    909.10.2Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed as determined in accordance with Section 909.10.1. Ducts shall be constructed and supported in accordance with the mechanical code.

    Ducts  shall  be  leak  tested  to  1.5  times  the  maximum  design  pressure  in accordance  with  nationally  accepted  practices.  Measured  leakage  shall  not exceed 5 percent of design flow. Results of such testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire-resis- tance-rated structural elements of the building by substantial, noncombustible  supports.

    Exception: Flexible connections (for the  purpose of vibration isolation) complying with the mechanical code, that are constructed of approved fire-  resistance-rated materials.

    909.10.3Equipment, inlets and outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard.

    Outside air inlets shall be located so as to minimize the potential for introducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard.

    909.10.4Automatic dampers. Automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and conform to the requirements of Section 716.3.

    909.10.5Fans. In addition to other requirements, belt-driven fans shall have 1.5  times the number of belts required for the design duty, with the minimum number of belts being two. Fans shall be selected for stable performance based  on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer's fan curves shall be part of the documentation procedures. Fans shall be supported and restrained by noncombustible devices in accordance with the requirements of Chapter 16. Motors driving fans shall not be operated beyond their nameplate horsepower (kilowatts), as determined from measurement of actual current draw, and shall have a minimum service factor of 1.15.

    909.11Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power system. Secondary power shall be from an approved standby source complying with  Chapter 27. The standby power source and its transfer switches shall be in a separate room from the normal power transformers and switch gear and shall be enclosed in a room constructed of not less than 1-hour fire barriers ventilated directly to and from the exterior. Power distribution from the two sources shall be  by independent routes. Transfer to full standby power shall be automatic and within 60 seconds of failure of the primary power. The systems shall comply with this code or Chapter 27.

    909.11.1Power sources and power surges. Elements of the smoke management system relying on volatile memories or the like shall be supplied with uninterruptable power sources of sufficient duration to span a 15-minute primary power interruption. Elements of the smoke management system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means.

    909.12Detection and control systems. Fire detection systems providing control input or output signals to mechanical smoke control systems or elements thereof shall comply with the requirements of Section 907. Such systems shall be equipped with a control unit complying with UL 864 and listed as smoke control equipment.

    Control systems for mechanical smoke control systems shall include provisions  for verification.  Verification  shall include positive confirmation of  actuation,

    testing, manual override, the presence of power downstream of all disconnects and, through a preprogrammed weekly test sequence, report abnormal conditions audibly, visually and by printed report.

    909.12.1Wiring. In addition to meeting requirements of Chapter 27,  all wiring, regardless of voltage, shall be fully enclosed within continuous raceways.

    909.12.2Activation. Smoke control systems shall be activated in accordance with this section.

    909.12.2.1Pressurization, airflow or exhaust method. Mechanical smoke control systems using the pressurization, airflow or exhaust method shall have completely automatic control.

    909.12.2.2Passive method.  Passive smoke control  systems actuated  by  approved spot-type detectors listed for releasing service shall be permitted.

    909.12.3Automatic control. Where completely automatic control is required  or used, the automatic-control sequences shall be initiated from an appropriately zoned automatic sprinkler system complying with Section 903.3.1.1, manual controls that are readily accessible to the fire department and any smoke detectors required by engineering analysis.

    909.13Control air tubing. Control air tubing shall be of sufficient size to meet the required response times. Tubing shall be flushed clean and dry prior to final connections and shall be adequately supported and protected from damage.  Tubing passing through concrete or masonry shall be sleeved and protected from abrasion and electrolytic action.

    909.13.1Materials. Control air tubing shall be hard drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM B 251 and ASTM B 280. Fittings shall be wrought copper or brass,  solder type, in accordance with ASME B 16.18 or ASME B 16.22. Changes in direction shall be made with appropriate tool bends. Brass compression-type fittings shall be used at final connection to devices; other joints shall be brazed using a BCuP5 brazing alloy with solidus above 1,100°F (593°C) and liquids below 1,500°F (816°C). Brazing flux shall be used on copper-to-brass joints only.

    Exception: Nonmetallic tubing used within control panels and at the final connection to devices, provided that all of the following conditions are met:

    1.    Tubing shall be listed by an approved agency for flame and smoke characteristics.

    2. Tubing and connected devices shall be completely enclosed within galvanized or paint-grade steel enclosure of not less than 0.030 inch

    (0.76 mm) (No. 22 galvanized sheet gage) thickness. Entry to the enclosure shall be by copper tubing with a protective grommet of  neoprene or teflon or by suit-able brass compression to male-barbed adapter.

    3.    Tubing shall be identified by appropriately documented coding.

    4. Tubing shall be neatly tied and supported within enclosure. Tubing bridging cabinet and door or moveable device shall be of sufficient length to avoid tension and excessive stress. Tubing shall be protected against abrasion. Tubing serving devices on doors shall be fastened along hinges.

    909.13.2Isolation from other functions. Control tubing serving other than smoke control functions shall be isolated by automatic isolation valves or shall be an independent system.

    909.13.3Testing. Control air tubing shall be tested at three times the operating  pressure for not less than 30 minutes without any noticeable loss in gauge  pressure prior to final connection to devices.

    909.14Marking and identification. The detection and control systems shall be clearly marked at all junctions, accesses and terminations.

    909.15Control diagrams. Identical control diagrams showing all devices in the system and identifying their location and function shall be maintained current and kept on file with the building official, the fire department and in the fire command center in a format and manner approved by the fire chief.

    909.16Fire-fighter's smoke control panel. A fire-fighter's smoke control panel  for fire department emergency response purposes only shall be provided and shall include manual control or override of automatic control for mechanical smoke control systems. The panel shall be located in a fire command center complying with Section 911 in high-rise buildings or buildings with smoke-protected assembly seating. In all other buildings, the fire-fighter's smoke control panel shall be installed in an approved location adjacent to the fire alarm control panel. The fire-fighter's smoke control panel shall comply with Sections 909.16.1  through 909.16.3.

    909.16.1Smoke control systems. Fans within the building shall be shown on  the fire-fighter's control panel. A clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control equipment, annunciated by fan and zone, and by  pilot-lamp-type indicators as follows:

    1. Fans, dampers and other operating equipment in their normal status- WHITE.

    2. Fans, dampers and other operating equipment in their off or closed

    status-RED.

    3. Fans, dampers and other operating equipment in their on or open status- GREEN.

    4. Fans, dampers and other operating equipment in a fault status- YELLOW/AMBER.

    909.16.2Smoke control panel. The fire-fighter's control panel shall provide control capability over the complete smoke-control system equipment within the building as follows:

    1.    ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes stairway pressurization fans; smoke exhaust fans; supply, return and exhaust fans; elevator shaft fans and other operating equipment used or intended for smoke control purposes.

    2.    OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building.

    3.    ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire-fighter's control panel.

    Exceptions:

    1. Complex systems, where approved, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit.

    2. Complex systems, where approved, where the control is accomplished by  computer interface using approved, plain English commands.

    909.16.3Control action and priorities. The firefighter's control panel actions shall be as follows:

    1.    ON-OFF and OPEN-CLOSE control actions shall have the highest priority  of any control point within the building. Once issued from the fire-fighter's control panel, no automatic or manual control from any other control point within the building shall contradict the control action. Where automatic means are provided to interrupt normal, nonemergency equipment operation  or produce a specific result to safe-guard the building or equipment (i.e., duct freezestats, duct smoke detectors, high-temperature cutouts, tem-  perature-actuated linkage and similar devices), such means shall be capable  of being overridden by the fire-fighter's control panel. The last control action as indicated by each fire-fighter's control panel switch position shall prevail. In no case shall control actions require the smoke control system to  assume more than one configuration at any one time.

    Exception: Power disconnects required by Chapter 27 and its referenced  standards listed in Chapter 35.

    2.    Only the AUTO position of each three-position fire-fighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the NORMAL,  nonemergency, building control position. Where a fire-fighter's control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described above. When directed by an automatic signal to assume an emergency condition, the NORMAL position shall become the emergency condition for that device or group of devices within

    the zone. In no case shall control actions require the smoke control system to assume more than one con-figuration at any one time.

    909.17System response time. Smoke-control system activation shall be initiated immediately after receipt of an appropriate automatic or manual activation  command. Smoke control systems shall activate individual components (such as  dampers and fans) in the sequence necessary to prevent physical damage to the  fans, dampers, ducts and other equipment. For purposes of smoke control, the fire-fighter's control panel response time shall be the same for automatic or  manual smoke control action initiated from any other building control point. The total response time, including that necessary for detection, shutdown of operating equipment and smoke control system startup, shall allow for full operational mode to be achieved before the conditions in the space exceed the design smoke condition. The system response time for each component and their sequential relationships shall be detailed in the required rational analysis and verification of  their installed condition reported in the required final report.

    909.18Acceptance testing. Devices, equipment, components and sequences shall be individually tested. These tests, in addition to those required by other provisions of this code, shall consist of determination of function, sequence and, where applicable, capacity of their installed condition.

    909.18.1Detection devices. Smoke or fire detectors that are a part of a smoke control system shall be tested in accordance with Chapter 9 in their installed condition. When applicable, this testing shall include verification of airflow in both minimum and maximum conditions.

    909.18.2Ducts. Ducts that are part of a smoke control system shall be traversed using generally accepted practices to determine actual air quantities.

    909.18.3Dampers. Dampers shall be tested for function in their installed condition.

    909.18.4Inlets and outlets. Inlets and outlets shall be read using generally accepted practices to determine air quantities.

    909.18.5Fans. Fans shall be examined for correct rotation. Measurements of  voltage, amperage, revolutions per minute (rpm) and belt tension shall be made.

    909.18.6Smoke barriers. Measurements using inclined manometers or other approved calibrated measuring devices shall be made  of the pressure  differences across smoke barriers. Such measurements shall be conducted for  each possible smoke control condition.

    909.18.7Controls. Each smoke zone, equipped with an automatic-initiation device, shall be put into operation by the actuation of one such device. Each additional device within the zone shall be verified to cause the same sequence without requiring the operation of fan motors in order to prevent damage. Control sequences shall be verified throughout the system, including verification of override from the fire-fighter's control panel and simulation of  standby power conditions.

    909.18.8Special inspections for smoke control. Smoke control systems shall be tested by a special inspector.

    909.18.8.1Scope of testing. Special inspections shall be conducted in accordance with the following:

    1.    During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location.

    2. Prior to occupancy and after sufficient completion for the purposes of  pressure-difference testing, flow measurements, and detection and control verification.

    909.18.8.2Qualifications. Special inspection agencies for smoke control shall have expertise in fire protection engineering, mechanical engineering and certification as air balancers.

    909.18.8.3Reports. A complete report of testing shall be prepared by the special inspector or special inspection agency. The report shall include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag or mark. The report shall be reviewed  by the responsible registered design professional and, when satisfied that the design intent has been achieved, the responsible registered design professional shall seal, sign and date the report.

    909.18.8.3.1 Report filing. A copy of the final report shall be filed with the building official and an identical copy shall be maintained in an approved location at the building.

    909.18.9Identification and documentation. Charts, drawings and other documents identifying and locating each component of the smoke control system, and describing its proper function and maintenance requirements, shall be maintained on file at the building as an attachment to the report required by  Section 909.18.8.3. Devices shall have an approved identifying tag or mark on  them consistent with the other required documentation and shall be dated indicating the last time they were successfully tested and by whom.

    909.19System acceptance. Buildings, or portions thereof, required by this code to comply with this section shall not be issued a certificate of occupancy until  such time that the building official determines that the provisions of this section have been fully complied with and that the fire department has received satisfactory instruction on the operation, both automatic and manual, of the system.

    Exception: In buildings of phased construction, a temporary certificate of  occupancy, as approved by the building official, shall be allowed provided that those portions of the building to be occupied meet the requirements of this sec- tion and that the remainder does not pose a significant hazard to the safety of  the proposed occupants or adjacent buildings.

    909.20Smokeproof enclosures. Where required by Section 1020.1.7, a smokeproof enclosure shall be constructed in accordance with this section. A  smokeproof enclosure shall consist of an enclosed interior exit stairway that conforms to Section 1020.1 and an open exterior balcony or ventilated vestibule meeting the requirements of this section. Where access to the roof is required by  Section 1009.11, such access shall be from the smokeproof enclosure where a smokeproof enclosure is required.

    909.20.1Access. Access to the stair shall be by way of a vestibule or an open exterior balcony. The minimum dimension of the vestibule shall not be less  than the required width of the corridor leading to the vestibule but shall not have a width of less than 44 inches (1118 mm) and shall not have a length of less than 72 inches (1829 mm) in the direction of egress travel.

    909.20.2Construction. The smokeproof enclosure shall be separated from the remainder of the building by not less than a 2-hour fire barrier without openings other than the required means of egress doors. The vestibule shall be separated from the stairway by not less than a 2-hour fire barrier. The open exterior balcony shall be constructed in accordance with the fire-resistance-rating requirements for floor construction.

    909.20.2.1Door closers. Doors in a smokeproof enclosure shall be self- or  automatic closing by actuation of a smoke detector installed at the floor-side entrance to the smokeproof enclosure. The actuation of the smoke detector on

    any door shall activate the closing devices on all doors in the smokeproof  enclosure at all levels. Smoke detectors shall be installed in accordance with Section 907.10.

    909.20.3Natural ventilation alternative. The provisions of Sections  909.20.3.1 through 909.20.3.3 shall apply to ventilation of smokeproof enclosures by natural means.

    909.20.3.1Balcony doors. Where access to the stairway is by way of an open exterior balcony, the door assembly into the enclosure shall be a fire  door assembly in accordance with Section 715.4.

    909.20.3.2Vestibule doors. Where access to the stair-way is by way of a vestibule, the door assembly into the vestibule shall be a fire door complying with Section 715.4. The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protection rating complying with Section 715.4.

    909.20.3.3Vestibule ventilation. Each vestibule shall have a minimum net area of 16 square feet (1.5 m2) of opening in a wall facing an outer court, yard or public way that is at least 20 feet (6096 mm) in width.

    909.20.4Mechanical ventilation alternative. The provisions of Sections  909.20.4.1 through 909.20.4.4 shall apply to ventilation of smokeproof enclosures by mechanical means.

    909.20.4.1Vestibule doors. The door assembly from the building into the vestibule shall be a fire door assembly complying with Section 715.4.3. The  door assembly from the vestibule to the stairway shall not have less than a 20-minute fire protection rating and meet the requirements for a smoke door  assembly in accordance with Section 715.4.3. The door shall be installed in accordance with NFPA 105.

    909.20.4.2Vestibule ventilation. The vestibule shall be supplied with not less  than one air change per minute and the exhaust shall not be less than 150  percent of supply. Supply air shall enter and exhaust air shall discharge from the vestibule through separate, tightly constructed ducts used only for that purpose. Supply air shall enter the vestibule within 6 inches (152 mm) of the floor level. The top of the exhaust register shall be located at the top of the smoke trap but not more than 6 inches (152 mm) down from the top of the trap, and shall be entirely within the smoke trap area. Doors in the open position shall not obstruct duct openings. Duct openings with controlling dampers are permitted where necessary to meet the design requirements, but dampers are not otherwise required.

    909.20.4.2.1 Engineered ventilation system. Where a specially engineered

    system is used, the system shall exhaust a quantity of air equal to not less  than 90 air changes per hour from any vestibule in the emergency operation mode and shall be sized to handle three vestibules simultaneously. Smoke detectors shall be located at the floor-side entrance to each vestibule and shall activate the system for the affected vestibule. Smoke detectors shall be installed in accordance with Section 907.10.

    909.20.4.3Smoke trap. The vestibule ceiling shall be at least 20 inches (508  mm) higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward-moving air column. The height shall not be decreased unless approved and justified by design and test.

    909.20.4.4Stair shaft air movement system. The stair shaft shall be provided with a dampered relief opening and supplied with sufficient air to maintain a minimum positive pressure of 0.10 inch of water (25 Pa) in the shaft relative to the vestibule with all doors closed.

    909.20.5Stair pressurization alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section  903.3.1.1, the vestibule is not required, provided that interior exit stairways are pressurized to a minimum of 0.15 inch of water (37 Pa) and a maximum of 0.35  inch of water (87 Pa) in the shaft relative to the building measured with all stairway doors closed under maximum anticipated stack pressures.

    909.20.6Ventilating equipment. The activation of ventilating equipment required by the alternatives in Sections 909.20.4 and 909.20.5 shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stair shaft and vestibule  doors is activated by smoke detection or power failure, the mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with Section 907.10.

    909.20.6.1Ventilation systems. Smokeproof enclosure ventilation systems  shall be independent of other building ventilation systems. The equipment and ductwork shall comply with one of the following:

    1. Equipment and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by 2-hour fire barriers.

    2. Equipment and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or  through ductwork enclosed by 2-hour fire barriers.

    3. Equipment and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by 2-hour fire barriers.

    909.20.6.2Standby power. Mechanical vestibule and stair shaft ventilation systems and automatic fire detection systems shall be powered by an approved standby power system conforming to Section 403.10.1 and Chapter 27.

    909.20.6.3Acceptance and testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the building official to confirm that the system is operating in compliance with these require- ments.

    SECTION 910 SMOKE AND HEAT VENTS

    910.1General. Where required by this code or otherwise installed, smoke and heat vents, or mechanical smoke exhaust systems, and draft curtains shall conform to the requirements of this section.

    Exceptions:

    1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

    2. Where areas of buildings are equipped with early suppression fast-  response (ESFR) sprinklers, smoke and heat vents shall not be required within these areas.

    910.2Where required. Smoke and heat vents shall be installed in the roofs of  one-story buildings or portions thereof occupied for the uses set forth in Sections 910.2.1 through 910.2.3.

    910.2.1Group F-1 or S-1. Buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 50,000 square feet (4645 m2) in undivided area.

    Exception: Group S-1 aircraft repair hangars.

    910.2.2High-piled combustible storage. Buildings and portions thereof containing high-piled combustible stock or rack storage in any occupancy  group in accordance with Section 413 and the fire code.

    910.2.3Exit access travel distance increase. Buildings and portions thereof  used as a Group F-1 or S-1 occupancy where the maximum exit access travel distance is increased in accordance with Section 1016.2.

    910.3Design and installation. The design and installation of smoke and heat vents and draft curtains shall be as specified in Sections 910.3.1 through 910.3.5.2 and Table 910.3.

    910.3.1Design. Smoke and heat vents shall be listed and labeled to indicate compliance with UL 793.

    910.3.2Vent operation. Smoke and heat vents shall be capable of being operated by approved automatic and manual means. Automatic operation of  smoke and heat vents shall conform to the provisions of Sections 910.3.2.1  through 910.3.2.3.

    910.3.2.1Gravity-operated drop-out vents. Automatic smoke and heat vents containing heat-sensitive glazing designed to shrink and drop out of  the vent opening when exposed to fire shall fully open within 5 minutes after the vent cavity is exposed to a simulated fire, represented by a time-  temperature gradient that reaches an air temperature of 500°F (260°C) within  5 minutes.

    910.3.2.2Sprinklered buildings. Where installed  in  buildings  provided with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically.

    910.3.2.3Nonsprinklered buildings. Where installed in buildings not provided with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100°F (38°C) and 220°F (104°C) above ambient.

    Exception:  Gravity-operated  drop-out  vents  complying  with  Section 910.3.2.1

    910.3.3Vent dimensions. The effective venting area shall not be less than 16 square feet (1.5 m2) with no dimension less than 4 feet (1219 mm), excluding  ribs or gutters having a total width not exceeding 6 inches (152 mm).

    910.3.4Vent locations. Smoke and heat vents shall be located 20 feet (6096  mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or  more from fire barrier walls. Vents shall be uniformly located within the roof  area above high-piled storage areas, with consideration given to roof pitch, draft curtain location, sprinkler location and structural members.

    910.3.5Draft curtains. Where required by Table 910.3, draft curtains shall be provided in accordance with this section.

    Exception: Where areas of buildings are equipped with ESFR sprinklers, draft curtains shall not be provided within these areas. Draft curtains shall only be provided at the separation between the ESFR sprinklers and the conventional sprinklers.

    TABLE 910.3

    REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

     

    OCCUPANCY GROUP AND

    COMMODITY CLASSIFICATION

    DESIGNATED STORAGE HEIGHT

    (feet)

    MINIMUM DRAFT CURTAIN DEPTH

    (feet)

    MAXIMUM AREA FORMED BY DRAFT CURTAINS

    (square feet)

    VENT-AREA- TO-FLOOR- AREA RATIOc

    MAXIMUM SPACING OF VENT CENTERS

    (feet)

    MAXIMUM DISTANCE TO VENTS FROM WALL OR DRAFT

    CURTAINSb

    (feet)

     

    Group F-1 and S-1

     

    -

    0.2 × Hd  but ? 4

     

    50,000

     

    1:100

     

    120

     

    60

    High-piled Storage (see Section 910.2.3) I-IV

    (Option 1)

    ? 20

    6

    10,000

    1:100

    100

    60

     

    > 20 ? 40

     

    6

     

    8,000

     

    1:75

     

    100

     

    55

    High-piled Storage (see Section 910.2.3) I-IV

    (Option 2)

    ? 20

    4

    3,000

    1:75

    100

    55

     

    > 20 ? 40

     

    4

     

    3,000

     

    1:50

     

    100

     

    50

    High-piled Storage (see Section 910.2.3)

    High hazard (Option 1)

    ? 20

    6

    6,000

    1:50

    100

    50

     

    > 20 ? 30

     

    6

     

    6,000

     

    1:40

     

    90

     

    45

    High-piled Storage (see Section 910.2.3)

    High hazard (Option 2)

    ? 20

    4

    4,000

    1:50

    100

    50

     

    > 20 ? 30

     

    4

     

    2,000

     

    1:30

     

    75

     

    40

    For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.

    a.  Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the fire code. For solid-piled storage heights in excess of those indicated, an approved engineered design shall be used.

    b. The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft curtained area.

    c.  Where draft curtains are not required, the vent-area-to-floor-area ratio shall be calculated based on a minimum draft curtain depth of 6 feet (Option 1).

    d. "H" is the height of the vent, in feet, above the floor.

    910.3.5.1Construction. Draft curtains shall be constructed of sheet metal, lath and plaster, gypsum board or other approved materials which provide equivalent performance to resist the passage of smoke. Joints and connections shall be smoke tight.

    910.3.5.2Location and depth. The location and minimum depth of draft curtains shall be in accordance with Table 910.3.

    910.4Mechanical smoke exhaust. Where approved by the building official, engineered mechanical smoke exhaust shall be an acceptable alternate to smoke and heat vents.

    910.4.1Location. Exhaust fans shall be uniformly spaced within each draft- curtained area and the maximum distance between fans shall not be greater than  100 feet (30 480 mm).

    910.4.2Size. Fans shall have a maximum individual capacity of 30,000 cfm

    (14.2 m3/s). The aggregate capacity of smoke exhaust fans shall be determined  by the equation:

    C = A × 300                                     (Equation 9-10)

    where:

    C = Capacity of mechanical ventilation required, in cubic feet per minute (m3/s).

    A = Area of roof vents provided in square feet (m2) in accordance with Table  910.3.

    910.4.3Operation. Mechanical smoke exhaust fans shall be automatically activated by the automatic sprinkler system or by heat detectors having operating characteristics equivalent to those described in Section 910.3.2. Individual manual controls of each fan unit shall also be provided.

    910.4.4Wiring and control. Wiring for operation and control of smoke exhaust  fans shall be connected ahead of the main disconnect and protected  against exposure to temperatures in excess of 1,000°F (538°C) for a period of not less than 15 minutes. Controls shall be located so as to be immediately accessible to the fire service from the exterior of the building and protected against interior fire exposure by fire barriers having a fire-resistance rating not less than 1 hour.

    910.4.5Supply air. Supply air for exhaust fans shall be provided at or near the floor level and shall be sized to provide a minimum of 50 percent of required exhaust. Openings for supply air shall be uniformly distributed around the periphery of the area served.

    910.4.6Interlocks. In combination comfort air-handling/smoke removal systems or independent comfort air-handling systems, fans shall be controlled to shut  down in accordance with the approved smoke control sequence.

    SECTION 911

    FIRE COMMAND CENTER

    911.1Features. Where required by other sections of this code, a fire command center for fire department operations shall be provided. The location and accessibility of the fire command center shall be approved by building official with input from the fire department. The fire command center shall be separated from the remainder of the building by not less than a 1-hour fire barrier constructed in accordance with Section 706 or horizontal assembly constructed in accordance with Section 711, or both. The room shall be a minimum of 96 square feet (9 m2) with a minimum dimension of 8 feet (2438 mm). A layout of the fire command center and all features required by the section to be contained therein

    shall be submitted for approval prior to installation. The fire command center shall comply with NFPA 72 and shall contain the following features:

    1.    The emergency voice/alarm communication system unit.

    2.    The fire department communications unit.

    3.    Fire detection and alarm system annunciator unit.

    4.    Annunciator unit visually indicating the location of the elevators and whether they are operational.

    5.    Status indicators and controls for air-handling systems.

    6.    The  fire-fighter's  control  panel  required  by  Section  909.16  for  smoke control systems installed in the building.

    7.    Controls for unlocking stairway doors simultaneously.

    8.    Sprinkler valve and water-flow detector display panels.

    9.    Emergency and standby power status indicators.

    10.  A telephone for fire department use with controlled access to the public telephone system.

    11.  Fire pump status indicators.

    12.  Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, fire-fighting equipment and fire department access.

    13.  Worktable.

    14.  Generator supervision devices, manual start and transfer features.

    15.  Public address system, where specifically required by other sections of this code.

    SECTION 912

    FIRE DEPARTMENT CONNECTIONS

    912.1Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply with Sections 912.2 through 912.5.

    Exceptions: Fire department connections are not required for: 1.   Limited area sprinkler systems supplied from the domestic water system.

    2. Automatic sprinkler systems having less than 20 sprinklers.

    912.2Location. With respect to hydrants, driveways, buildings and landscaping, fire department connections shall  be so located that fire apparatus and hose  connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be approved by the building official with input from the fire department.

    912.2.1Visible location. Fire department connections shall be located on the

    street side of buildings, fully visible and recognizable from the street or nearest point of fire department vehicle access or as otherwise approved by the building  official.

    912.2.2Existing buildings. On existing buildings, wherever the  fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters  "FDC" at least 6 inches (152 mm) high and words in letters at least 2 inches (51  mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the building official.

    912.3Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or  any other object for a minimum of 3 feet (914 mm).

    912.3.1Locking fire department connection caps. The building official is authorized to require locking caps on fire department connections for water- based fire protection systems where the responding fire department carries appropriate key wrenches for removal.

    912.4Signs. A metal sign with raised letters at least 1 inch (25 mm) in size shall be mounted on all fire department connections serving automatic sprinklers, standpipes or fire pump connections. Such signs shall read: AUTOMATIC  SPRINKLERS, STANDPIPES or TEST CONNECTION, or a combination thereof as applicable.

    912.5Backflow protection. The potable water supply to automatic sprinkler and standpipe systems shall be protected against backflow as required by the  plumbing code.

    Replaces:                                                     4101:1-9-01.5, 4101:1-9-01.6.1, 4101:1-9-01.6.2,

    4101:1-9-01.8, 4101:1-9-02.1, 4101:1-9-03.2.1.3,

    4101:1-9-03.2.7, 4101:1-9-03.2.9, 4101:1-9-03.2.10,

    4101:1-9-03.3.1.2, 4101:1-9-03.3.1.3, 4101:1-9-03.3.5,

    4101:1-9-03.3.7, 4101:1-9-03.3.7.1, 4101:1-9-03.4,

    4101:1-9-03.4.2, 4101:1-9-04.2.1, 4101:1-9-04.3.1,

    4101:1-9-05.3, 4101:1-9-07.2.6, 4101:1-9-07.2.6.1,

    4101:1-9-07.2.6.2, 4101:1-9-07.2.6.3,

    4101:1-9-07.2.6.3.1, 4101:1-9-07.2.6.3.2,

    4101:1-9-07.2.6.3.3, 4101:1-9-07.5, 4101:1-9-07.9,

    4101:1-9-07.9.1, 4101:1-9-07.9.1.1, 4101:1-9-07.9.1.2,

    4101:1-9-07.9.1.3, 4101:1-9-07.9.1.4, 4101:1-9-07.9.2,

    4101:1-9-07.14, 4101:1-9-09.2, 4101:1-9-09.3,

    4101:1-9-09.4.6, 4101:1-9-09.5, 4101:1-9-09.8.1,

    4101:1-9-09.8.3, 4101:1-9-09.8.4, 4101:1-9-09.9,

    4101:1-9-09.10.4, 4101:1-9-09.11, 4101:1-9-09.12.1,

    4101:1-9-09.16.3, 4101:1-9-10.1, 4101:1-9-10.2.2,

    4101:1-9-10.3

    Effective:                                                     07/01/2007

    R.C. 119.032 review dates:                         07/01/2012

    CERTIFIED ELECTRONICALLY

    Certification

    02/02/2007

    Date

    Promulgated Under:                           119.03

    Statutory Authority:                           3781.10(A)

    Rule Amplifies:                                  3781.10, 3781.11, 3791.04

    Prior Effective Dates:                         7/1/79, 1/1/81, 7/1/82, 3/1/85, 7/1/85, 3/1/86, 9/1/86.

    1/1/89, 1/1/90, 8/1/90, 9/1/92, 2/1/93, 7/1/85, 3/1/98,

    1/1/02, 1/1/03, 8/15/03, 1/1/04, 3/1/05, 9/6/05, 3/1/06,

    7/1/06