4101:3-9-01 Vents.  

  • Text Box: ACTION: Final Text Box: DATE: 02/02/2007 1:25 PM

     

     

     

     

     

     

    4101:3-9-01    Vents.

     

    [Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:3-13-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.4 of rule 4101:1-1-01 of the Administrative Code.]

     

    SECTION 901

     GENERAL

    901.1Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems.

    901.2Trap seal protection. The plumbing system shall be provided with  a system of vent piping that will permit the admission or emission of air so that the seal of any fixture trap shall not be subjected to a pneumatic pressure differential of more than 1 inch of water column (249 Pa).

    901.2.1 Venting required. Every trap and trapped fixture shall be vented in accordance with one of the venting methods specified in this chapter.

    901.3Chemical waste vent system. The vent system for a chemical waste system shall be independent of the sanitary vent system and shall terminate separately through the roof to the open air.

    901.4Use limitations. The plumbing vent system shall not be utilized for purposes other than the venting of the plumbing system.

    901.5Tests. The vent system shall be tested in accordance with Section 312.  901.6 Engineered systems. Engineered venting systems shall conform to the provisions of Section 918.

     

    SECTION 902 MATERIALS

    902.1Vents. The materials and methods utilized for the construction and installation of venting systems shall comply with the applicable provisions of Section 702.

    902.2Sheet copper. Sheet copper for vent pipe flashings shall conform to ASTM B 152 and shall weigh not less than 8 ounces per square foot (2.5 kg/m2).

    902.3Sheet lead. Sheet lead for vent pipe flashings shall weigh not less than 3 pounds per square foot (15 kg/m2) for field-constructed flashings and not less than 2.5 pounds per square foot (12 kg/m2) for prefabricated flashings.

     

     

     

     

     

     

     

     

     

    SECTION 903 OUTDOOR VENT EXTENSION

    903.1Required vent extension. The vent system serving each building drain shall have at least one vent pipe that extends to the outdoors through and above the roof.

    903.1.1Installation. The required vent shall be a dry vent that connects to the building drain or an extension of a drain that connects to the building drain. Such vent shall not be an island fixture vent as allowed by Section 913.

    903.1.2Size. The required vent shall be sized in accordance with Section 916.2 based on the required size of the building drain.

    903.2Vent stack required. A vent stack shall be required for every drainage stack that has five branch intervals or more.

    903.3Vent termination. Every vent stack or stack vent shall terminate outdoors to the open air or to a stack-type air admittance valve in accordance with Section 917.

    903.4Vent connection at base. Every vent stack shall connect to the base of the drainage stack. The vent stack shall connect at or below the lowest horizontal branch. Where the vent stack connects to the building drain, the connection shall be located downstream of the drainage stack and within a distance of 10 times the diameter of the drainage stack.

    903.5Vent headers. Stack vents and vent stacks connected into a common vent header at the top of the stacks and extending to the open air at one point shall be sized in accordance with the requirements of Section 916.1. The number of fixture units shall be the sum of all fixture units on all stacks connected thereto, and the developed length shall be the longest vent length from the intersection at the base of the most distant stack to the vent terminal in the open air, as a direct extension of one stack.

    SECTION 904 VENT TERMINALS

    904.1Roof extension. All open vent pipes that extend through a roof shall be terminated at least 12 inches (305 mm) above the roof, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet (2134 mm) above the roof.

    904.2Frost closure. Every vent extension through a roof or wall shall be a

    minimum of 3 inches (76 mm) in diameter. Any increase in the size of the vent shall be made inside the structure a minimum of 1 foot (305 mm) below the roof or inside the wall.

    904.3Flashings. The juncture of each vent pipe with the roof line shall be made water tight by an approved flashing.

    904.4Prohibited use. Vent terminals shall not be used as a flag pole or to support flag poles, television aerials or similar items, except when the piping has been anchored in an approved manner.

    904.5Location of vent terminal. An open vent terminal from a drainage system shall not be located directly beneath any door, openable window, or other air intake opening of the building or of an adjacent building, and any such vent terminal shall not be within 10 feet (3048 mm) horizontally of such an opening unless it is at least 2 feet (610 mm) above the top of such opening.

    904.6Extension through the wall. Vent terminals extending through the wall shall terminate a minimum of 10 feet (3048 mm) from the lot line and 10 feet (3048 mm) above average ground level. Vent terminals shall not terminate under the overhang of a structure with soffit vents. Side wall vent terminals shall be protected to prevent birds or rodents from entering or blocking the vent opening. 904.7 Extension outside a structure. In climates where the 97.5-percent value for outside design temperature is less than 0°F (-18°C), vent pipes installed on the exterior of the structure shall be protected against freezing by insulation, heat or both.

    SECTION 905

    VENT CONNECTIONS AND GRADES

    905.1Connection. All individual, branch and circuit vents shall: 1.      Connect to a vent stack, or

    2.         Connect to a stack vent, or 3.       Extend to the open air, or

    4.         Connect to an air admittance valve in accordance with Section 917.

    905.2Grade. All vent and branch vent pipes shall be so graded and connected as to drain back to the drainage pipe by gravity.

    905.3Vent connection to drainage system. Every dry vent connecting to a horizontal drain shall connect above the centerline of the horizontal drain pipe.

    905.4Vertical rise of vent. Every dry vent shall rise vertically to a minimum of 6 inches (152 mm) above the flood level rim of the highest trap or trapped fixture being vented.

    Exception: Vents for interceptors located outdoors.

    905.5Height above fixtures. A connection between a vent pipe and a vent stack or stack vent shall be made at least 6 inches (152 mm) above the flood level rim of the highest fixture served by the vent. Horizontal vent pipes forming branch vents, relief vents or loop vents shall be at least 6 inches (152 mm) above the flood level rim of the highest fixture served.

    905.6Vent for future fixtures. Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed. The vent size shall be not less than one-half the diameter of the rough-in drain to be served. The vent rough-in shall connect to the vent system, or shall be vented by other means as provided for in this chapter. The connection shall be identified to indicate that it is a vent.

    SECTION 906 FIXTURE VENTS

    906.1Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in Table 906.1.

    Exception: The developed length of the fixture drain from the trap weir to the vent fitting for self-siphoning fixtures, such as water closets, shall not be limited.

    TABLE 906.1

     

    SIZE OF

    TRAP(inches)

     

    SLOPE(inch per foot)

    DISTANCE FROM TRAP

    (feet)

    11/4

    1/4

    5

    1 1/2

    1/4

    6

    2

    1/4

    8

    3

    1/8

    12

    4

    1/8

    16

     

     
    MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT

    For SI:  1 inch = 25.4 mm, 1 foot = 304.8 mm.     1 inch per foot = 83.3 mm/m.

    906.2Venting of fixture drains. The total fall in a fixture drain due to pipe slope shall not exceed the diameter of the fixture drain, nor shall the vent connection to a fixture drain, except for water closets, be below the weir of the trap.

    906.3Crown vent. A vent shall not be installed within two pipe diameters of the trap weir.

    SECTION 907 INDIVIDUAL VENT

    907.1 Individual vent permitted. Each trap and trapped fixture is permitted to

    be provided with an individual vent. The individual vent shall connect to the fixture drain of the trap or trapped fixture being vented.

    SECTION 908 COMMON VENT

    908.1Individual vent as common vent. An individual vent is permitted to vent two traps or trapped fixtures as a common vent. The traps or trapped fixtures being common vented shall be located on the same floor level.

    908.2Connection at the same level. Where the fixture drains being common vented connect at the same level, the vent connection shall be at the interconnection of the fixture drains or downstream of the interconnection.

    908.3Connection at different levels. Where the fixture drains connect at different levels, the vent shall connect as a vertical extension of the vertical drain. The vertical drain pipe connecting the two fixture drains shall be considered the vent for the lower fixture drain, and shall be sized in accordance with Table 908.3. The upper fixture shall not be a water closet.

    TABLE 908.3  COMMON VENT SIZES

    PIPE SIZE

    (inches)

    MAXIMUM DISCHARGE FROM UPPER FIXTURE DRAIN (dfu)

    11/2

    1

    2

    4

    21/2 to 3

    6

    For SI: 1 inch = 25.4 mm.

    SECTION 909 WET VENTING

    909.1Horizontal wet vent permitted. Any combination of fixtures within two bathroom groups located on the same floor level is permitted to be vented by a horizontal wet vent. The wet vent shall be considered the vent for the fixtures and shall extend from the connection of the dry vent along the direction of the flow in the drain pipe to the most downstream fixture drain connection to the horizontal branch drain. Only the fixtures within the bathroom groups shall connect to the wet-vented horizontal branch drain. Any additional fixtures shall discharge downstream of the horizontal wet vent.

    909.1.1 Vertical wet vent permitted. Any combination of fixtures within two bathroom groups located on the same floor level is permitted to be vented by a vertical wet vent. The vertical wet vent shall be considered the vent for the fixtures and shall extend from the connection of the dry vent down to the lowest fixture drain connection. Each wet-vented fixture shall connect independently

    to the vertical wet vent. Water closet drains shall connect at the same elevation. Other fixture drains shall connect above or at the same elevation as the water closet fixture drains. The dry-vent connection to the vertical wet vent shall be an individual or common vent serving one or two fixtures.

    909.2Vent connection. The dry-vent connection to the wet vent shall be an individual vent or common vent to the lavatory, bidet, shower or bathtub. In vertical wet-vent systems, the most upstream fixture drain connection shall be a dry-vented fixture drain connection. In horizontal wet-vent systems, not more than one wet-vented fixture drain shall discharge upstream of the dry-vented fixture drain connection.

    909.3Size. The dry vent serving the wet vent shall be sized based on the largest required diameter of pipe within the wet-vent system served by the dry vent. The wet vent shall be of a minimum size as specified in Table 909.3, based on the fixture unit discharge to the wet vent.

    TABLE 909.3 WET VENT SIZE

    WET VENT PIPE SIZE

    (inches)

    DRAINAGE FIXTURE UNIT LOAD

    11/2

    1

    2

    4

    21/2

    6

    3

    12

    For SI: 1 inch = 25.4 mm.

    SECTION 910 WASTE STACK VENT

    910.1Waste stack vent permitted. A waste stack shall be considered a vent for all of the fixtures discharging to the stack where installed in accordance with the requirements of this section.

    910.2Stack installation. The waste stack shall be vertical, and both horizontal and vertical offsets shall be prohibited between the lowest fixture drain connection and the highest fixture drain connection. Every fixture drain shall connect separately to the waste stack. The stack shall not receive the discharge of water closets or urinals.

    910.3Stack vent. A stack vent shall be provided for the waste stack. The size of the stack vent shall be not less than the size of the waste stack. Offsets shall be permitted in the stack vent, shall be located at least 6 inches (152 mm) above the

    flood level of the highest fixture and shall be in accordance with Section 905.2. The stack vent shall be permitted to connect with other stack vents and vent stacks in accordance with Section 903.5.

    910.4Waste stack size. The waste stack shall be sized based on the total discharge to the stack and the discharge within a branch interval in accordance with Table 910.4. The waste stack shall be the same size throughout its length.

    TABLE 910.4 WASTE STACK VENT SIZE

     

     

    STACK SIZE

    (inches)

    MAXIMUM NUMBER OF DRAINAGE FIXTURE

    UNITS (dfu)

    Total discharge into one branch interval

    Total discharge for stack

    11/2

    1

    2

    2

    2

    4

    21/2

    No limit

    8

    3

    No limit

    24

    4

    No limit

    50

    5

    No limit

    75

    6

    No limit

    100

    For SI: 1 inch = 25.4 mm.

    SECTION 911 CIRCUIT VENTING

    911.1Circuit vent permitted. A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect horizontally to the horizontal branch being circuit vented. The horizontal branch drain shall be classified as a vent from the most downstream fixture drain connection to the most upstream fixture drain connection to the horizontal branch.

    911.1.1Multiple circuit-vented branches. Circuit-vented horizontal branch drains are permitted to be connected together. Each group of a maximum of eight fixtures shall be considered a separate circuit vent and shall conform to the requirements of this section.

    911.2Vent connection. The circuit vent connection shall be located between the two most upstream fixture drains. The vent shall connect to the horizontal branch and shall be installed in accordance with Section 905. The circuit vent pipe shall not receive the discharge of any soil or waste.

    911.3Slope and size of horizontal branch. The maximum slope of the vent section  of  the  horizontal  branch  drain  shall  be  one  unit  vertical  in  12  units

    horizontal (8-percent slope). The entire length of the vent section of the horizontal branch drain shall be sized for the total drainage discharge to the branch.

    911.3.1Size of multiple circuit vent. Each separate circuit-vented horizontal branch that is interconnected shall be sized independently in accordance with Section 911.3. The downstream circuit-vented horizontal branch shall be sized for the total discharge into the branch, including the upstream branches and the fixtures within the branch.

    911.4Relief vent. A relief vent shall be provided for circuit-vented horizontal branches receiving the discharge of four or more water closets and connecting to a drainage stack that receives the discharge of soil or waste from upper horizontal branches.

    911.4.1Connection and installation. The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain of the circuit vent. The relief vent shall be installed in accordance with Section 905.

    911.4.2Fixture drain or branch. The relief vent is permitted to be a fixture drain or fixture branch for fixtures located within the same branch interval as the circuit-vented horizontal branch. The maximum discharge to a relief vent shall be four fixture units.

    911.5Additional fixtures. Fixtures, other than the circuit-vented fixtures, are permitted to discharge to the horizontal branch drain. Such fixtures shall be located on the same floor as the circuit-vented fixtures and shall be either individually or common vented.

    SECTION 912 COMBINATION DRAIN AND VENT SYSTEM

    912.1Type of fixtures. A combination drain and vent system shall not serve fixtures other than floor drains, sinks, lavatories and drinking fountains. Combination drain and vent systems shall not receive the discharge from a food waste grinder or clinical sink.

    912.2Installation. The only vertical pipe of a combination drain and vent system shall be the connection between the fixture drain and the horizontal combination drain and vent pipe. The maximum vertical distance shall be 8 feet (2438 mm).

    912.2.1Slope. The horizontal combination drain and vent pipe shall have a maximum slope of one-half unit vertical in 12 units horizontal  (4-percent slope). The minimum slope shall be in accordance with Table 704.1.

    912.2.2Connection. The combination drain and vent system shall be provided with a dry vent connected at any point within the system or the system shall

    connect to a horizontal drain that is vented in accordance with one of the venting methods specified in this chapter. Combination drain and vent systems connecting to building drains receiving the discharge from a stack or stacks shall be provided with a dry vent. The vent connection to the combination drain and vent pipe shall extend vertically a minimum of 6 inches (152 mm) above the flood level rim of the highest fixture being vented before offsetting horizontally.

    912.2.3Vent size. The vent shall be sized for the total drainage fixture unit load in accordance with Section 916.2.

    912.2.4Fixture branch or drain. The fixture branch or fixture drain shall connect to the combination drain and vent within a distance specified in Table 906.1. The combination drain and vent pipe shall be considered the vent for the fixture.

    912.3Size. The minimum size of a combination drain and vent pipe shall be in accordance with Table 912.3.

    TABLE 912.3

     

    DIAMETER PIPE

    (inches)

    MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS

    Connecting to a horizontal branch or stack

    Connecting to a building drain or building subdrain

    2

    3

    4

    21/2

    6

    26

    3

    12

    31

    4

    20

    50

    5

    160

    250

    6

    360

    575

     

     
    SIZE OF COMBINATION DRAIN AND VENT PIPE

    For SI: 1 inch = 25.4 mm.

    SECTION 913 ISLAND FIXTURE VENTING

    913.1Limitation. Island fixture venting shall not be permitted for fixtures other than sinks and lavatories. Residential kitchen sinks with a dishwasher waste connection, a food waste grinder, or both, in combination with the kitchen sink waste, shall be permitted to be vented in accordance with this section.

    913.2Vent connection. The island fixture vent shall connect to the fixture drain as required for an individual or common vent. The vent shall rise vertically to above the drainage outlet of the fixture being vented before offsetting horizontally

    or vertically downward. The vent or branch vent for multiple island fixture vents shall extend to a minimum of 6 inches (152 mm) above the highest island fixture being vented before connecting to the outside vent terminal.

    913.3Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 916.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout.

    SECTION 914

    RELIEF VENTS-STACKS OF MORE THAN 10 BRANCH INTERVALS

    914.1Where required. Soil and waste stacks in buildings having more than 10 branch intervals shall be provided with a relief vent at each tenth interval installed, beginning with the top floor.

    914.2Size and connection. The size of the relief vent shall be equal to the size of the vent stack to which it connects. The lower end of each relief vent shall connect to the soil or waste stack through a wye below the horizontal branch serving the floor, and the upper end shall connect to the vent stack through a wye not less than 3 feet (914 mm) above the floor.

    SECTION 915

    VENTS FOR STACK OFFSETS

    915.1Vent for horizontal offset of drainage stack. Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented by venting the upper section of the drainage stack and the lower section of the drainage stack.

    915.2Upper section. The upper section of the drainage stack shall be vented as a separate stack with a vent stack connection installed in accordance with Section 903.4. The offset shall be considered the base of the stack.

    915.3Lower section. The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke vent connection shall be permitted to be a vertical extension of the drainage stack. The size of the yoke vent and connection shall be a minimum of the size required for the vent stack of the drainage stack.

    SECTION 916 VENT PIPE SIZING

    916.1Size of stack vents and vent stacks. The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 916.1, but in no case shall the diameter be less than one-half the diameter of the drain served or less than inches (32 mm).

    916.2Vents other than stack vents or vent stacks. The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 710.1(2). Vent pipes shall not be less than inches (32 mm) in diameter. Vents exceeding 40 feet (12 192 mm) in developed length shall be increased by one nominal pipe size for the entire developed length of the vent pipe. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 914.2.

    916.3Developed length. The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.

    TABLE 916.1

     

     

    DIAMETER OF SOIL ORWASTE STACK

    (inches)

     

    TOTAL FIXTURE UNITS BEING

    VENTED (dfu)

    MAXIMUM DEVELOPED LENGTH OF VENT (feet)a

    DIAMETER OF VENT (inches)

    11/4

    11/2

    2

    21/2

    3

    4

    5

    6

    8

    10

    12

    1-1/4

    2

    30

     

    150

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

    1-1/2

    8

    50

    1-1/2

    10

    30

    100

    2

    2

    12

    20

    30

    26

    75

    50

    200

    150

     

     

    300

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

    2-1/2

    42

    30

    100

    3

    10

     

    -

    42

    150

    360

    1,040

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

    3

    21

    32

    110

    270

    810

    3

    53

    27

    94

    230

    680

    3

    102

     

    -

    25

    86

    210

    620

     

    980

     

    -

     

    -

     

    -

     

    -

     

    -

    4

    43

    35

    85

    250

    4

    140

    27

    65

    200

    750

    4

    320

     

    -

     

    -

    23

    55

    170

    640

     

    990

     

    -

     

    -

     

    -

     

    -

    4

    540

    21

    50

    150

    580

    5

    190

    28

    82

    320

    5

    490

     

    -

     

    -

     

    -

    21

    63

    250

    760

     

    -

     

    -

     

    -

     

    -

    5

    940

    18

    53

    210

    670

    5

    1,400

    16

    49

    190

    590

     

     
    SIZE AND DEVELOPED LENGTH OF STACK VENTS AND VENT STACKS

                                                                                                    

    6

    500

     

    -

     

    -

     

    -

     

    -

    33

    130

    400

    1,000

     

    -

     

    -

     

    -

    6

    1,100

    26

    100

    310

    780

    6

    2,000

    22

    84

    260

    660

    6

    2,900

     

    -

     

    -

     

    -

     

    -

    20

    77

    240

    600

     

    940

     

    -

     

    -

    8

    1,800

    31

    95

    240

    8

    3,400

    24

    73

    190

    720

    8

    5,600

     

    -

     

    -

     

    -

     

    -

     

    -

    20

    62

    160

    610

     

     

    960

     

    -

    8

    7,600

    18

    56

    140

    560

    10

    4,000

    31

    78

    310

    10

    7,200

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

    24

    60

    240

    740

     

    -

    10

    11,000

    20

    51

    200

    630

    10

    15,000

    18

    46

    180

    570

    12

    7,300

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

    31

    120

    380

    940

    12

    13,000

    24

    94

    300

    720

    12

    20,000

    20

    79

    250

    610

    12

    26,000

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    -

     

    18

    72

    230

    500

    15

    15,000

    40

    130

    310

    15

    25,000

    31

    96

    240

    15

    15

    38,000

    50,000

    -

    -

    -

    -

    -

    -

    -

    -

    26

    24

    81

    74

    200

    180

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

    a. The developed length shall be measured from the vent connection to the open air.

    916.4Multiple branch vents. Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit (dfu) load being vented.

    916.4.1Branch vents exceeding 40 feet in developed length. Branch vents exceeding 40 feet (12 192 mm) in developed length shall be increased by one nominal size for the entire developed length of the vent pipe.

    916.5Sump vents. Sump vent sizes shall be determined in accordance with Sections 916.5.1 and 916.5.2.

    916.5.1Sewage pumps and sewage ejectors other than pneumatic. Drainage piping below sewer level shall be vented in a similar manner to that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 916.5.1.

    916.5.2Pneumatic sewage ejectors. The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure, but shall not be less than 11/4 inches (32 mm) in size.

    SECTION 917

    AIR ADMITTANCE VALVES

    917.1General. Vent systems utilizing air admittance valves shall comply with this  section.  Stack-type  air  admittance  valves  shall  conform  to  ASSE  1050.

    Individual and branch-type air admittance valves shall conform to ASSE 1051.

    917.2Installation. The valves shall be installed in accordance with the requirements of this section and the manufacturer's installation instructions. Air admittance valves shall be installed after the DWV testing required by Section 312.2 or 312.3 has been performed.

    917.3Where permitted. Individual, branch and circuit vents shall be permitted to terminate with a connection to an individual or branch-type air admittance valve. Stack vents and vent stacks shall be permitted to terminate to stack-type air admittance valves. Individual and branch-type air admittance valves shall vent only fixtures that are on the same floor level and connect to a horizontal branch drain. The horizontal branch drain having individual and branch-type air admittance valves shall conform to Section 917.3.1 or 917.3.2. Stack-type air admittance valves shall conform to Section 917.3.3.

    917.3.1Location of branch. The horizontal branch drain shall connect to the drainage stack or building drain a maximum of four branch intervals from the top of the stack.

    917.3.2Relief vent. Where the horizontal branch is located more than four branch intervals from the top of the stack, the horizontal branch shall be provided with a relief vent that shall connect to a vent stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in accordance with Section 916.2 and installed in accordance with Section 905. The relief vent shall be permitted to serve as the vent for other fixtures.

    917.3.3Stack. Stack-type air admittance valves shall not serve as the vent terminal for vent stacks or stack vents that serve drainage stacks exceeding six branch intervals.

    917.4Location. Individual and branch-type air admittance valves shall be located a minimum of 4 inches (102 mm) above the horizontal branch drain or fixture drain being vented. Stack-type air admittance valves shall be located not less than 6 inches (152 mm) above the flood level rim of the highest fixture being vented. The air admittance valve shall be located within the maximum developed length permitted for the vent. The air admittance valve shall be installed a minimum of 6 inches (152 mm) above insulation materials.

    917.5Access and ventilation. Access shall be provided to all air admittance valves. The valve shall be located within a ventilated space that allows air to enter the valve.

    917.6Size. The air admittance valve shall be rated in accordance with  the standard for the size of the vent to which the valve is connected.

    917.7Vent required. Within each plumbing system, a minimum of one stack vent or vent stack shall extend outdoors to the open air.

    917.8Prohibited installations. Air admittance valves shall not be installed in nonneutralized special waste systems as described in Chapter 8. Valves shall not be located in spaces utilized as supply or return air plenums or where limited by the manufacturer's installation instructions.

    SECTION 918 ENGINEERED VENT SYSTEMS

    918.1General. Engineered vent systems shall comply with this section and the design, submittal, approval, inspection and testing requirements of Section 106.7 of the building code.

    918.2Individual branch fixture and individual fixture header vents. The maximum developed length of individual fixture vents to vent branches and vent headers shall be determined in accordance with Table 918.2 for the minimum pipe diameters at the indicated vent airflow rates.

    The individual vent airflow rate shall be determined in accordance with the following:

    Qh,b = Nn,b Qv                                                     (Equation 9-1) For SI: Qh,b = Nn,b Qv (0.4719 L/s)

    where:

    Nn,b  = Number of fixtures per header (or vent branch) ÷ total number of fixtures connected to vent stack.

    Qh,b           = Vent branch or vent header airflow rate (cfm). Qv           = Total vent stack airflow rate (cfm).

    Qv (gpm) = 27.8 rs 2/3 (1 - rs) D8/3 Qv (cfm) = 0.134 Qv (gpm)

    where:

    D = Drainage stack diameter (inches). Qw = Design discharge load (gpm).

    rs = Waste water flow area to total area.

    =  (Q w)/(27. 8 D 8/3)

    Individual vent airflow rates are obtained by equally distributing Qh,b into one- half the total number of fixtures on the branch or header for more than two

    fixtures; for an odd number of total fixtures, decrease by one; for one fixture, apply the full value of Qh,b.

    Individual vent developed length shall be increased by 20 percent of the distance from the vent stack to the fixture vent connection on the vent branch or header.

    SECTION 919 COMPUTERIZED VENT DESIGN

    919.1Design of vent system. The sizing, design and layout of the vent system shall be permitted to be determined by approved computer program design methods.

    919.2System capacity. The vent system shall be based on the air capacity requirements of the drainage system under a peak load condition.

    TABLE 916.5.1

    SIZE AND LENGTH OF SUMP VENTS

    DISCHARGE CAPACITY OF PUMP

    (gpm)

    MAXIMUM DEVELOPED LENGTH OF VENT (feet)a

     

     

    Diameter of vent (inches)

     

     

    11/4

    11/2

    2

    21/2

    3

    4

    10

    No limitb

    No limit

    No limit

    No limit

    No limit

    No limit

    20

    270

    No limit

    No limit

    No limit

    No limit

    No limit

    40

    72

    160

    No limit

    No limit

    No limit

    No limit

    60

    31

    75

    270

    No limit

    No limit

    No limit

    80

    16

    41

    150

    380

    No limit

    No limit

    100

    10c

    25

    97

    250

    No limit

    No limit

    150

    Not permitted

    10c

    44

    110

    370

    No limit

    200

    Not permitted

    Not permitted

    20

    60

    210

    No limit

    250

    Not permitted

    Not permitted

    10

    36

    132

    No limit

    300

    Not permitted

    Not permitted

    10c

    22

    88

    380

    400

    Not permitted

    Not permitted

    Not permitted

    10c

    44

    210

    500

    Not permitted

    Not permitted

    Not permitted

    Not permitted

    24

    130

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.

    a.    Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances shall be obtained from NSB Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.

    b.   Actual values greater than 500 feet.

    c.    Less than 10 feet.

    TABLE 918.2

    MINIMUM DIAMETER AND MAXIMUM LENGTH OF INDIVIDUAL BRANCH FIXTURE VENTS AND INDIVIDUAL FIXTURE HEADER VENTS FOR SMOOTH

    PIPES

     

    DIAMETER OF VENT PIPE

    (inches)

    INDIVIDUAL VENT AIRFLOW RATE (cubic feet per minute)

    Maximum developed length of vent (feet)

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    1/2

    95

    25

    13

    8

    5

    4

    3

    2

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    3/4

    100

    88

    47

    30

    20

    15

    10

    9

    7

    6

    5

    4

    3

    3

    3

    2

    2

    2

    2

    1

    1

    -

    -

    100

    94

    65

    48

    37

    29

    24

    20

    17

    14

    12

    11

    9

    8

    7

    7

    6

    6

    11/4

    -

    -

    -

    -

    -

    -

    -

    100

    87

    73

    62

    53

    46

    40

    36

    32

    29

    26

    23

    21

    11/2

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    100

    96

    84

    75

    65

    60

    54

    49

    45

    2

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    100

    For SI: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.4719 L/s, 1 foot = 304.8 mm.

    Replaces:                                                     4101:3-9-03.1, 4101:3-9-04.1, 4101:3-9-04.2,

    4101:3-9-05.1, 4101:3-9-12.2.2, 4101:3-9-17.8,

    4101:3-9-18.1

    Effective:                                                     07/01/2007

    R.C. 119.032 review dates:                         07/01/2012

    CERTIFIED ELECTRONICALLY

    Certification

    02/02/2007

    Date

    Promulgated Under:                           119.03

    Statutory Authority:                           3781.10(A)

    Rule Amplifies:                                  3781.10, 3781.11, 3791.04