4101:2-5-01 Exhaust systems.  

  • Text Box: ACTION: Final Text Box: DATE: 04/18/2011 11:45 AM

     

     

     

     

     

     

    4101:2-5-01 Exhaust systems.

     

    [Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:2-15-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:1-1-01 of the Administrative Code.]

     

    SECTION 501 GENERAL

     

    501.1Scope. This chapter shall govern the design, construction and installation of  mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502.

     

    501.2Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not  less than the distances specified in Section 501.2.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic or crawl space.

    Exceptions:

    1.      Whole-house ventilation-type attic fans shall be permitted to discharge into the attic space of dwelling units having private attics.

    2.      Commercial cooking recirculating systems.

     

    501.2.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following  minimum distances:

    1.      For ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet  (9144 mm) from property lines; 10 feet (3048 mm) from operable openings into buildings; 6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144  mm) from combustible walls and operable openings into buildings which are in the direction of the exhaust discharge; 10 feet (3048 mm) above adjoining grade.

    2.      For other product-conveying outlets: 10 feet (3048 mm) from the property lines; 3 feet (914 mm) from exterior walls and roofs; 10 feet (3048 mm) from

     

     

     

     

     

     

     

     

    operable openings into buildings; 10 feet (3048 mm) above adjoining grade.

    3.      For all environmental air exhaust: 3 feet (914 mm) from property lines; 3 feet  (914 mm) from operable openings into buildings for all occupancies other than Group U, and 10 feet (3048 mm) from mechanical air intakes. Such  exhaust shall not be considered hazardous or noxious.

    4.      Exhaust outlets serving structures in flood hazard areas shall be installed at or  above the design flood level.

    5.      For specific systems see the following sections:  5.1. Clothes dryer exhaust, Section 504.4.

    5.2.Kitchen hoods and other kitchen exhaust equipment, Sections 506.3.12, 506.4 and 506.5.

    5.3.Dust stock and refuse conveying systems, Section 511. 5.4. Subslab soil exhaust systems, Section 512.4

    5.5. Smoke control systems, Section 513.10.3 5.6. Refrigerant discharge, Section 1105.7

    5.7. Machinery room discharge, Section 1105.6.1

    501.2.1.1  Exhaust  discharge.  Exhaust  air  shall  not  be  directed  onto walkways.

    501.2.2  Exhaust  opening  protection.  Exhaust  openings  that  terminate  outdoors shall be protected with corrosion-resistant screens, louvers or grilles.

    1

    Openings in screens, louvers and grilles shall be sized not less than

    1

    /4 inch (6

    mm) and not larger than

    /2 inch (13 mm). Openings shall be protected against

    local weather conditions. Outdoor openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with the  building code.

    501.3Pressure equalization. Mechanical exhaust systems shall be sized to remove the quantity of air required by this chapter to be exhausted. The system shall operate when air is required to be exhausted. Where mechanical exhaust is required in a room or space in other than occupancies in R-3 and dwelling units in  R-2, such space shall be maintained with a neutral or negative pressure. If a greater quantity of air is supplied by a mechanical ventilating supply system than  is removed by a mechanical exhaust for a room, adequate means shall be provided  for the natural or mechanical exhaust of the excess air supplied. If only a mechanical exhaust system is installed for a room or if a greater quantity of air is removed by a mechanical exhaust system than is supplied by a mechanical ventilating supply system for a room, adequate makeup air consisting of supply air, transfer air or outdoor air shall be provided to satisfy the deficiency. The calculated building infiltration rate shall not be used to satisfy the requirements of

    this section.

    501.4Ducts. Where exhaust duct construction is not specified in this chapter,  such construction shall comply with Chapter 6.

    SECTION 502 REQUIRED SYSTEMS

    502.1General. An exhaust system shall be provided, maintained and operated as  specifically required by this section and for all occupied areas where machines, vats, tanks, furnaces, forges, salamanders and other appliances, equipment and  processes in such areas produce or throw off dust or particles sufficiently light to float in the air, or which emit heat, odors, fumes, spray, gas or smoke, in such  quantities so as to be irritating or injurious to health or safety.

    502.1.1Exhaust location. The inlet to an exhaust system shall be located in the area of heaviest concentration of contaminants.

    502.1.2Fuel-dispensing areas. The bottom of an air inlet or exhaust opening in fuel-dispensing areas shall be located not more than 18 inches (457 mm)  above the floor.

    502.1.3Equipment, appliance and service rooms. Equipment, appliance and system service rooms that house sources of odors, fumes, noxious gases,  smoke, steam, dust, spray or other contaminants shall be designed and con- structed so as to prevent spreading of such contaminants to other occupied parts  of the building.

    502.1.4Hazardous exhaust. The mechanical exhaust of high concentrations of  dust or hazardous vapors shall conform to the requirements of Section 510.

    502.2Aircraft fueling and defueling. Compartments housing piping, pumps, air eliminators, water separators, hose reels and similar equipment used in aircraft fueling and defueling operations shall be adequately ventilated at floor level or  within the floor itself.

    502.3Battery-charging areas for powered industrial trucks and equipment.  Ventilation shall be provided in an approved manner in battery-charging areas for  powered industrial trucks and equipment to prevent a dangerous accumulation of  flammable gases.

    502.4Stationary storage battery systems. Stationary storage battery systems, as  regulated by Section 608 of the fire code, shall be provided with ventilation in accordance with this chapter and Section 502.4.1 or 502.4.2.

    Exception: Lithium-ion batteries shall not require ventilation.

    502.4.1Hydrogen  limit  in  rooms.  For  flooded  lead  acid,  flooded  nickel

    cadmium and VRLA batteries, the ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room.

    502.4.2Ventilation rate in rooms. Continuous ventilation shall be provided at a

    2

    rate of not less than 1 cubic foot per minute per square foot (cfm/ft ) [0.00508

    3              2

    m /(s m )] of floor area of the room.

    502.5Valve-regulated lead-acid batteries in cabinets.

    Valve-regulated lead-acid (VRLA) batteries installed in cabinets, as regulated by  Section 608.6.2 of the fire code, shall be provided with ventilation in accordance with Section 502.5.1 or 502.5.2.

    502.5.1Hydrogen limit in cabinets. The cabinet ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the cabinet during the worst-case event of simultaneous boost charging of all batteries in the cabinet.

    502.5.2Ventilation rate in cabinets. Continuous cabinet ventilation shall be

    2

    provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft )

    3               2

    [0.00508 m /(s m )] of the floor area covered by the cabinet. The room in which

    the cabinet is installed shall also be ventilated as required by Section 502.4.1 or 502.4.2.

    502.6Dry cleaning plants. Ventilation in dry cleaning plants shall be adequate to protect employees and the public in accordance with this section and DOL 29 CFR Part 1910.1000, where applicable.

    502.6.1Type II systems. Type II dry cleaning systems shall be provided with a mechanical ventilation system that is designed to exhaust 1 cubic foot of air per

    2                            3               2

    minute for each square foot of floor area (1 cfm/ft ) [0.00508 m /(s m )] in dry

    cleaning rooms and in drying rooms. The ventilation system shall operate automatically when the dry cleaning equipment is in operation and shall have manual controls at an approved location.

    502.6.2Type IV and V systems. Type IV and V dry cleaning systems shall be provided with an automatically activated exhaust ventilation system to maintain a minimum of 100 feet per minute (0.51 m/s) air velocity through the loading door when the door is opened.

    Exception: Dry cleaning units are not required to be provided with exhaust ventilation where an exhaust hood is installed immediately outside of and above the loading door which operates at an airflow rate as follows:

    Q = 100 ×ALD                                        (Equation 5-1)

    where:

    Q  Flow rate exhausted through the hood, cubic feet per minute.

    ALD =Area of the loading door, square feet.

    502.6.3Spotting and pretreating. Scrubbing tubs, scouring, brushing or  spotting operations shall be located such that solvent vapors are captured and exhausted by the ventilating system.

    502.7Application of flammable finishes. Mechanical exhaust as required by this section and the fire code shall be provided for operations involving the application of flammable finishes.

    502.7.1During construction. Ventilation shall be provided for operations involving the application of materials containing flammable solvents in the course  of construction, alteration or demolition of a structure.

    502.7.2Limited spraying spaces. Positive  mechanical  ventilation  which provides a minimum of six complete air changes per hour shall be installed in limited spraying spaces. Such system shall meet the requirements of the fire code  for handling flammable vapors. Explosion venting is not required.

    502.7.3Flammable vapor areas. Mechanical ventilation of flammable vapor areas shall be provided in accordance with Sections 502.7.3.1 through 502.7.3.6.

    502.7.3.1Operation. Mechanical ventilation shall be kept in operation at all times while spraying operations are being conducted and for a sufficient time thereafter to allow vapors from drying coated articles and finishing material residue to be exhausted. Spraying equipment shall be interlocked with the ventilation of the flammable vapor area such that spraying operations cannot be conducted unless the ventilation system is in operation.

    502.7.3.2Recirculation. Air exhausted from spraying operations shall not be recirculated.

    Exceptions:

    1.Air exhausted from spraying operations shall be permitted to be recirculated  as makeup air for unmanned spray operations provided that:

    1.1.The solid particulate has been removed.

    1.2.The vapor concentration is less than 25 percent of the lower flammable limit (LFL).

    1.3.Approved equipment is used to monitor the vapor concentration.

    1.4.An alarm is sounded and spray operations are automatically shut  down if the vapor concentration exceeds 25 percent of the LFL.

    1.5.In the event of shutdown of the vapor concentration monitor, 100  percent of the air volume specified in Section 510 is automatically exhausted.

    2.Air exhausted from spraying operations is allowed to be recirculated as  makeup air to manned spraying operations where all of the conditions provided

    in Exception 1 are included in the installation and documents have been prepared to show that the installation does not pose a life safety hazard to personnel inside the spray booth, spraying space or spray room.

    502.7.3.3Air velocity. Ventilation systems shall be designed, installed and maintained such that the average air velocity over the open face of the booth, or  booth cross section in the direction of airflow during spraying operations, is not  less than 100 feet per minute (0.51 m/s).

    502.7.3.4Ventilation obstruction. Articles being sprayed shall be positioned in a manner that does not obstruct collection of overspray.

    502.7.3.5Independent ducts. Each spray booth and spray room shall have an independent exhaust duct system discharging to the outdoors.

    Exceptions:

    1.      Multiple spray booths having a combined frontal area of 18 square feet (1.67

    2

    m ) or less are allowed to have a common exhaust where identical spray-

    finishing material is used in each booth. If more than one fan serves one booth, such fans shall be interconnected so that all fans operate simultaneously.

    2.      Where treatment of exhaust is necessary for air pollution control or energy conservation, ducts shall be allowed to be manifolded if all of the following conditions are met:

    2.1.The sprayed materials used are compatible and will not react or cause ignition of the residue in the ducts.

    2.2.Nitrocellulose-based finishing material shall not be used.

    2.3.A filtering system shall be provided to reduce the amount of overspray carried into the duct manifold.

    2.4.Automatic sprinkler protection shall be provided at the junction of each booth exhaust with the manifold, in addition to the protection required by  this chapter.

    502.7.3.6Fan motors and belts. Electric motors driving exhaust fans shall not be placed inside booths or ducts. Fan rotating elements shall be nonferrous or  nonsparking or the casing shall consist of, or be lined with, such material. Belts shall not enter the duct or booth unless the belt and pulley within the duct are tightly enclosed.

    502.7.4 Dipping operations. Flammable vapor areas of dip tank operations shall be provided with mechanical ventilation adequate to prevent the dangerous  accumulation of vapors. Required ventilation systems shall be so arranged that the failure of any ventilating fan will automatically stop the dipping conveyor system.  502.7.5 Electrostatic apparatus. The flammable vapor area in spray-finishing

    operations involving electrostatic apparatus and devices shall be ventilated in accordance with Section 502.7.3.

    502.7.6Powder coating. Exhaust ventilation for powder-coating operations shall be sufficient to maintain the atmosphere below one-half of the minimum explosive concentration for the material being applied. Nondeposited, air-  suspended powders shall be removed through exhaust ducts to the powder  recovery system.

    502.7.7Floor resurfacing operations. To prevent the accumulation  of  flammable vapors during floor resurfacing operations, mechanical ventilation at a

    2                           3               2

    minimum rate of 1 cfm/ft  [0.00508 m /(s m )] of area being finished shall be

    provided.  Such  exhaust  shall  be  by  approved  temporary  or  portable  means.  Vapors shall be exhausted to the exterior of the building.

    502.8Hazardous materials-general requirements.

    Exhaust ventilation systems for structures containing hazardous materials shall be provided as required in Sections 502.8.1 through 502.8.5.

    502.8.1Storage in excess of the maximum allowable quantities. Indoor  storage areas and storage buildings for hazardous materials in amounts exceeding the maximum allowable quantity per control area shall be provided with mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be acceptable for the materials as stored.

    Exception: Storage  areas for  flammable  solids  complying with  Section  3604 of the fire code.

    502.8.1.1 System requirements. Exhaust ventilation systems shall  comply with all of the following:

    1.      The installation shall be in accordance with this code.

    2.      Mechanical ventilation shall be provided at a rate of not less than 1 cfm per

    3              2

    square foot [0.00508 m /(s m )] of floor area over the storage area.

    3.      The systems shall operate continuously unless alternate designs are approved.

    4.      A manual shutoff control shall be provided outside of the room in a position  adjacent to the access door to the room or in another approved location. The switch shall be a break-glass or other approved type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.

    5.      The exhaust ventilation shall be designed to consider the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor. For fumes or vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (305 mm) of the highest point of the room.

    6.      The location of both the exhaust and inlet air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of vapors.

    7.      The exhaust air shall not be recirculated to occupied areas if the materials stored are capable of emitting hazardous vapors and contaminants have not been removed. Air contaminated with explosive or flammable vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radioactive materials shall not be recirculated.

    502.8.2Gas rooms, exhausted enclosures and gas cabinets. The ventilation system for gas rooms, exhausted enclosures and gas cabinets for any quantity of  hazardous material shall be designed to operate at a negative pressure in relation to the surrounding area. Highly toxic and toxic gases shall also comply with Sections 502.9.7.1, 502.9.7.2 and 502.9.8.4.

    502.8.3Indoor dispensing and use. Indoor dispensing and use areas for hazardous materials in amounts exceeding the maximum allowable quantity per control area shall be provided with exhaust ventilation in accordance with Section  502.8.1.

    Exception: Ventilation is not required for dispensing and use of flammable solids other than finely divided particles.

    502.8.4Indoor dispensing and use-point sources.

    Where gases, liquids or solids in amounts exceeding the maximum allowable quantity per control area and having a hazard ranking of 3 or 4 in accordance with  NFPA 704 are dispensed or used, mechanical exhaust ventilation shall be provided to capture gases, fumes, mists or vapors at the point of generation.

    Exception: Where it can be demonstrated that the gases, liquids or solids do  not create harmful gases, fumes, mists or vapors.

    502.8.5Closed systems. Where closed systems for the use of hazardous materials in amounts exceeding the maximum allowable quantity per control area are designed to be opened as part of normal operations, ventilation shall be provided in accordance with Section 502.8.4.

    502.9Hazardous materials-requirements for specific materials. Exhaust ventilation systems for specific hazardous materials shall be provided as required in Section 502.8 and Sections 502.9.1 through 502.9.11.

    502.9.1Compressed gases-medical gas systems.

    Rooms for the storage of compressed medical gases in amounts exceeding the maximum allowable exempt quantity per control area, and which do not have an exterior wall, shall be exhausted through a duct to the exterior of the build- ing. Both separate airstreams shall be enclosed in a 1-hour-rated shaft enclosure from  the  room  to  the  exterior.  Approved  mechanical  ventilation  shall  be

    2                          3              2

    provided at a minimum rate of 1 cfm/ft  [0.00508 m /(s • m )] of the area of the

    room.

    Gas  cabinets  for  the  storage  of  compressed  medical  gases  in  amounts

    exceeding the maximum allowable quantity per control area shall be connected to an exhaust system. The average velocity of ventilation at the face of access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window.

    502.9.2Corrosives. Where corrosive materials in amounts exceeding the maximum allowable quantity per control area are dispensed or used, mechanical exhaust ventilation in accordance with Section 502.8.4 shall be provided.

    502.9.3Cryogenics. Storage areas for stationary or portable containers of  cryogenic fluids in any quantity shall be ventilated in accordance with Section  502.8. Indoor areas where cryogenic fluids in any quantity are dispensed shall be ventilated in accordance with the requirements of Section 502.8.4 in a manner that captures any vapor at the point of generation.

    Exception: Ventilation for indoor dispensing areas is not required where it can be demonstrated that the cryogenic fluids do not create harmful  vapors.

    502.9.4Explosives. Squirrel cage blowers shall not be used for exhausting hazardous fumes, vapors or gases in operating buildings and rooms for the manufacture, assembly or testing of explosives. Only nonferrous fan blades shall be used for fans located within the ductwork and through which hazardous materials are exhausted. Motors shall be located outside the duct.

    502.9.5Flammable and combustible liquids. Exhaust ventilation systems shall be provided as required by Sections 502.9.5.1 through 502.9.5.5 for the storage,  use, dispensing, mixing and handling of flammable and combustible liquids.  Unless otherwise specified, this section shall apply to any quantity of flammable and combustible liquids.

    Exception: This section shall not apply to the following:

    1.Specific provisions for flammable liquids in motor fuel-dispensing facilities, airports and marinas as identified in Chapter 22 of the fire code.

    2.Medicines, foodstuffs, cosmetics, and commercial, institutional and industrial products in the same concentration and packaging containing not more than fifty percent by volume of water-miscible liquids and with the remainder of the solution not being flammable, and alcoholic beverages in retail or wholesale sales or storage uses when packaged in individual containers not exceeding 1.3 gallons (5 L).

    3.Storage and use of fuel oil tanks and containers connected to oil burning equipment. Such storage and use shall be in accordance with chapter 13.

    4.Refrigerant liquids and oils in refrigeration systems.

    5.Storage and display of aerosol products complying with the fire code.

    6.Storage and use of liquids that have no fire point when tested in accordance with ASTM D 92.

    7.Liquids with a flashpoint greater than ninety-five degrees Fahrenheit (thirty-

    five degrees Centigrade) in a water-miscible solution or dispersion with a water and inert (noncombustible) solids content of more than eighty per cent by weight, which do not sustain combustion.

    8.Liquids without flash points that can be flammable under some conditions, such as certain halogenated hydrocarbons and mixtures containing halogenated hydrocarbons.

    9.The storage of distilled spirits and wines in wooden barrels and casks.

    10.Underground storage tanks installed in accordance with the fire code and rules adopted by the state fire marshal and enforced by the fire official, in accordance with section 3737.87 to 3737.89 of the Revised Code.

    502.9.5.1Vaults. Vaults that contain tanks of Class I liquids shall be provided

    2

    with continuous ventilation at a rate of not less than 1 cfm/ft  of floor area

    3              2                                                                        3

    [0.00508 m /(s m )], but not less than 150 cfm (4 m /min). Failure of the exhaust

    airflow shall automatically shut down the dispensing system. The exhaust system shall be designed to provide air movement across all parts of the vault floor. Supply and exhaust ducts shall extend to a point not greater than 12 inches (305  mm) and not less than 3 inches (76 mm) above the floor. The exhaust system shall be installed in accordance with the provisions of NFPA 91. Means shall be provided to automatically detect any flammable vapors and to automatically shut  down the dispensing system upon detection of such flammable vapors in the exhaust duct at a concentration of 25 percent of the LFL.

    502.9.5.2Storage rooms and warehouses. Liquid storage rooms and liquid storage warehouses for quantities of liquids exceeding those specified in the  building code shall be ventilated in accordance with Section 502.8.1.

    502.9.5.3Cleaning machines. Areas containing machines used for parts cleaning  in accordance with the fire code shall be adequately ventilated to prevent accumulation of vapors.

    502.9.5.4Use, dispensing and mixing. Continuous mechanical ventilation shall be provided for the use, dispensing and mixing of flammable and combustible liquids in open or closed systems in amounts exceeding the maximum allowable quantity per control area and for bulk transfer and process transfer operations. The

    2                          3               2

    ventilation rate shall be not less than 1 cfm/ft  [0.00508 m /(s m )] of floor area

    over the design area. Provisions shall be made for the introduction of makeup air in a manner that will include all floor areas or pits where vapors can collect. Local  or spot ventilation shall be provided where needed to prevent the accumulation of  hazardous vapors.

    Exception: Where natural ventilation can be shown to be effective for the materials used, dispensed or mixed.

    502.9.5.5Bulk plants or terminals. Ventilation shall be provided for portions of  properties where flammable and combustible liquids are received by tank vessels,  pipelines, tank cars or tank vehicles and which are stored or blended in bulk for

    the purpose of distributing such liquids by tank vessels, pipelines, tank cars, tank vehicles or containers as required by Sections 502.9.5.5.1 through 502.9.5.5.3.

    502.9.5.5.1  General.  Ventilation  shall  be  provided  for  rooms,  buildings  and enclosures in which Class I liquids are pumped, used or transferred. Design of  ventilation  systems  shall  consider  the  relatively  high  specific  gravity  of  the  vapors. Where natural ventilation is used, adequate openings in outside walls at floor level, unobstructed except by louvers or coarse screens, shall be provided. Where natural ventilation is inadequate, mechanical ventilation shall be provided.  502.9.5.5.2 Basements and pits. Class I liquids shall not be stored or used within a building having a basement or pit into which flammable vapors can travel,  unless such area is provided with ventilation designed to prevent the accumulation  of flammable vapors therein.

    502.9.5.5.3 Dispensing of Class I liquids. Containers of Class I liquids shall not be drawn from or filled within buildings unless a provision is made to prevent the accumulation of flammable vapors in hazardous concentrations. Where mechanical ventilation is required, it shall be kept in operation while flammable  vapors could be present.

    502.9.6Highly toxic and toxic liquids. Ventilation exhaust shall be provided for  highly toxic and toxic liquids as required by Sections 502.9.6.1 and 502.9.6.2.

    502.9.6.1Treatment system. This provision shall apply to indoor and outdoor storage and use of highly toxic and toxic liquids in amounts exceeding the maximum allowable quantities per control area. Exhaust scrubbers or other systems for processing vapors of highly toxic liquids shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic  vapors at normal temperature and pressure.

    502.9.6.2Open and closed systems. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in open systems in accordance with Section 502.8.4. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in closed systems in accordance with Section 502.8.5.  Exception: Liquids or solids that do not generate highly toxic or toxic fumes,  mists or vapors.

    502.9.7Highly toxic and toxic compressed gases- any quantity. Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2.

    502.9.7.1Gas cabinets. Gas cabinets containing highly toxic or toxic compressed  gases in any quantity shall comply with Section 502.8.2 and the following requirements:

    1.      The average ventilation velocity at the face of gas cabinet access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window.

    2.      Gas cabinets shall be connected to an exhaust system.

    3.      Gas cabinets shall not be used as the sole means of exhaust for any room or  area.

    502.9.7.2Exhausted enclosures. Exhausted enclosures containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2  and the following requirements:

    1.      The average ventilation velocity at the face of the enclosure shall be not  less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150  feet per minute (0.76 m/s).

    2.      Exhausted enclosures shall be connected to an exhaust system.

    3.      Exhausted enclosures shall not be used as the sole means of exhaust for  any room or area.

    502.9.8Highly toxic and toxic compressed gases-quantities exceeding the maximum allowable quantity per control area. Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in amounts exceeding the maximum allowable quantities per control area as required by Sections 502.9.8.1  through

    502.9.8.6.

    502.9.8.1Ventilated areas. The room or area in which indoor gas cabinets or  exhausted enclosures are located shall be provided with exhaust ventilation. Gas  cabinets or exhausted enclosures shall not be used as the sole means of exhaust  for any room or area.

    502.9.8.2Local exhaust for portable tanks. A means of local exhaust shall be provided to capture leakage from indoor and outdoor portable tanks. The local exhaust shall consist of portable ducts or collection systems designed to be applied to the site of a leak in a valve or fitting on the tank. The local exhaust system shall be located in a gas room. Exhaust shall be directed to a treatment system where required by Section 3704.2.2.7 of the fire code.

    502.9.8.3Piping and controls-stationary tanks. Filling or dispensing connections on indoor stationary tanks shall be provided with a means of local exhaust. Such exhaust shall be designed to capture fumes and vapors. The exhaust shall be directed to a treatment system where required by the fire code.

    502.9.8.4Gas rooms. The ventilation system for gas rooms shall be designed to operate at a negative pressure in relation to the surrounding area. The exhaust ventilation from gas rooms shall be directed to an exhaust system.

    502.9.8.5Treatment system. The exhaust ventilation from gas cabinets, exhausted enclosures and gas rooms, and local exhaust systems required in Sections 502.9.8.2 and 502.9.8.3 shall be directed to a treatment system where required by the fire code.

    502.9.8.6Process equipment. Effluent from indoor and outdoor process

    equipment containing highly toxic or toxic compressed gases which could be discharged to the atmosphere shall be processed through an exhaust scrubber  or other processing system. Such systems shall be in accordance with the fire code.

    502.9.9Ozone gas generators. Ozone cabinets and ozone gas-generator rooms

    1

    for systems having a maximum ozone-generating capacity of

    /2 pound (0.23 kg)

    or more over a 24-hour period shall be mechanically ventilated at a rate of not less  than six air changes per hour. For cabinets, the average velocity of ventilation at makeup air openings with cabinet doors closed shall be not less than 200 feet per minute (1.02 m/s).

    502.9.10LP-gas distribution facilities. LP-gas distribution facilities shall be ventilated in accordance with NFPA 58.

    502.9.10.1Portable container use. Above-grade underfloor spaces or basements in which portable LP-gas containers are used or are stored awaiting use or resale shall be provided with an approved means of ventilation.

    Exception: Department of Transportation (DOT) specification cylinders  with a maximum water capacity of 2.5 pounds (1 kg) for use in completely self-contained hand torches and similar applications. The quantity of LP- gas shall not exceed 20 pounds (9 kg).

    502.9.11Silane gas. Exhausted enclosures and gas cabinets for the indoor storage of silane gas in amounts exceeding the maximum allowable quantities per control area shall comply with this section.

    1.      Exhausted enclosures and gas cabinets shall be in accordance with Section 502.8.2.

    2.      The velocity of ventilation across unwelded fittings and connections on the piping system shall not be less than 200 feet per minute (1.02 m/s).

    3.      The average velocity at the face of the access ports or windows in the gas cabinet shall not be less than 200 feet per minute (1.02 m/s)  with a minimum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window.

    502.10Hazardous production materials (HPM).

    Exhaust ventilation systems and materials for ducts utilized for the exhaust of HPM shall comply with this section, other applicable provisions of this code, the  building code and the fire code.

    502.10.1Where required. Exhaust ventilation systems shall be provided in the  following locations in accordance with the requirements of this section and the  building code.

    1.      Fabrication areas: Exhaust ventilation for fabrication areas shall comply

    with  the  building  code.  Additional  manual  control  switches  shall  be provided where required by the code official.

    2.      Workstations: A ventilation system shall be provided to capture and  exhaust gases, fumes and vapors at workstations.

    3.      Liquid storage rooms: Exhaust ventilation for liquid storage rooms shall comply with Section 502.8.1.1 and the building code.

    4.      HPM rooms: Exhaust ventilation for HPM rooms shall comply with Section 502.8.1.1 and the building code.

    5.      Gas cabinets: Exhaust ventilation for gas cabinets shall comply with Section 502.8.2. The gas cabinet ventilation system is allowed to connect to a workstation ventilation system. Exhaust ventilation for gas cabinets containing highly toxic or toxic gases shall also comply with Sections 502.9.7 and 502.9.8.

    6.      Exhausted enclosures: Exhaust ventilation for exhausted enclosures shall comply with Section 502.8.2. Exhaust ventilation for exhausted enclosures containing highly toxic or toxic gases shall also comply with Sections 502.9.7 and 502.9.8.

    7.      Gas rooms: Exhaust ventilation for gas rooms shall comply with Section  502.8.2. Exhaust ventilation for gas cabinets containing highly toxic or  toxic gases shall also comply with Sections 502.9.7 and 502.9.8.

    502.10.2Penetrations. Exhaust ducts penetrating fire barrier assemblies shall be contained in a shaft of equivalent fire-resistive construction. Exhaust ducts shall not penetrate building separation walls. Fire dampers shall not be installed in exhaust ducts.

    502.10.3Treatment systems. Treatment systems for highly toxic and toxic  gases shall comply with Section 3704.2.2.7 of the fire code.

    502.11Motion picture projectors. Motion picture projectors shall be exhausted in accordance with Section 502.11.1 or

    502.11.2.

    502.11.1Projectors with an exhaust discharge. Projectors equipped with an exhaust discharge shall be directly connected to a mechanical exhaust system.  The exhaust system shall operate at an exhaust rate as indicated by the man-  ufacturer's installation instructions.

    502.11.2Projectors without exhaust connection. Projectors without an exhaust connection shall have contaminants exhausted through a mechanical exhaust system. The exhaust rate for electric arc projectors shall be a minimum

    3

    of 200 cubic feet per minute (cfm) (0.09 m /s) per lamp. The exhaust rate for

    3

    xenon projectors shall be a minimum of 300 cfm (0.14 m /s) per lamp. Xenon

    projector exhaust shall be at a rate such that the exterior temperature of the lamp housing does not exceed 130ºF (54ºC). The lamp and projection room

    exhaust systems, whether combined or independent, shall not be interconnected with any other exhaust or return system within the building.

    502.12Organic coating processes. Enclosed structures involving organic coating  processes in which Class I liquids are processed or handled shall be ventilated at a

    2                          3              2

    rate of not less than 1 cfm/ft  [0.00508 m /(s m )] of solid floor area. Ventilation

    shall be accomplished by exhaust fans that intake at floor levels and discharge to a safe location outside the structure. Noncontaminated intake air shall be introduced in such a manner that all portions of solid floor areas are provided with con- tinuous uniformly distributed air movement.

    502.13Public garages. Mechanical exhaust systems for public garages, as  required in Chapter 4, shall operate continuously or in accordance with Section 404.

    502.14Motor vehicle operation. In areas where motor vehicles operate, mechanical ventilation shall be provided in accordance with Section 403.  Additionally, areas  in  which stationary motor vehicles are operated shall be provided with a source capture system that connects directly to the motor vehicle exhaust systems.

    Exceptions:

    1.      This section shall not apply where the motor vehicles being operated or  repaired are electrically powered.

    2.      Deleted.

    3.      This section shall not apply to motor vehicle service areas where engines are operated inside the building only for the duration necessary to move the motor vehicles in and out of the building.

    502.15Repair garages. Where Class I liquids or LP-gas are stored or used within a building having a basement or pit wherein flammable vapors could accumulate, the basement or pit shall be provided with ventilation designed to prevent the accumulation of flammable vapors therein.

    502.16Repair garages for natural gas-and hydrogen-fueled vehicles. Repair garages used for the repair of natural gas-or hydrogen-fueled vehicles shall be provided with an approved mechanical ventilation system. The mechanical ven- tilation system shall be in accordance with Sections 502.16.1 and 502.16.2.

    Exception: Where approved by the code official, natural ventilation shall be permitted in lieu of mechanical ventilation.

    502.16.1Design. Indoor locations shall be ventilated utilizing air supply inlets and exhaust outlets arranged to provide uniform air movement to the extent practical. Inlets shall be uniformly arranged on exterior walls near floor level. Outlets shall be located at the high point of the room in exterior walls or the  roof.

    Ventilation shall be by a continuous mechanical ventilation system or by a mechanical ventilation system activated by a continuously monitoring natural  gas detection system, or for hydrogen, a continuously monitoring flammable  gas detection system, each activating at a gas concentration of 25 percent of the lower flammable limit (LFL). In all cases, the system shall shut down the fueling system in the event of failure of the ventilation system.

    The ventilation rate shall be at least 1 cubic foot per minute per 12 cubic feet

    3              3

    [0.00138 m /(s m )] of room volume.

    502.16.2Operation. The mechanical ventilation system shall operate continuously.

    Exceptions:

    1.      Mechanical ventilation systems that are interlocked with a gas detection system designed in accordance with the fire code.

    2.      Mechanical ventilation systems in garages that are used only for the repair of vehicles fueled by liquid fuels or odorized gases, such as CNG,  where the ventilation system is electrically interlocked with the lighting circuit.

    502.17Tire rebuilding or recapping. Each room where rubber cement is used or  mixed, or where flammable or combustible solvents are applied, shall be ventilated in accordance with the applicable provisions of NFPA 91.

    502.17.1 Buffing machines. Each buffing machine shall be connected to a dust-collecting system that prevents the accumulation of the dust produced by  the buffing process.

    502.18Specific rooms. Specific rooms, including bathrooms, locker rooms,  smoking lounges and toilet rooms, shall be exhausted in accordance with the ventilation requirements of Chapter 4.

    502.19Indoor firing ranges. Ventilation shall be provided in an  approved manner in areas utilized as indoor firing ranges. Ventilation shall be designed to protect employees and the public in accordance with OSHA 29 CFR 1910.1025  where applicable.

    SECTION 503 MOTORS AND FANS

    503.1General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such environments. A manually operated remote control installed at an approved location shall be provided to shut off fans or blowers in

    flammable vapor or dust systems. Electrical equipment and appliances used in operations that generate explosive or flammable vapors, fumes or dusts shall be interlocked with the ventilation system so that the equipment and appliances cannot be operated unless the ventilation fans are in operation. Motors for fans used to convey flammable vapors or dusts shall be located outside the duct or  shall be protected with approved shields and dustproofing. Motors and fans shall be provided with a means of access for servicing and maintenance.

    503.2Fans. Parts of fans in contact with explosive or flammable vapors, fumes or dusts shall be of nonferrous or nonsparking materials, or their casing shall be lined or constructed of such material. When the size and hardness of materials  passing through a fan are capable of producing a spark, both the fan and the casing shall be of nonsparking materials. When fans are required to be spark resistant, their bearings shall not be within the airstream, and all parts of the fan  shall be grounded. Fans in systems-handling materials that are capable of  clogging the blades, and fans in buffing or woodworking exhaust systems, shall be of the radial-blade or tube-axial type.

    503.3Equipment and appliance identification plate. Equipment and appliances  used to exhaust explosive or flammable vapors, fumes or dusts shall bear an identification plate stating the ventilation rate for which the system was designed.

    503.4Corrosion-resistant fans. Fans located in systems conveying corrosives shall be of materials that are resistant to the corrosive or shall be coated with  corrosion-resistant materials.

    SECTION 504 CLOTHES DRYER EXHAUST

    504.1Installation. Clothes dryers shall be exhausted in accordance with the manufacturer's instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building.

    Exception:  This  section  shall  not  apply  to  listed  and  labeled  condensing (ductless) clothes dryers.

    504.2Exhaust penetrations. Where a clothes dryer exhaust duct penetrates a wall or ceiling membrane, the annular space shall be sealed with noncombustible material, approved fire caulking or a noncombustible dryer exhaust duct wall receptacle. Ducts that exhaust clothes dryers shall not penetrate or be located within any fireblocking, draftstopping or any wall, floor/ceiling or other assembly required by the building code to be fire-resistance rated, unless such duct is

    constructed of galvanized steel or aluminum of the thickness specified in Section 603.4 and the fire-resistance rating is maintained in accordance with the building code. Fire dampers, combination fire/smoke dampers and any similar devices that will obstruct the exhaust flow shall be prohibited in clothes dryer exhaust ducts.  504.3 Cleanout. Each vertical riser shall be provided with a means for cleanout.

    504.4Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate  on the outside of the building and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected  or installed with sheet metal screws or other fasteners that will obstruct the exhaust flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent or chimney. Clothes dryer exhaust ducts shall not extend into or  through ducts or plenums.

    3

    504.5Makeup air. Installations exhausting more than 200 cfm (0.09m /s) shall

    be provided with makeup air. Where a closet is designed for the installation of a clothes dryer, an opening having an area of not less than 100 square inches

    2

    (0.0645 m ) shall be provided in the closet enclosure or makeup air shall be

    provided by other approved means.

    504.6Domestic clothes dryer ducts. Exhaust ducts for domestic clothes dryers  shall conform to the requirements of Sections 504.6.1 through 504.6.7.

    504.6.1Material and size. Exhaust ducts shall have a smooth interior finish and shall be constructed of metal a minimum 0.016 inch (0.4 mm) thick. The exhaust duct size shall be 4 inches (102 mm) nominal in diameter.

    504.6.2Duct installation. Exhaust ducts shall be supported at 4-foot (1219 mm)  intervals and secured in place. The insert end of the duct shall extend into the adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with  screws or similar fasteners that protrude into the inside of the duct.

    504.6.3Transition ducts. Transition ducts used to connect the dryer  to the exhaust duct system shall be a single length that is listed and labeled in accordance with UL 2158A. Transition ducts shall be a maximum of 8 feet (2438  mm) in length and shall not be concealed within construction.

    504.6.4Duct length. The maximum allowable exhaust duct length shall be determined by one of the methods specified in Section 504.6.4.1 or 504.6.4.2.

    504.6.4.1Specified length. The maximum length of the exhaust duct shall be  35 feet (10 668 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance with Table 504.6.4.1.

    TABLE 504.6.4.1

    DRYER EXHAUST DUCT FITTING EQUIVALENT LENGTH

    DRYER EXHAUST DUCT FITTING TYPE

    EQUIVALENT LENGTH

    4" radius mitered 45-degree elbow

    2 feet 6 inches

    4" radius mitered 90-degree elbow

    5 feet

    6" radius smooth 45-degree elbow

    1 foot

    6" radius smooth 90-degree elbow

    1 foot 9 inches

    8" radius smooth 45-degree elbow

    1 foot

    8" radius smooth 90-degree elbow

    1 foot 7 inches

    10" radius smooth 45-degree elbow

    9 inches

    10" radius smooth 90-degree elbow

    1 foot 6 inches

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.

    504.6.4.2Manufacturer's instructions. The maximum length of the exhaust duct shall be determined by the dryer manufacturer's installation instructions. The code official shall be provided with a copy of the installation instructions for the make and model of the dryer. Where the exhaust duct is to be concealed, the installation instructions shall be provided to the code official prior to the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table 504.6.4.1 shall be used.

    504.6.5Length identification. Where the exhaust duct is concealed within the building construction, the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6  feet (1829 mm) of the exhaust duct connection.

    504.6.6Exhaust duct required. Where space for a clothes dryer is provided, an exhaust duct system shall be installed. Where the clothes dryer is not installed at the time of occupancy, the exhaust duct shall be capped at the location of the future dryer.

    Exception: Where a listed condensing clothes dryer is installed prior to occupancy of structure.

    504.6.7Protection required. Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all

    1

    framing members where there is less than 1 /4 inches (32 mm) between the

    duct and the finished face of the framing member. Protective shield plates shall

    be constructed of steel, have a thickness of 0.062 inch (1.6 mm) and extend a minimum of 2 inches (51 mm) above sole plates and below top plates.

    504.7Commercial clothes dryers. The installation of dryer exhaust ducts serving Type 2 clothes dryers shall comply with the appliance manufacturer's installation instructions. Exhaust fan motors installed in exhaust systems shall be located outside of the airstream. In multiple installations, the fan shall operate continuously or be interlocked to operate when any individual unit is operating.  Ducts shall have a minimum clearance of 6 inches (152 mm) to combustible materials. Clothes dryer transition ducts used to connect the appliance to the exhaust duct system shall be limited to single lengths not to exceed 8 feet (2438  mm) in length and shall be listed and labeled for the application. Transition ducts shall not be concealed within construction.

    504.8Common exhaust systems for clothes dryers located in multistory structures. Where a common multistory duct system is designed and installed to convey exhaust from multiple clothes dryers, the construction of the system shall be in accordance with all of the following:

    1.      The shaft in which the duct is installed shall be constructed and fire- resistance rated as required by the building code.

    2.      Dampers shall be prohibited in the exhaust duct. Penetrations of the shaft and ductwork shall be protected in accordance with Section 607.5.5,  Exception 2.

    3.      Rigid metal ductwork shall be installed within  the shaft  to convey the exhaust. The ductwork shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) and in accordance with  SMACNA Duct Construction Standards.

    4.      The ductwork within the shaft shall be designed and installed without offsets.

    5.      The exhaust fan motor design shall be in accordance with Section 503.2.

    6.      The exhaust fan motor shall be located outside of the airstream.

    7.      The exhaust fan shall run continuously.

    8.      Exhaust fan operation shall initiate an audible or visual signal when the fan is not in operation.

    9.      Makeup air shall be provided for the exhaust system.

    10.  A cleanout opening shall be located at the base of the shaft to provide access to the duct to allow for cleaning and inspection. The finished opening shall be not less than 12 inches by 12 inches (305 mm by 305 mm).

    11.  Screens shall not be installed at the termination.

    SECTION 505

    DOMESTIC KITCHEN EXHAUST EQUIPMENT

    505.1Domestic systems. Where domestic range hoods and domestic appliances equipped with downdraft exhaust are located within dwelling units, such hoods  and appliances shall discharge to the outdoors through sheet metal ducts constructed of galvanized steel, stainless steel, aluminum or copper. Such ducts shall have smooth inner walls and shall be air tight and equipped with a backdraft damper.

    Exceptions:

    1.      Where installed in accordance with the manufacturer's installation instructions and where mechanical or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled ductless range hoods shall not  be required to discharge to the outdoors.

    2.      Ducts for domestic kitchen cooking appliances equipped with downdraft exhaust systems shall be permitted to be constructed of Schedule 40 PVC pipe and fittings provided that the installation complies with all of the following:

    2.1.The duct shall be installed under a concrete slab poured on grade.

    2.2.The  underfloor  trench  in  which  the  duct  is  installed  shall  be completely backfilled with sand or gravel.

    2.3.The PVC duct shall extend not more than 1 inch (25 mm) above the indoor concrete floor surface.

    2.4.The PVC duct shall extend not more than 1 inch (25 mm) above grade outside of the building.

    2.5.The PVC ducts shall be solvent cemented.

    505.2Makeup air required. Exhaust hood systems capable of exhausting

    3

    in excess of 400 cfm (0.19 m /s) shall be provided with makeup air at a

    rate approximately equal to the exhaust air rate. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system.

    SECTION 506

    COMMERCIAL KITCHEN HOOD VENTILATION SYSTEM DUCTS AND EXHAUST EQUIPMENT

    506.1General. Commercial kitchen hood ventilation ducts  and  exhaust equipment shall comply with the requirements of this section. Commercial kitchen grease ducts shall be designed for the type of cooking appliance and hood  served.

    506.2Corrosion protection. Ducts exposed to the outside atmosphere or subject to a corrosive environment shall be protected against corrosion in an approved manner.

    506.3Ducts serving Type I hoods. Type I exhaust ducts shall be independent of  all other exhaust systems except as provided in Section 506.3.5. Commercial kitchen duct systems serving Type I hoods shall be designed, constructed and installed in accordance with Sections 506.3.1 through 506.3.12.3.

    506.3.1Duct materials. Ducts serving Type I hoods shall be constructed of materials in accordance with Sections 506.3.1.1 and 506.3.1.2.

    506.3.1.1Grease duct materials. Grease ducts serving Type I hoods shall be constructed of steel having a minimum thickness of 0.0575 inch (1.463  mm) (No. 16 gage) or stainless steel not less than 0.0450 inch (1.14 mm) (No. 18 gage) in thickness.

    Exception: Factory-built commercial kitchen grease ducts listed and  labeled in accordance with UL 1978 and installed in accordance with Section 304.1.

    506.3.1.2Makeup air ducts. Makeup air ducts connecting to or within 18  inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1, 603.3, 603.4, 603.9, 603.10 and 603.12.  Duct insulation installed within 18 inches (457 mm) of a Type I hood shall be noncombustible or shall be listed for the application.

    506.3.2Joints, seams and penetrations of grease ducts.

    Joints, seams and penetrations of grease ducts shall be made with a continuous liquid-tight weld or braze made on the external surface of the duct system.

    Exceptions:

    1.      Penetrations shall not be required to be welded or brazed where sealed by devices that are listed for the application.

    2.      Internal welding or brazing shall not be prohibited provided that the joint is formed or ground smooth and is provided with ready access for inspection.

    3.      Factory-built  commercial  kitchen  grease  ducts  listed  and  labeled  in accordance with UL 1978 and installed in accordance with Section 304.1.

    506.3.2.1Duct joint types. Duct joints shall be butt joints, welded flange

    1

    joints with a maximum flange depth of

    /2 inch (12.7 mm) or overlapping

    duct joints of either the telescoping or bell type. Overlapping joints shall be installed to prevent ledges and obstructions from collecting grease or  interfering with gravity drainage to the intended collection point. The difference between the inside cross-sectional dimensions of overlapping

    1

    sections of duct shall not exceed

    /4 inch (6 mm). The length of overlap for

    overlapping duct joints shall not exceed 2 inches (51 mm).

    506.3.2.2Duct-to-hood joints. Duct-to-hood joints shall be made with continuous internal or external liquid-tight welded or brazed joints. Such  joints shall be smooth, accessible for inspection, and without grease traps.  Exceptions: This section shall not apply to:

    1.A vertical duct-to-hood collar connection made in the top plane of the hood  in accordance with all of the following:

    1.1.The hood duct opening shall have a 1-inch-deep (25 mm), full perimeter, welded flange turned down into the hood interior at an angle of 90 degrees (1.57 rad) from the plane of the opening.

    1.2.The duct shall have a 1-inch-deep (25 mm) flange made by a 1-inch  by 1-inch (25 mm by 25 mm) angle iron welded to the full perimeter  of the duct not less than 1 inch (25 mm) above the bottom end of the duct.

    1.3.A gasket rated for use at not less than 1,500ºF (815ºC) is installed between the duct flange and the top of the hood.

    1

    1.4.The duct-to-hood joint shall be secured by stud bolts not less than  /4

    inch (6.4 mm) in diameter welded to the hood with a spacing not greater than 4 inches (102 mm) on center for the full perimeter of the opening. All bolts and nuts are to be secured with lockwashers.

    2    Listed and labeled duct-to-hood collar connections installed in accordance with Section 304.1.

    506.3.2.3Duct-to-exhaust fan connections. Duct-to-exhaust fan  connections shall be flanged and gasketed at the base of the fan for vertical discharge fans; shall be flanged, gasketed and bolted to the inlet of the fan for side-inlet utility fans; and shall be flanged, gasketed and bolted to the inlet and outlet of the fan for  in-line fans.

    506.3.2.4Vibration isolation. A vibration isolation connector for connecting a duct to a fan shall consist of noncombustible packing in a metal sleeve joint of  approved design or shall be a coated-fabric flexible duct connector listed and labeled for the application. Vibration isolation connectors shall be installed only at the connection of a duct to a fan inlet or outlet.

    506.3.2.5Grease duct test. Prior to the use or concealment of any portion of a grease duct system, a leakage test shall be performed. Ducts shall be considered to be concealed where installed in shafts or covered by coatings or wraps that prevent the ductwork from being visually inspected on all sides. The permit holder shall be responsible to provide the necessary equipment and perform the grease duct leakage test. A light test shall be performed to determine that all welded and brazed joints are liquid tight.

    A light test shall be performed by passing a lamp having a power rating of not less  than 100 watts through the entire section of ductwork to be tested. The lamp shall be open so as to emit light equally in all directions perpendicular to the duct walls.  A test shall be performed for the entire duct system, including the hood-to-duct connection. The duct work shall be permitted to be tested in sections, provided that every joint is tested. For listed factory-built grease ducts, this test shall be limited to duct joints assembled in the field and shall exclude factory welds.

    506.3.3Grease duct supports. Grease duct bracing and supports shall be of  noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of the building code. Bolts,  screws, rivets and other mechanical fasteners shall not penetrate duct walls.

    506.3.4Air velocity. Grease duct systems serving a Type I hood shall  be designed and installed to provide an air velocity within the duct system of not less  than 500 feet per minute (2.5 m/s).

    Exception: The velocity limitations shall not apply within duct transitions  utilized to connect ducts to differently sized or shaped openings in hoods and  fans, provided that such transitions do not exceed 3 feet (914 mm) in length and  are designed to prevent the trapping of grease.

    506.3.5Separation of grease duct system. A separate grease duct system shall be provided for each Type I hood. A separate grease duct system is not required where all of the following conditions are met:

    1.      All interconnected hoods are located within the same story.

    2.      All interconnected hoods are located within the same room or in adjoining rooms.

    3.      Interconnecting  ducts  do  not  penetrate  assemblies  required  to  be  fire-  resistance rated.

    4.      The grease duct system does not serve solid-fuel-fired appliances.

    506.3.6Grease duct clearances. Where enclosures are not required, grease duct systems and exhaust equipment serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 3 inches (76 mm).

    Exceptions:

    1.      Factory-built   commercial   kitchen   grease   ducts   listed   and   labeled   in accordance with UL 1978.

    2.      Listed and labeled exhaust equipment installed in accordance with Section  304.1.

    3.      Where commercial kitchen grease ducts are continuously covered on all sides  with a listed and labeled field-applied grease duct enclosure material, system,  product or method of construction specifically evaluated for such purpose in accordance with ASTM E 2336, the required clearance shall be in accordance with the listing of such material, system, product or method.

    506.3.7Prevention of grease accumulation in grease ducts. Duct systems  serving a Type I hood shall be constructed and installed so that grease cannot collect in any portion thereof, and the system shall slope not less than one-fourth unit vertical in 12 units horizontal (2 percent slope) toward the hood or toward an approved grease reservoir. Where horizontal ducts exceed 75 feet (22 860 mm) in length, the slope shall not be less than one unit vertical in 12 units horizontal (8.3 percent slope).

    506.3.8Grease duct cleanouts and other openings.

    Grease duct systems shall not have openings therein other than those required for  proper operation and maintenance of the system. Any portion of such system having sections not provided with access from the duct entry or discharge shall be provided with cleanout openings. Cleanout openings shall be equipped with tight- fitting doors constructed of steel having a thickness not less than that required for  the duct. Doors shall be equipped with a substantial method of latching, sufficient to hold the door tightly closed. Door assemblies, including any frames and gasketing, shall be approved for the purpose, and shall not have fasteners that penetrate the duct. Listed and labeled access door assemblies shall be installed in accordance with the terms of the listing.

    506.3.8.1Personnel entry. Where ductwork is large enough to allow entry of personnel, not less than one approved or listed opening having dimensions not less than 22 inches by 20 inches (559 mm by 508 mm)  shall be provided in the horizontal sections, and in the top of vertical  risers. Where such entry is provided, the duct and its supports shall be capable of supporting the additional load, and the cleanouts specified in Section 506.3.8 are not required.

    506.3.8.2Cleanouts serving in-line fans. A cleanout shall be provided  for both the inlet side and outlet side of an in-line fan except where a duct  does not connect to the fan. Such cleanouts shall be located within 3 feet  (914 mm) of the fan duct connections.

    506.3.9Grease duct horizontal cleanouts. Cleanouts located on horizontal sections of ducts shall be spaced not more than 20 feet (6096 mm) apart. The cleanouts shall be located on the side of the duct with the opening not less than

    1

    1 /2 inches (38 mm) above the bottom of the duct, and not less than 1 inch (25

    mm) below the top of the duct. The opening minimum dimensions shall be 12  inches (305 mm) on each side. Where the dimensions of the side of the duct

    prohibit the cleanout installation prescribed herein, the openings shall be on the top of the duct or the bottom of the duct. Where located on the top of the duct, the opening edges shall be a minimum of 1 inch (25 mm) from the edges of the duct. Where located in the bottom of the duct, cleanout openings shall be designed to provide internal damming around the opening, shall be provided with gasketing to preclude grease leakage, shall provide for drainage of grease down the duct around the dam and shall be approved for the application. Where the dimensions of the sides, top or bottom of the duct preclude the installation of the prescribed minimum-size cleanout opening, the cleanout shall be located on the duct face that affords the largest opening dimension and shall be installed with the opening edges at the prescribed distances from the duct edges as previously set forth in this section.

    506.3.10Grease duct enclosures. A grease duct serving a Type I hood that penetrates a ceiling, wall or floor shall be enclosed from the point of penetration to the outlet terminal. A duct shall penetrate exterior walls only at locations where unprotected openings are permitted by the building code. The duct enclosure shall serve a single grease duct and shall not contain other ducts, piping or wiring systems. Duct enclosures shall be either field-applied or factory-built. Duct enclosures shall have a fire-resistance rating not less than that of the floor assembly penetrated, but need not exceed 2 hours. Duct enclosures shall be as  prescribed by Section 506.3.10.1, 506.3.10.2 or 506.3.10.3.

    506.3.10.1Shaft enclosure. Commercial kitchen grease ducts constructed in accordance with Section 506.3.1 shall be permitted to be enclosed in accordance with the building code requirements for shaft construction.  Such grease duct systems and exhaust equipment shall have a clearance to combustible construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 6 inches (76 mm). Duct enclosures shall be sealed around the duct at the point of penetration and vented to the outside of the building through the use of weather- protected openings.

    506.3.10.2Field-applied grease duct enclosure. Commercial kitchen  grease ducts constructed in accordance with Section 506.3.1 shall be enclosed by a field-applied grease duct enclosure that is a listed and labeled material, system, product or method of construction specifically evaluated for such purpose in accordance with ASTM E 2336. The surface  of the duct shall be continuously covered on all sides from the point at which the duct originates to the outlet terminal. Duct penetrations shall be protected with a through-penetration firestop system classified in accordance with ASTM E 814 or UL 1479 and having an "F" and "T"

    rating equal to the fire-resistance rating of the assembly being penetrated.  Such systems shall be installed in accordance with the listing and the manufacturer's installation instructions. Exposed duct wrap systems shall be protected where subject to physical damage.

    506.3.10.3Factory-built grease duct assemblies. Factory-built grease duct assemblies incorporating integral enclosure materials shall be listed and labeled  for use as commercial kitchen grease duct assemblies in accordance with UL 2221. Duct penetrations shall be protected with a through-penetration firestop system classified in accordance with ASTM E 814 or UL 1479 and having an "F" and "T" rating equal to the fire-resistance rating of the assembly being penetrated. Such assemblies shall be installed in accordance with the listing and the manufacturer's installation instructions.

    506.3.10.4Duct enclosure not required. A duct enclosure shall not be required for a grease duct that penetrates only a nonfire-resistance-rated roof/ceiling assembly.

    506.3.11Grease duct fire-resistive access opening.

    Where cleanout openings are located in ducts within a fire-resistance-rated enclosure, access openings shall be provided in the enclosure at each cleanout point. Access openings shall be equipped with tight-fitting sliding or hinged doors  that are equal in fire-resistive protection to that of the shaft or enclosure. An  approved sign shall be placed on access opening panels with wording as follows: "ACCESS PANEL. DO NOT OBSTRUCT."

    506.3.12Exhaust outlets serving Type I hoods. Exhaust outlets for grease ducts serving Type I hoods shall conform to the requirements of Sections 506.3.12.1  through 506.3.12.3.

    506.3.12.1Termination above the roof. Exhaust outlets that terminate above the roof shall have the discharge opening located not less than 40 inches (1016  mm) above the roof surface.

    506.3.12.2Termination through an exterior wall.

    Exhaust outlets shall be permitted to terminate through exterior walls where the smoke, grease, gases, vapors and odors in the discharge from such  terminations do not create a public nuisance or a fire hazard. Such termina- tions shall not be located where protected openings are required by the  building code. Other exterior openings shall not be located within 3 feet (914  mm) of such terminations.

    506.3.12.3Termination location. Exhaust outlets shall be located not less  than 10 feet (3048 mm) horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet (3048 mm) above the adjoining grade level. Exhaust

    outlets shall be located not less than 10 feet (3048 mm) horizontally from or  not less than 3 feet (914 mm) above air intake openings into any building.

    Exception: Exhaust outlets shall terminate not less than 5 feet (1524  mm) from parts of the same or contiguous building, an adjacent building, adjacent property line and air intake openings into a building where air from the exhaust outlet discharges away from such locations.

    506.4Ducts serving Type II hoods. Single or combined Type II exhaust systems for food-processing operations shall be independent of all other exhaust systems.  Commercial kitchen exhaust systems serving Type II hoods shall comply with Sections 506.4.1 and 506.4.2.

    506.4.1Ducts. Ducts and plenums serving Type II hoods shall be constructed of rigid metallic materials. Duct construction, installation, bracing and supports shall comply with Chapter 6. Ducts subject to positive  pressure and ducts conveying moisture-laden or waste-heat-laden air shall be constructed, joined and sealed in an approved manner.

    506.4.2Type II terminations. Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all of the following:

    1.      Exhaust outlets shall terminate not less than 3 feet (914 mm) in any direction from openings into the building.

    2.      Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot.

    3.      Outlets shall terminate not less than 10 feet (3048 mm) above grade.

    4.      Outlets that terminate above a roof shall terminate not less than 30  inches (762 mm) above the roof surface.

    5.      Outlets shall terminate not less than 30 inches (762 mm) from exterior  vertical walls

    6.      Outlets shall be protected against local weather conditions.

    7.      Outlets shall not be directed onto walkways.

    8.      Outlets shall meet the provisions for exterior wall opening protectives in accordance with the building code.

    506.5Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be of an approved design or shall be listed for the application.

    506.5.1Exhaust fans. Exhaust fan housings serving a Type I hood shall be constructed as required for grease ducts in accordance with Section 506.3.1.1.

    Exception: Fans listed and labeled in accordance with UL 762.

    506.5.1.1 Fan motor. Exhaust fan motors shall be located outside of the

    exhaust airstream.

    506.5.2Exhaust fan discharge. Exhaust fans shall be positioned so that the discharge will not impinge on the roof, other equipment or appliances or parts  of the structure. A vertical discharge fan shall be manufactured with an approved drain outlet at the lowest point of the housing to permit drainage of  grease to an approved grease reservoir.

    506.5.3Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches (457 mm) above the roof  surface.

    506.5.4Clearances. Exhaust equipment serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm).

    Exception: Factory-built exhaust equipment installed in accordance with Section 304.1 and listed for a lesser clearance.

    506.5.5Termination location. The outlet of exhaust equipment serving Type I hoods shall be in accordance with Section 506.3.12.

    Exception: The minimum horizontal distance between vertical discharge  fans and parapet-type building structures shall be 2 feet (610 mm) provided that such structures are not higher than the top of the fan discharge opening.

    SECTION 507 COMMERCIAL KITCHEN HOODS

    507.1General. Commercial kitchen exhaust hoods shall comply with the requirements of this section. Hoods shall be Type I or II and shall be designed to capture and confine cooking vapors and residues. Commercial kitchen exhaust  hood systems shall operate during the cooking operation.

    Exceptions:

    1.      Factory-built commercial exhaust hoods which are tested in accordance with UL 710, listed, labeled and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4, 507.7, 507.11, 507.12, 507.13, 507.14 and 507.15.

    2.      Factory-built commercial cooking recirculating systems which are tested in accordance with UL 710B, listed, labeled and installed in accordance with Section 304.1 shall not be required to comply with Sections 507.4, 507.5, 507.7, 507.12, 507.13, 507.14 and 507.15. Spaces in which such systems are located shall be considered to be kitchens and shall be venti- lated in accordance with Table 403.3. For the purpose of determining the

    floor area required to be ventilated, each individual appliance shall be

    2

    considered as occupying not less than 100 square feet (9.3 m ).

    3.      Net exhaust volumes for hoods shall be permitted to be reduced during  part-load cooking conditions, where engineered or listed multispeed or  variable-speed controls automatically operate the exhaust system to maintain capture and removal of cooking effluents as required by this section. Reduced volumes shall not be below that required to maintain capture and removal of effluents from the idle cooking appliances that are operating in a standby mode.

    507.2Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2.  Where any cooking appliance under a single hood requires a Type I hood, a Type  I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed.

    507.2.1 Type I hoods. Type I hoods shall be installed where cooking appliances produce grease or smoke, such as occurs with griddles, fryers,  broilers, ovens, ranges, wok ranges, salamanders, tilting skillets, and rotisseries.

     Exceptions:

    1.A Type I hood is not required for a single light-duty electric convection, bread, retherm or microwave oven provided that the additional heat and moisture loads generated by such appliances are accounted for in the design of the HVAC system.

    2.A Type II hood may be installed in lieu of a Type I hood over ovens where grease laden vapors or smoke are generated in quantities that do not constitute a hazard.

    507.2.1.1 Operation. Type I hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods.

    507.2.2.Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do  not produce grease or smoke, such as steamers, kettles, pasta cookers, cheese- melters, ovens, and dishwashing machines.

    Exceptions:

    1.    A Type II hood is not required for Under-counter-type commercial  dishwashing machines.

    2.    A Type II hood is not required for dishwashers and potwashers that are provided with heat and water vapor exhaust systems that are supplied

    by the appliance manufacturer and are installed in accordance with the manufacturer's instructions.

    3. A Type II hood is not required for a single light-duty electric convection, bread, retherm or microwave oven provided that the additional heat and moisture loads generated by such appliances are  accounted for in the design of the HVAC system.

    4. A Type II hood is not required for the following electrically heated appliances: toasters, popcorn poppers, hot dog cookers, coffee makers,  rice cookers, egg cookers, holding/warming ovens provided that the  additional heat and moisture loads generated by such appliances are  accounted for in the design of the HVAC system.

    507.2.3Domestic cooking appliances used for commercial purposes.  Domestic cooking appliances utilized for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes in accordance with Sections 507.2, 507.2.1 and 507.2.2.

    507.2.4Extra-heavy-duty. Type I hoods for use over extra-heavy-duty cooking appliances shall not cover heavy-, medium-or light-duty appliances.  Such hoods shall discharge to an exhaust system that is independent of other exhaust systems.

    507.3Fuel-burning appliances. Where vented fuel-burning appliances are located in the same room or space as the hood, provisions shall be made to prevent the hood system from interfering with normal operation of the appliance vents.

    507.4Type I materials. Type I hoods shall be constructed of steel having a minimum thickness of 0.0466 inch (1.181 mm) (No. 18 gage) or stainless steel not  less than 0.0335 inch [0.8525 mm (No. 20 MSG)] in thickness.

    507.5Type II hood materials. Type II hoods shall be constructed of steel having a minimum thickness of 0.0296 inch (0.7534 mm) (No. 22 gage) or stainless steel not less than 0.0220 inch (0.5550 mm) (No. 24 gage) in thickness, copper sheets

    2

    weighing not less than 24 ounces per square foot (7.3 kg/m ) or of other approved

    material and gage.

    507.6Supports. Type I  hoods shall be secured in  place by noncombustible  supports. All Type I and Type II hood supports shall be adequate for the applied load of the hood, the unsupported ductwork, the effluent loading and the possible weight of personnel working in or on the hood.

    507.7Hood joints, seams and penetrations. Hood joints, seams and penetrations shall comply with Sections 507.7.1 and 507.7.2.

    507.7.1Type I hoods. External hood joints, seams and penetrations for Type I hoods shall be made with a continuous external liquid-tight weld or braze to the lowest outermost perimeter of the hood. Internal hood joints, seams, penetra- tions, filter support frames and other appendages attached inside the hood shall

    not be required to be welded or brazed but shall be otherwise sealed to be grease tight.

    Exceptions:

    1.Penetrations shall not be required to be welded or brazed where sealed  by devices that are listed for the application.

    2.Internal welding or brazing of seams, joints and penetrations of the  hood shall not be prohibited provided that the joint is formed smooth or ground so as to not trap grease, and is readily cleanable.

    507.7.2Type II hoods. Joints, seams and penetrations for Type II hoods shall be constructed as set forth in Chapter 6, shall be sealed on the interior of the  hood and shall provide a smooth surface that is readily cleanable and water tight.

    507.8Cleaning and grease gutters. A hood shall be designed to provide for  thorough cleaning of the entire hood. Grease gutters shall drain to an approved collection receptacle that is fabricated, designed and installed to allow access for cleaning.

    507.9Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).

    Exception: Clearance shall not be required from gypsum wallboard or

    1

    /2-inch

    (12.7 mm) or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.

    507.10Hoods penetrating a ceiling. Type I hoods or portions thereof penetrating a ceiling, wall or furred space shall comply with all the requirements of Section  506.3.10.

    507.11Grease filters. Type I hoods shall be equipped with listed grease filters designed for the specific purpose. Grease-collecting equipment shall be provided with access for cleaning. The lowest edge of a grease filter located above the cooking surface shall be not less than the height specified in Table 507.11.

    TABLE 507.11

    MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A GREASE FILTER AND THE COOKING SURFACE OR THE  HEATING SURFACE

     

    TYPE OF COOKING APPLIANCES

    HEIGHT ABOVE COOKING SURFACE

    (feet)

    Without exposed flame

    0.5

    Exposed flame and burners

    2

    Exposed charcoal and charbroil type

    3.5

                                            For SI: 1 foot = 304.8 mm.

    507.11.1Criteria. Filters shall be of such size, type and arrangement as will permit the required quantity of air to pass through such units at rates not exceeding those for which the filter or unit was designed or approved. Filter units shall be installed in frames or holders so as to be readily removable without the use of separate tools, unless designed and installed to be cleaned in place and the system is equipped for such cleaning in place. Removable filter units shall be of a size that will allow them to be cleaned in a dishwashing  machine or pot sink. Filter units shall be arranged in place or provided with drip-intercepting devices to prevent grease or other condensate from dripping into food or on food preparation surfaces.

    507.11.2Mounting position. Filters shall be installed at an angle of not less  than 45 degrees (0.79 rad) from the horizontal and shall be equipped with a drip tray beneath the lower edge of the filters.

    507.12Canopy size and location. The inside lower edge of canopy-type Type I  and II commercial hoods shall overhang or extend a horizontal distance of not less  than 6 inches (152 mm) beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of  the hood and such surface shall not exceed 4 feet (1219 mm).

    Exception: The hood shall be permitted to be flush with the outer edge of the cooking surface where the hood is closed to the appliance side by a noncombustible wall or panel.

    507.13Capacity of hoods. Commercial food service hoods shall exhaust a minimum net quantity of air determined in accordance with this section and Sections 507.13.1 through 507.13.4. The net quantity of exhaust air shall be calculated by subtracting any airflow supplied directly to a hood cavity from the total exhaust flow rate of a hood. Where any combination of heavy-duty, medium-  duty and light-duty cooking appliances are utilized under a single hood, the exhaust rate required by this section for the heaviest duty appliance covered by  the hood shall be used for the entire hood. See Chapter 2 of this code for the definitions of light-duty, medium-duty, heavy-duty, and extra-heavy-duty cooking appliances.

    507.13.1Extra-heavy-duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for extra-heavy-duty cooking appliances shall be determined as follows:

    Type of Hood CFM per linear foot of hood  Backshelf/pass-over                                            Not allowed Double island canopy                                            (per side) 550  Eyebrow    Not allowed Single island canopy  700

    Wall-mounted canopy        550

    For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.

    507.13.2Heavy-duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for heavy-duty cooking appliances shall be determined as follows:

    Type of Hood CFM per linear foot of hood

    Backshelf/pass-over                400

    Double island canopy          (per side) 400  Eyebrow    Not allowed Single island canopy  600

    Wall-mounted canopy        400

    For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.

    507.13.3Medium-duty cooking appliances. The minimum net airflow for hoods, as determined by Section 507.2, used for medium-duty cooking appliances shall be determined as follows:

    Type of Hood         CFM per linear foot of hood

    Backshelf/pass-over                300 Double island canopy(per side) 300  Eyebrow 250  Single island canopy                                 500  Wall-mounted canopy                                            300

    For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.

    507.13.4Light-duty cooking appliances. The minimum net airflow for hoods, as  determined by Section 507.2, used for light-duty cooking appliances and food  service preparation shall be determined as follows:

    Type of Hood             CFM per linear foot of hood Backshelf/pass-over                                                            250       Double island canopy (per side)                            250

    Eyebrow                                               250

    Single island canopy                            400  Wall-mounted canopy                                                 200

    For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.

    507.13.5Dishwashing appliances. The minimum net airflow for Type II hoods used for dishwashing appliances shall be 100 CFM per linear foot of hood  length.

    Exception: Dishwashing appliances and equipment installed in accordance with Section 507.2.2.

    507.14Noncanopy size and location. Noncanopy-type hoods shall be located a maximum of 3 feet (914 mm) above the cooking surface. The edge of the hood  shall be set back a maximum of 1 foot (305 mm) from the edge of the cooking surface.

    507.15Exhaust outlets. Exhaust outlets located within the hood shall be located  so as to optimize the capture of particulate matter. Each outlet shall serve not more than a 12-foot (3658 mm) section of hood.

    507.16Performance test. A performance test shall be conducted upon  completion and before final approval of the installation of a ventilation system serving commercial cooking appliances. The test shall verify the rate of exhaust airflow required by Section 507.13, makeup airflow required by Section 508 and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the tests.

    507.16.1 Capture and containment test. The permit holder shall verify capture and containment performance of the exhaust system. This field test shall be conducted with all appliances under the hood at operating temperatures, with all  sources of outdoor air providing makeup air for the hood operating and with all  sources of recirculated air providing conditioning for the space in which the hood  is located operating. Capture and containment shall be verified visually by  observing smoke or steam produced by actual or simulated cooking, such as with smoke candles, smoke puffers, etc.

    SECTION 508 COMMERCIAL KITCHEN MAKEUP AIR

    508.1Makeup air. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup air supplied to the building from all sources  shall be approximately equal to the amount of exhaust air for all exhaust systems for the building. The makeup air shall not reduce the effectiveness of the exhaust

    system. Makeup air shall be provided by gravity or mechanical means or both. Mechanical makeup air systems shall be automatically controlled to start and operate simultaneously with the exhaust system. Makeup air intake opening locations shall comply with Section 401.4.

    508.1.1 Makeup air temperature. The temperature differential between makeup air and the air in the conditioned space shall not exceed 10ºF (6ºC).

    Exceptions:

    1.      Makeup air that is part of the air-conditioning system.

    2.      Makeup air that does not decrease the comfort conditions of the occupied space.

    508.2Compensating hoods. Manufacturers of compensating hoods shall provide a label indicating minimum exhaust flow and/or maximum makeup airflow that provides capture and containment of the exhaust effluent.

    Exception: Compensating hoods with makeup air supplied only from the front face discharge and side face discharge openings shall not be required to be labeled with the maximum makeup airflow.

    SECTION 509

    FIRE SUPPRESSION SYSTEMS

    509.1 Where required. Commercial cooking appliances required by Section 507.2.1 to have a Type I hood shall be provided with an approved automatic fire  suppression system complying with the building code and the fire code.

    SECTION 510 HAZARDOUS EXHAUST SYSTEMS

    510.1General. This section shall govern the design and construction of duct systems for hazardous exhaust and shall determine where such systems are required. Hazardous exhaust systems are systems designed to capture and control hazardous emissions generated from product handling or processes, and convey those emissions to the outdoors. Hazardous emissions include flammable vapors, gases, fumes, mists or dusts, and volatile or airborne materials posing a health hazard, such as toxic or corrosive materials. For the purposes of this section, the health hazard rating of materials shall be as specified in NFPA 704.

    For the purposes of the provisions of Section 510, a laboratory shall be defined  as a facility where the use of chemicals is related to testing, analysis, teaching, research or developmental activities. Chemicals are used or synthesized on a

    nonproduction basis, rather than in a manufacturing process.

    510.2Where required. A hazardous exhaust system shall be required wherever operations involving the handling or processing of hazardous materials, in the absence of such exhaust systems and under normal operating conditions, have the potential to create one of the following conditions:

    1.      A flammable vapor, gas, fume, mist or dust is present in concentrations  exceeding 25 percent of the lower flammability limit of the substance for the expected room temperature.

    2.      A vapor, gas, fume, mist or dust with a health-hazard rating of 4 is present in any concentration.

    3.      A vapor, gas, fume, mist or dust with a health-hazard rating of 1, 2 or 3 is present in concentrations exceeding 1 percent of the median lethal concentration of the substance for acute inhalation toxicity.

    Exception: Laboratories, as defined in Section 510.1, except where the concentrations listed in Item 1 are exceeded or a vapor, gas, fume, mist or dust with a health-hazard rating of 1, 2, 3 or 4 is present in concentrations exceeding  1 percent of the median lethal concentration of the substance for acute inhalation toxicity.

    510.2.1Lumber yards and woodworking facilities.

    Equipment or machinery located inside buildings at lumber yards and  woodworking facilities which generates or emits combustible dust shall be provided with an approved dust-collection and exhaust system installed in conformance with this section and the fire code. Equipment and systems that are used to collect, process or convey combustible dusts shall be provided with an approved explosion-control system.

    510.2.2Combustible fibers. Equipment or machinery within a building which generates or emits combustible fibers shall be provided with an approved dust-  collecting and exhaust system. Such systems shall comply with this code and the fire code.

    510.3Design and operation. The design and operation of the exhaust system shall be such that flammable contaminants are diluted in noncontaminated air to maintain concentrations in the exhaust flow below 25 percent of the contaminant's lower flammability limit.

    510.4Independent system. Hazardous exhaust systems shall be independent of  other types of exhaust systems. Incompatible materials shall not be exhausted through the same hazardous exhaust system. Hazardous exhaust systems shall not share common shafts with other duct systems, except where such systems are haz- ardous exhaust systems originating in the same fire area.

    Exception: The provision of this section shall not apply to laboratory exhaust systems where all of the following conditions apply:

    1.      All of the hazardous exhaust ductwork and other laboratory exhaust within both the occupied space and the shafts are under negative pressure while in operation.

    2.      The hazardous exhaust ductwork manifolded together within the occupied  space must originate within the same fire area.

    3.      Each control branch has a flow regulating device.

    4.      Perchloric acid hoods and connected exhaust shall be prohibited from manifolding.

    5.      Radioisotope hoods are equipped with filtration and/or carbon beds where required by the registered design professional.

    6.      Biological safety cabinets are filtered.

    7.      Provision is made for continuous maintenance of negative static pressure  in the ductwork.

    Contaminated air shall not be recirculated to occupiable areas. Air containing  explosive or flammable vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radioactive material shall be considered to be contaminated.

    510.5Design. Systems for removal of vapors, gases and smoke shall be designed  by the constant velocity or equal friction methods. Systems conveying particulate matter shall be designed employing the constant velocity method.

    510.5.1Balancing. Systems conveying explosive or radioactive materials shall be prebalanced by duct sizing. Other systems shall be balanced by duct sizing with balancing devices, such as dampers. Dampers provided to balance airflow shall be provided with securely fixed minimum-position blocking devices to prevent restricting flow below the required volume or velocity.

    510.5.2Emission control. The design of the system shall be such that the emissions are confined to the area in which they are generated by air currents,  hoods or enclosures and shall be exhausted by a duct system to a safe location  or treated by removing contaminants.

    510.5.3Hoods required. Hoods or enclosures shall be used where contaminants originate in a limited area of a space. The design of the hood or  enclosure shall be such that air currents created by the exhaust systems will capture the contaminants and transport them directly to the exhaust duct.

    510.5.4Contaminant capture and dilution. The velocity and circulation of air in work areas shall be such that contaminants are captured by an airstream at the area where the emissions are generated and conveyed into a product-con- veying  duct  system.  Contaminated  air  from  work  areas  where  hazardous

    contaminants are generated shall be diluted below the thresholds specified in Section 510.2 with air that does not contain other hazardous contaminants.

    510.5.5Makeup air. Makeup air shall be provided at a rate approximately equal to the rate that air is exhausted by the hazardous exhaust system.  Makeup-air intakes shall be located so as to avoid recirculation of contaminated air.

    510.5.6Clearances. The minimum clearance between hoods and combustible construction shall be the clearance required by the duct system.

    510.5.7Ducts. Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through ducts and plenums.

    510.6Penetrations. Penetrations of structural elements by a hazardous exhaust system shall conform to Sections 510.6.1 through 510.6.4.

    Exception:  Duct  penetrations  within  H-5  occupancies  as  allowed  by  the

    building code.

    510.6.1Fire dampers and smoke dampers. Fire dampers and smoke dampers are prohibited in hazardous exhaust ducts.

    510.6.2Floors. Hazardous exhaust systems that penetrate a floor/ceiling assembly shall be enclosed in a fire-resistance-rated shaft constructed in accordance with the building code.

    510.6.3Wall assemblies. Hazardous exhaust duct systems that penetrate fire- resistance-rated wall assemblies shall be enclosed in fire-resistance-rated construction from the point of penetration to the outlet terminal, except where the interior of the duct is equipped with an approved automatic fire suppression  system. Ducts shall be enclosed in accordance with the building code  requirements for shaft construction and such enclosure shall have a minimum  fire-resistance-rating of not less than the highest fire-resistance-rated wall assembly penetrated.

    510.6.4Fire walls. Ducts shall not penetrate a fire wall.

    510.7Suppression  required.  Ducts  shall  be  protected  with  an  approved automatic fire suppression system installed in accordance with the building code.

    Exceptions:

    1.      An approved automatic fire suppression system shall not be required in ducts conveying materials, fumes, mists and vapors that are nonflammable and noncombustible under all conditions and at any concentrations.

    2.      An approved automatic fire suppression system shall not be required in ducts where the largest cross-sectional diameter of the duct is less than 10 inches  (254 mm).

    3.      For laboratories, as defined in Section 510.1, automatic fire protection systems shall not be required in laboratory hoods or exhaust systems.

    510.8Duct construction. Ducts used to convey hazardous exhaust shall be constructed of approved G90 galvanized sheet steel, with a minimum nominal thickness as specified in Table 510.8. Nonmetallic ducts used in systems  exhausting nonflammable corrosive fumes or vapors shall be listed and labeled.

    Nonmetallic ducts shall have a flame spread index of 25 or less and a smoke- developed index of 50 or less, when tested in accordance with ASTM E 84 or UL 723. Ducts shall be approved for installation in such an exhaust system. Where the products being exhausted are detrimental to the duct material, the ducts shall be constructed of alternative materials that are compatible with the exhaust.

    TABLE 510.8 MINIMUM DUCT THICKNESS

    DIAMETER OF DUCT OR MAXIMUM SIDE DIMENSION

    MINIMUM NOMINAL THICKNESS

     

    Nonabrasive materials

    Nonabrasive/ Abrasive materials

     

    Abrasive materials

    0-8 inches

    0.028 inch (No. 24 gage)

    0.034 inch (No. 22 gage)

    0.040 inch (No. 20 gage)

    9-18 inches

    0.034 inch (No. 22 gage)

    0.040 inch (No. 20 gage)

    0.052 inch (No. 18 gage)

    19-30 inches

    0.040 inch (No. 20 gage)

    0.052 inch (No. 18 gage)

    0.064 inch (No. 16 gage)

    Over 30 inches

    0.052 inch (No. 18 gage)

    0.064 inch (No. 16 gage)

    0.079 inch (No. 14 gage)

    For SI: 1 inch = 25.4 mm.

    510.8.1Duct joints. Ducts shall be made tight with lap joints having a minimum lap of 1 inch (25 mm).

    510.8.2Clearance to combustibles. Ducts shall have a clearance to combustibles in accordance with Table 510.8.2. Exhaust gases having temperatures in excess of 600ºF (316ºC) shall be exhausted to a chimney in accordance with Section 511.2.

    TABLE 510.8.2 CLEARANCE TO COMBUSTIBLES

     

    TYPE OF EXHAUST OR TEMPERATURE OF EXHAUST (ºF)

    CLEARANCE TO COMBUSTIBLES

    (inches)

    Less than 100

    1

    100-600

    12

    Flammable vapors

    6

    For SI: 1 inch = 25.4 mm, ºC = [(ºF)- 32]/1.8.

    510.8.3Explosion relief. Systems exhausting potentially explosive mixtures shall be protected with an approved explosion relief system or by an approved explosion prevention system designed and installed in accordance with NFPA 69. An explosion relief system shall be designed to minimize the structural and mechanical damage resulting from an explosion or deflagration within the exhaust system. An explosion prevention system shall be designed to prevent an explosion or deflagration from occurring.

    510.9Supports. Ducts shall be supported at intervals not exceeding 10 feet (3048  mm). Supports shall be constructed of noncombustible material.

    SECTION 511

    DUST, STOCK AND REFUSE CONVEYING SYSTEMS

    511.1Dust, stock and refuse conveying systems. Dust, stock and refuse conveying systems shall comply with the provisions of Section 510 and Sections 511.1.1 through 511.2.

    511.1.1Collectors and separators. Collectors and separators involving such  systems as centrifugal separators, bag filter systems and similar devices, and associated supports shall be constructed of noncombustible materials and shall be located on the exterior of the building or structure. A collector or separator  shall not be located nearer than 10 feet (3048 mm) to combustible construction  or to an unprotected wall or floor opening, unless the collector is provided with a metal vent pipe that extends above the highest part of any roof with a distance  of 30 feet (9144 mm).

    Exceptions:

    1.      Collectors such as "Point of Use" collectors, close extraction weld fume collectors, spray finishing booths, stationary grinding tables, sanding booths, and integrated or machine-mounted collectors shall be permitted to be installed indoors provided the installation is in accordance with the fire code  and NFPA 70.

    2.      Collectors in independent exhaust systems handling combustible dusts shall be permitted to be installed indoors provided that such collectors are installed in compliance with the fire code and NFPA 70.

    511.1.2Discharge pipe. Discharge piping shall conform to the requirements for

    ducts, including clearances required for high-heat appliances, as contained in this code. A delivery pipe from a cyclone collector shall not convey refuse directly into the firebox of a boiler, furnace, dutch oven, refuse burner, incinerator or other appliance.

    511.1.3Conveying systems exhaust discharge. An exhaust system shall discharge to the outside of the building either directly by flue  or  indirectly through the bin or vault into which the system discharges except where the contaminants have been removed. Exhaust system discharge shall be permitted to be recirculated provided that the solid particulate has been removed at a minimum efficiency of 99.9 percent at 10 microns (10.01 mm), vapor concentrations are  less than 25 percent of the LFL, and approved equipment is used to monitor the vapor concentration.

    511.1.4Spark protection. The outlet of an open-air exhaust terminal shall be protected with an approved metal or other noncombustible screen to prevent the entry of sparks.

    511.1.5Explosion relief vents. A safety or  explosion relief vent  shall be provided on all systems that convey combustible refuse or stock of an explosive nature, in accordance with the requirements of the building code.

    511.1.5.1Screens. Where a screen is installed in a safety relief vent, the screen shall be attached so as to permit ready release under the explosion  pressure.

    511.1.5.2Hoods.  The  relief  vent  shall  be  provided  with  an  approved noncombustible cowl or hood, or with a counterbalanced relief valve or  cover arranged to prevent the escape of hazardous materials, gases or liquids.

    511.2Exhaust outlets. Outlets for exhaust that exceed 600ºF (315ºC) shall be designed as a chimney in accordance with Table 511.2.

    SECTION 512

    SUBSLAB SOIL EXHAUST SYSTEMS

    512.1General. When a subslab soil exhaust system is provided, the duct shall conform to the requirements of this section.

    512.2Materials. Subslab soil exhaust system duct material shall be air duct material listed and labeled to the requirements of UL 181 for Class 0 air ducts, or  any of the following piping materials that comply with the plumbing code as  building sanitary drainage and vent pipe: cast iron; galvanized steel; brass or  copper pipe; copper tube of a weight not less than that of copper drainage tube, Type DWV; and plastic piping.

    512.3Grade. Exhaust system ducts shall not be trapped and shall have a minimum slope of one-eighth unit vertical in 12 units horizontal (1-percent slope).

    512.4Termination. Subslab soil exhaust system ducts shall extend through the roof and terminate at least 6 inches (152 mm) above the roof and at least 10 feet  (3048 mm) from any operable openings or air intake.

    TABLE 511.2

    CONSTRUCTION, CLEARANCE AND TERMINATION REQUIREMENTS FOR SINGLE-WALL METAL CHIMNEYS

     

     

     

     

    CHIMNEYS SERVING

    MINIMUM THICKNESS

    TERMINATION

    CLEARANCE

     

     

     

     

    Walls (inch)

     

     

     

     

    Lining

     

    Above roof opening (feet)

    Above any part of building within (feet)

    Combustible construction (inches)

     

    Noncombustible construction

     

    10

     

    25

     

    50

    Interior inst.

    Exterior inst.

    Interior inst.

    Exterior inst.

    High-heat appliances (Over 2,000ºF)a

    0.127

    (No. 10 MSG)

    41/2 ?laid on 41/2 ?  bed

     

    20

     

    -

     

    -

     

    20

     

    See Note c

    Low-heat appliances (1,000ºF normal operation)

     

    0.127

    (No. 10 MSG)

     

    none

     

    3

     

    2

     

    -

     

    -

     

    18

     

    6

     

     

    Up to 18?diameter, 2?  Over 18?diameter, 4?

    Medium-heat appliances (2,000ºF maximum)b

    0.127

    (No. 10 MSG)

    Up to 18?dia.-2 ½?  Over 18?-41/2 ?

    On 41/2 ?bed

     

    10

     

    -

     

    10

     

    -

     

    36

     

    24

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, ºC = [(ºF)-32]/1.8.

    a. Lining shall extend from bottom to top of outlet.

    b.Lining shall extend from 24 inches below connector to 24 feet above.

    c. Clearance shall be as specified by the design engineer and shall have sufficient clearance from buildings and structures to avoid overheating combustible materials (maximum 160ºF).

    512.5Identification. Subslab soil exhaust ducts shall be permanently identified  within each floor level by means of a tag, stencil or other approved marking.

    SECTION 513 SMOKE CONTROL SYSTEMS

    513.1Scope and purpose. This section applies to mechanical and passive smoke control systems that are required by the building code. The purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations,  or for assistance in fire suppression or overhaul activities. Smoke control systems

    regulated by this section serve a different purpose than the smoke-and heat- venting provisions found in Section 910 of the building code.

    513.2General design requirements. Buildings, structures, or parts thereof required by this code to have a smoke control system or systems shall have such  systems designed in accordance with the applicable requirements of Section 909 of the building code and the generally accepted and well-established principles of  engineering relevant to the design. The construction documents shall include  sufficient information and detail to describe adequately the elements of the design  necessary for the proper implementation of the smoke control systems. These documents shall be accompanied with sufficient information and analysis to demonstrate compliance with these provisions.

    513.3Special inspection and test requirements. In addition to the ordinary inspection and test requirements which buildings, structures and parts thereof are required to undergo, smoke control systems subject to the provisions of Section  909 of the building code shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its final installed condition. The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such  inspections and tests. Such commissioning shall be in accordance with generally accepted engineering practice and, where possible, based on published standards for the particular testing involved. The special inspections and tests required by  this section shall be conducted under the same terms as found in Section 1704 of  the building code.

    513.4Analysis. A rational analysis supporting the types of smoke control systems  to be employed, their methods of operation, the systems supporting them and the methods of construction to be utilized shall accompany the submitted construction  documents and shall include, but not be limited to, the items indicated in Sections  513.4.1 through 513.4.6.

    513.4.1Stack effect. The system shall be designed such that the maximum probable normal or reverse stack effects will not adversely interfere with the system's capabilities. In determining the maximum probable stack effects, altitude, elevation, weather history and interior temperatures shall be used.

    513.4.2Temperature effect of fire. Buoyancy and expansion caused by the design fire in accordance with Section 513.9 shall be analyzed. The system shall be designed such that these effects do not adversely interfere with its capabilities.  513.4.3 Wind effect. The design shall consider the adverse effects of wind. Such  consideration shall be consistent with the wind-loading provisions of the building code.

    513.4.4HVAC systems. The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis shall include all permutations of systems' status. The

    design shall consider the effects of fire on the HVAC systems.

    513.4.5Climate. The design shall consider the effects of low temperatures on  systems, property and occupants. Air inlets and exhausts shall be located so as to prevent snow or ice blockage.

    513.4.6Duration of operation. All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event  for a period of not less than either 20 minutes or 1.5 times the calculated egress  time, whichever is less.

    513.5 Smoke barrier construction. Where provided, smoke barriers shall comply  with the building code. Smoke barriers shall be constructed and sealed to limit leakage areas exclusive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the following leak age area ratios:

    1. Walls:                   A/Aw    = 0.00100

    2.  Exit enclosures:   A/Aw = 0.00035

    3.  All other shafts:   A/Aw = 0.00150

    4.  Floors and roofs: A/AF = 0.00050  where:

    2

    A = Total leakage area, square feet (m ).

    2

    AF = Unit floor or roof area of barrier, square feet (m ).

    2

    Aw = Unit wall area of barrier, square feet (m ).

    The leakage area ratios shown do not include openings due to doors, operable  windows or similar gaps. These shall be included in calculating the total leakage area.

    513.5.1 Leakage area. Total leakage area of the barrier is the product of the smoke barrier gross area times the allowable leakage area ratio, plus the area of  other openings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official.

      513.5.2 Opening protection. Openings in smoke barriers shall be protected  by automatic-closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by door  assemblies complying with the requirements of the building code for doors in smoke barriers.

    Exceptions:

    1.      Passive smoke control systems with automatic-closing devices actuated by

    spot-type smoke detectors listed for releasing service installed in accordance with the building code.

    2.      Fixed openings between smoke zones which are protected utilizing the airflow method.

    3.      In Group I-2 where such doors are installed across corridors, a pair of  opposite-swinging doors without a center mullion shall be installed having vision panels with approved fire-rated glazing materials in approved fire-rated frames, the area of which shall not exceed that tested. The doors shall be close-fitting within operational tolerances, and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or  rabbets at meeting edges and automatic-closing devices. Positive latching devices are not required.

    4.      Group I-3.

    5.      Openings between smoke zones with clear ceiling heights of 14 feet (4267  mm) or greater and bank down capacity of greater than 20 minutes as deter- mined by the design fire size.

    513.5.2.1 Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250ºF (121ºC) smoke damper complying with the building code.

    513.6Pressurization method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke control zone of fire origin.

    513.6.1Minimum pressure difference. The minimum pressure difference across  a smoke barrier shall be 0.05-inch water gage (12.4 Pa) in fully sprinklered build- ings.

    In buildings permitted to be other than fully sprinklered, the smoke control system shall be designed to achieve pressure differences at least two times the maximum calculated pressure difference produced by the design fire.

    513.6.2Maximum pressure difference. The maximum air pressure difference  across a smoke barrier shall be determined by required door-opening or closing forces. The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with the building code. Opening and closing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reactions. The calculated force to set a side-hinged, swinging door in motion shall be determined by:

    F = Fdc+K(WA?P)/2(W-d)                          (Equation 5-2)

    where:

    2

    A = Door area, square feet (m ).

    d =  Distance from door handle to latch edge of door, feet (m).

    F = Total door opening force, pounds (N).

    Fdc = Force required to overcome closing device, pounds (N). K = Coefficient 5.2 (1.0).

    W = Door width, feet (m).

    ?P = Design pressure difference, inches (Pa) water gage.

    513.7Airflow design method. When approved by the building official, smoke migration through openings fixed in a permanently open position, which are located between smoke control zones by the use of the airflow method, shall be permitted. The design airflows shall be in accordance with this section. Airflow  shall be directed to limit smoke migration from the fire zone. The geometry of  openings shall be considered to prevent flow reversal from turbulent effects.

    513.7.1Velocity. The minimum average velocity through a fixed opening shall not be less than:

    v = 217.2 [h (Tf -To)/(Tf + 460)]

    1/2

    (Equation 5-3)

    1/2

    For SI: v = 119.9 [h (Tf -To)/Tf]

    where:

    H = Height of opening, feet (m).

    Tf = Temperature of smoke, ºF (K).

    To= Temperature of ambient air, ºF (K).

    v = Air velocity, feet per minute (m/minute).

    513.7.2Prohibited conditions. This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. In no case shall airflow toward the fire exceed 200 feet per minute (1.02 m/s). Where the formula in Section  513.7.1 requires airflow to exceed this limit, the airflow method shall not be  used.

    513.8Exhaust method. When approved by the building official, mechanical smoke control for large enclosed volumes, such as in atriums  or malls, shall be permitted to utilize the exhaust method. Smoke control systems using the exhaust method shall be designed in accordance with  NFPA 92B.

    513.8.1 Exhaust rate. The height of the lowest horizontal surface of the accumulating smoke layer shall be maintained at least 6 feet (1829 mm)  above any walking surface which forms a portion of a required egress

    system within the smoke zone.

    513.9Design fire. The design fire shall be based on a rational analysis performed by the registered design professional and approved by the building official. The design fire shall be based on the analysis in accordance with Section 513.4 and this section.

    513.9.1Factors considered. The engineering analysis shall include the characteristics of the fuel, fuel load, effects included by the fire and whether the  fire is likely to be steady or unsteady.

    513.9.2Design fire fuel. Determination of the design fire shall include consideration of the type of fuel, fuel spacing and configuration.

    513.9.3Heat-release assumptions. The analysis shall make use of the best available data from approved sources and shall not be based on excessively stringent limitations of combustible material.

    513.9.4Sprinkler effectiveness assumptions. A documented  engineering analysis shall be provided for conditions that assume fire growth is halted at the time of sprinkler activation.

    513.10Equipment. Equipment such as, but not limited to, fans, ducts, automatic dampers and balance dampers shall be suitable for their intended use, suitable for  the probable exposure temperatures that the rational analysis indicates, and as  approved by the building official.

    513.10.1Exhaust fans. Components of exhaust fans shall be rated and certified  by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by:

    Ts =(Qc/mc)+(Ta)                              (Equation 5-4)

    where:

    c =  Specific heat of smoke at smoke-layer temperature, Btu/lbºF (kJ/kg ×K).  m = Exhaust rate, pounds per second (kg/s).

    Qc = Convective heat output of fire, Btu/s (kW).

    Ta = Ambient temperature, ºF (K).

    Ts = Smoke temperature, ºF (K).

    Exception: Reduced Ts  as calculated based on the assurance of adequate dilution air.

    513.10.2Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed as determined in accordance with Section 513.10.1. Ducts shall be constructed and supported in accordance with Chapter 6. Ducts shall be leak tested to 1.5 times the maximum design pressure in accordance with nationally accepted practices.

    Measured leakage shall not exceed 5 percent of design flow. Results of such  testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire-resistance-rated structural elements of the building by  substantial, noncombustible supports.

    Exception: Flexible connections, for the purpose of vibration isolation, that are constructed of approved fire-resistance-rated materials.

    513.10.3Equipment, inlets and outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard.  Outdoor air inlets shall be located so as to minimize the potential for introduc- ing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard.

    513.10.4Automatic dampers. Automatic dampers, regardless of the purpose for  which they are installed within the smoke control system, shall be listed and conform to the requirements of Section 607.3.

    513.10.5Fans. In addition to other requirements, belt-driven fans shall have 1.5  times the number of belts required for the design duty with the minimum number  of belts being two. Fans shall be selected for stable performance based on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer's fan curves shall be part of the documentation procedures. Fans  shall be supported and restrained by noncombustible devices in accordance with the structural design requirements of the building code. Motors driving fans shall not be operating beyond their nameplate horsepower (kilowatts) as determined from measurement of actual current draw. Motors driving fans shall have a mini- mum service factor of 1.15.

    513.11Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be the normal building power systems.  Secondary power shall be from an approved standby source complying with Chapter 27 of the building code. The standby power source and its transfer switches shall be in a room separate from the normal power transformers and switch gear and ventilated directly to and from the exterior. The room shall be enclosed with not less than 1-hour fire-resistance-rated fire barriers constructed in accordance with Section 707 of the building code or horizontal assemblies  constructed in accordance with Section 712 of the building code, or both. Power  distribution from the two sources shall be by independent routes. Transfer to full standby power shall be automatic and within 60 seconds of failure of the primary  power. The systems shall comply with NFPA 70.

    513.11.1Power sources and power surges. Elements of the smoke management system relying on volatile memories or the like shall be supplied with uninterruptible power sources of sufficient duration to span 15-minute primary  power  interruption.  Elements  of  the  smoke  management  system

    susceptible to power surges shall be suitably protected by conditioners,  suppressors or other approved means.

    513.12Detection and control systems. Fire detection systems providing control input or output signals to mechanical smoke control systems or elements thereof shall comply with the requirements of Chapter 9 of the building code and NFPA 72. Such systems shall be equipped with a control unit complying with UL 864  and listed as smoke control equipment.

    Control systems for mechanical smoke control systems shall include provisions  for verification. Verification shall  include positive confirmation  of actuation, testing, manual override, the presence of power downstream of all disconnects and, through a preprogrammed weekly test sequence report, abnormal conditions audibly, visually and by printed report.

    513.12.1Wiring. In addition to meeting the requirements of NFPA 70, all wiring, regardless of voltage, shall be fully enclosed within continuous raceways.

    513.12.2Activation. Smoke control systems shall be activated in accordance with the building code.

    513.12.3Automatic control. Where completely automatic control is required  or used, the automatic control sequences shall be initiated from an appropriately zoned automatic sprinkler system complying with Section  903.3.1.1 of the building code or from manual controls that are readily accessible to the fire department, and any smoke detectors required by  engineering analysis.

    513.13Control-air tubing. Control-air tubing shall be of sufficient size to meet the required response times. Tubing shall be flushed clean and dry prior to final connections. Tubing shall be adequately supported and protected from damage. Tubing passing through concrete or masonry shall be sleeved and protected from abrasion and electrolytic action.

    513.13.1Materials. Control-air tubing shall be hard-drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM  B 251 and ASTM B 280. Fittings shall be wrought copper or brass, solder type in accordance with ASME B 16.18 or ASME B 16.22. Changes in direction shall be made with appropriate tool bends. Brass compression-type fittings shall be used at final connection to devices; other joints shall be brazed using a BCuP5 brazing alloy with solidus above 1,100ºF (593ºC) and liquids below 1,500ºF (816ºC).  Brazing flux shall be used on copper-to-brass joints only.

    Exception: Nonmetallic tubing used within control panels and at the final connection to devices provided all of the following conditions are met:

    1.      Tubing  shall  be  listed  by  an  approved  agency  for  flame  and  smoke characteristics.

    2.      Tubing and connected device shall be completely enclosed within a galvanized or paint-grade steel enclosure having a minimum thickness of 0.0296 inch (0.7534 mm) (No. 22 gage). Entry to the enclosure shall be by  copper tubing with a protective grommet of Neoprene or Teflon or by suitable  brass compression to male barbed adapter.

    3.      Tubing shall be identified by appropriately documented coding.

    4.      Tubing shall be neatly tied and supported within the enclosure. Tubing bridging cabinets and doors or moveable devices shall be of sufficient length to avoid tension and excessive stress. Tubing shall be protected against abrasion. Tubing serving devices on doors shall be fastened along hinges.

     513.13.2 Isolation from  other  functions. Control  tubing serving  other than smoke control functions shall be isolated by automatic isolation valves or shall be an independent system.

    513.13.3 Testing. Test control-air tubing at three times the operating pressure for  not less than 30 minutes without any noticeable loss in gauge pressure prior to final connection to devices.

    513.14Marking and identification. The detection and control systems shall be clearly marked at all junctions, accesses and terminations.

    513.15Control diagrams. Identical control diagrams shall be provided and maintained as required by the building code.

    513.16Fire fighter's smoke control panel. A fire fighter's smoke control panel  for fire department emergency response purposes only shall be provided in accordance with the building code.

    513.17System response time. Smoke control system activation shall comply with the building code.

    513.18Acceptance testing. Devices, equipment, components and sequences shall be tested in accordance with the building code.

    513.19System acceptance. Acceptance of the smoke control system shall be in accordance with the building code.

    SECTION 514

    ENERGY RECOVERY VENTILATION SYSTEMS

    514.1General. Energy recovery ventilation systems shall be installed in accordance with this section. Where required for purposes of energy conservation, energy recovery ventilation systems shall also comply with the the applicable energy conservation code referenced from Chapter 13 of the building code.

    514.2Prohibited applications. Energy recovery ventilation systems shall not be  used in the following systems:

    1.      Hazardous exhaust systems covered in Section 510.

    2.      Dust, stock and refuse systems that convey explosive or flammable vapors,  fumes or dust.

    3.      Smoke control systems covered in Section 513.

    4.      Commercial kitchen exhaust systems serving Type I and Type II hoods.

    5.      Clothes dryer exhaust systems covered in Section 504.

    514.3Access. A means of access shall be provided to the heat exchanger and other components of the system as required for service, maintenance, repair or  replacement.

    Replaces:                                                     4101:2-5-01

    Effective:                                                     11/01/2011

    R.C. 119.032 review dates:                         11/01/2016

    CERTIFIED ELECTRONICALLY

    Certification

    04/18/2011

    Date

    Promulgated Under:                           119.03

    Statutory Authority:                           3781.10(A)

    Rule Amplifies:                                  3781.10, 3781.11, 3791.04

    Prior Effective Dates:                         1/1/02, 3/1/05, 9/6/05, 3/1/06, 7/1/07, 11/1/07

Document Information

Effective Date:
11/1/2011
File Date:
2011-04-18
Last Day in Effect:
2011-11-01
Rule File:
4101$2-5-01_PH_FF_N_RU_20110418_1145.pdf
Related Chapter/Rule NO.: (1)
Ill. Adm. Code 4101:2-5-01. Exhaust systems